Download Print this page
Dwyer Instruments PROXIMITY 185 Series Specifications-Installation And Operating Instructions

Dwyer Instruments PROXIMITY 185 Series Specifications-Installation And Operating Instructions

Smart positioners

Advertisement

Quick Links

Series 185
The Series 185 and 285 Smart Positioners control valve movements accurately
using an input signal of 4 to 20 mA from the controller. In addition, a highly efficient
microprocessing operator built into the product performs various functions such as
auto calibration, PID control, alarm and Hart
Features
• LCD allows the user to directly check the positioner condition in the field.
• Endures severe vibration.
• Operates normally regardless of changes in supply pressure during operation.
• Simple to use auto calibration.
• Easily equipped on small actuators because of its small size.
• Low air consumption reduces operating cost.
• Can be used in low voltage (8.5 V), leaving no limitation in controller.
• HART
communication available for configurating parameters or monitoring the
®
valve position.
• Analog feedback signal (4 to 20 mA).
• The adjustment of valve characteristics (linear, quick open, equal percentage)
available.
• Tight shut-close and shut-open can be set in the programming menu.
• PID parameters can easily be adjusted in the field without additional
communicator.
• Split ranges such as 4 to 12 mA, with 12 to 20 mA available.
• The positioner can manually actuate the valve or damper.
• An air filter regulator can be mounted directly to the positioner.
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
Series 185/285 Smart Positioners
Specifications - Installation and Operating Instructions
Series 285
protocol.
®
DOUBLE
SINGLE
ACTION
ACTION
3-27/32
[97.50]
CONDUIT ENTRY
1/2 NPT
2-11/32
[59.60]
3-1/64
[76.50]
SPECIFICATIONS
Input Signal: 4 to 20 mA DC.
Input Impedance: 460 Ω max @ 20 mA DC.
Enclosure: Aluminum, SS.
Air Supply: 35 to 116 psi (2.4 to 9 bar).
Air Connection: 1/4˝ NPT.
Gage Connection: 1/8˝ NPT.
Conduit Connection: 1/2˝ NPT.
Linearity: ±0.5% FS.
Hysteresis: ±0.5% FS.
Sensitivity: ±0.2% FS.
Repeatability: ±0.3% FS.
Air Consumption: .0004 scfm (.01 LPM) at 20 psig (1.4 bar) supply.
Flow Capacity: 2.1 scfm (60 LPM) at 20 psig (1.4 bar) supply.
Stroke: 185: 0.5 to 6 in (10 to 150 mm); 285: 0 to 90°.
Enclosure Rating: NEMA 4X (IP66).
Temperature: Operating: -22 to 185°F (-30 to 85°C).
Weight: 185: 3.3 lb (1.5 kg); 285: 6.4lb (2.9 kg).
Lever: 185: .39 to 1.57 in (10 to 40 mm); 285: NAMUR.
HART
is a registered trademark of Hart Communication Foundation
®
Phone: 219/879-8000
Fax: 219/872-9057
Bulletin V-185/285
LCD SCREEN
SMART POSITIONER
8-31/64
[215.70]
STAINLESS STEEL
4-31/64
[113.8]
STANDARD
2-33/64
[64.00]
SUPPLY
1/4 NPT
4-7/64
[104.20]
www.dwyer-inst.com
e-mail: info@dwyermail.com
3-47/64
[95.00]
4-13/32
[111.90]

Advertisement

loading
Need help?

Need help?

Do you have a question about the PROXIMITY 185 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Dwyer Instruments PROXIMITY 185 Series

  • Page 1 • The positioner can manually actuate the valve or damper. • An air filter regulator can be mounted directly to the positioner. HART is a registered trademark of Hart Communication Foundation ® DWYER INSTRUMENTS, INC. Phone: 219/879-8000 www.dwyer-inst.com P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A. Fax: 219/872-9057...
  • Page 2: Installation

    • Spanners for hexagon head bolts Series 185 Installation Series 185 is used for linear motion valves such as Dwyer Instruments’ globe valves using a spring return type diaphragm actuator or piston actuator. The Series 185 consists of the following components. Be sure that all the components are included.
  • Page 3 7. Check that the Series 185’s feedback lever is level at 50% of valve stroke. If not, Series 285 is designed for rotary motion valves such as Dwyer Instruments’ ball move bracket or feedback link until it is level. Product linearity becomes work if and butterfly valves using rack and pinion, scotch yoke or complex type actuators Series 185 is installed without being level at 50% of valve stroke.
  • Page 4: Piping Connection

    Installing Series 285 with Bracket 5.Once the fork lever position is set, lock the check nuts on the bottom of the fork Series 285 is supplied with a standard bracket. The bracket consists of two parts lever by turning clockwise. Set the upper height of the fork lever to .24˝ to .43˝ (6 and is used with a NAMUR shaft.
  • Page 5 Piping Connection With Actuator Series 185 and Series 285 can operate either single or double acting actuators. Single Acting Actuator To operate a single acting actuator, connect OUT1 port to actuator supply pressure port. Close off the OUT2 port with the supplied 1/4˝ NPT plug. Terminal Plate of Series 185 and 285 Terminal Connection of Current Input Signal LCD SCREEN...
  • Page 6 Auto Calibration and Basic Operations Auto Calibration Types Auto 1 Calibration (AUTO1) CAUTION Since this makes the valve or actuator move, before auto In this mode, all parameters necessary for valve operation are set except KP, KI, calibration, the valve must be separated from the entire KD and RA/DA.
  • Page 7 Parameter Mode (PARAM) HAND CAL Parameter Types When auto calibration is started, Series 185 and 285 positioners set zero points There are four parameter modes: Dead Zone, KP, KI, and KD. and end points based on full stroke. HAND CAL allows for user defined zero and These values are reflected as soon as they are changed, therefore the appropriate end points.
  • Page 8 Valve Mode Adjustment of User Characteristics (USER SET) This mode adjusts the various characteristics. 1. Push <ENTER> at VALVE mode and scroll with <DOWN> to select USER SET. 2. Push <ENTER>. *PO SET mode is displayed. In this mode, users can adjust the Action Type (ACT) first point of characteristic in 16 points.
  • Page 9 Tight Shut Open (TSHUT OP) VIEW Mode This allows the user to fully open valve at input values around 20 mA. This mode provides users with various information about the Series 185 and 285 positioners. In this mode, users can change the valve stroke types displayed on Adjustment of Tight Shut Open (TSHUT OP) LCD to % or numbers.
  • Page 10: Maintenance/Repair

    Manual Mode Parameter Hand cal Valve View (5 sec) RUN Mode ©Copyright 2014 Dwyer Instruments, Inc. Printed in U.S.A. 7/14 FR# RV-443952-00 Rev. 3 DWYER INSTRUMENTS, INC. Phone: 219/879-8000 www.dwyer-inst.com P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A. Fax: 219/872-9057...

This manual is also suitable for:

Proximity 285 series