RR2552 SPREAD SPECTRUM
REPEATER
Installation & Operation Instructions
Do not use this product in any safety related applications where human life may be affected.
GENERAL INFORMATION
The RR2552B repeater uses the reliable 900 MHz spread spectrum technology to work with any ACI wireless
system to boost or extend the range of wireless sensors and is easily installed. The RR2552B has an 8 position
dipswitch that is user selectable to set the address of the RR2552B to match the Network ID of the
receiver/transceiver in each system so there is no programming required. The RR2552B must be powered with 24
VAC. Two Duracell DL123 3V lithium batteries are included for temporary power to position the repeater before
nal installation and wiring. Without the use of the RR2552B wireless repeater, all systems will be a point to point
system, meaning that the sensor and transceiver will communicate directly with each other. Sensor distance and
reliability can be increased with the addition of a RR2552B(s) repeater. The RR2552B will work with all ACI wireless
sensors, receivers and transceivers.
MOUNTING INSTRUCTIONS
PRECAUTIONS
• To maintain high performance, do not install sensors, repeaters, or receivers in the following areas:
- Inside metal enclosure / panel
- Inside or immediately next to elevator shaft or elevator banks
- In front of or immediately next to large trees or large body of water
- Do not mount above false ceiling. Mount in wall 1" below ceiling.
- Use the battery option to determine mounting location before wiring.
- Do not put more then two RR2552B repeaters in series.
- Contact ACI Tech Support for further assistance.
SETTING REPEATABLE NETWORK ID
The RM2432 or MOD9200's has a network ID assigned to them through the con guration software (default
network ID of 1). If there are multiple ACI wireless systems running in a building at the same time, each
receiver or transceiver needs to have its own separate network ID # which is set through the con guration
software. If a repeater is added to a system, the repeater has Binary dip switches that must match the
network ID of the system the repeater is being added to. If there is only one ACI wireless system running,
the network ID is probably set to
default 1. With all the dip switches o
on the repeater, the default address
is binary "1" (default).
Example: To set the Network ID to "2",
depress the "+1" switch to "ON" to
add "1" to the Base ID of "1".
To set the Network ID to "3", set the
"+1" switch to "OFF", and the "+2"
switch to "ON" to add "2" to the Base
ID of "1" equaling "3". See Table 1 for
switch positions.
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
TABLE 1: REPEATABLE NETWORK ID SWITCH SETTING
Switch
Switch
Switch
#32
#16
#8
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
Page 1
Phone: 1-888-967-5224
Website: workaci.com
Switch
Switch
Switch
#4
#2
#1
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Version: 7.0
Network
Address
1
2
3
4
5
9
17
33
I0000666

Advertisement

loading

Summary of Contents for aci RR2552B

  • Page 1 The RR2552B repeater uses the reliable 900 MHz spread spectrum technology to work with any ACI wireless system to boost or extend the range of wireless sensors and is easily installed. The RR2552B has an 8 position dipswitch that is user selectable to set the address of the RR2552B to match the Network ID of the receiver/transceiver in each system so there is no programming required.
  • Page 2 The battery operated mode is intended to be used for site survey or powered to located the repeater and must be with 24 VAC for long term use. The RR2552B will last about 6 hours if used in battery mode.
  • Page 3 WIRING INSTRUCTIONS WIRING PRECAUTIONS • Remove power before wiring. NEVER connect or disconnect wiring with power applied. • The RR2552 is full wave rectified. • It is recommended that you use an isolated UL-listed Class 2 transformer when powering the unit with 24 VAC.
  • Page 4 Enclosure Material | Flammability Rating: WARRANTY The ACI Wireless Series are covered by ACI’s Two (2) Year Limited Warranty, which is located in the front of ACI’S SENSORS & TRANSMITTERS CATALOG or can be found on ACI’s website: www.workaci.com. W.E.E.E. DIRECTIVE At the end of their useful life the packaging and product should be disposed of via a suitable recycling centre.