Download Print this page

Full Gauge Controls TI-44e Plus Quick Start Quide

Four-sensor digital thermometer with serial communication

Advertisement

Quick Links

Have this manual in your hands
using the FG Finder application.
1. DESCRIPTION
Temperature indicator designed to monitor average, differential or individual temperatures of up-to four
sensors. It can be connected to Sitrad real-time monitoring and management software or smartphone
APP using RS485 serial communication port.
It features IP65 frontal protection, optional drip protection case at rear and tamper-proof function
lockdown to prevent unauthorized change of parameters.
2. SAFETY RECOMMENDATIONS
- Check the controller for correct fastening;
- Make sure that the power supply is off and that it is not turned on during the controller installation;
- Read the present manual before installing and using the controller;
- Use adequate Personal Protective Equipment (PPE);
- For application at sites subject to water spills, such as refrigerated counters, install the protecting vinyl
supplied with the controller;
- For protection under more critical conditions, we recommend the Ecase cover, which we make
available as an optional item (sold separately);
- The installation procedures should be performed by a qualified technician.
3. APPLICATIONS
• cold storage equipment
• machine tools
• stoves
• furnaces
• motor vehicles
• air conditioned rooms
• food, chemical, and pharmaceutical industries.
4. TECHNICAL SPECIFICATIONS
Ti-44E Plus:115 or 230 Vac ±10%* (50/60 Hz)
Power Supply
Ti-44EL Plus: 12 or 24Vac/dc +10%*
Approximate consumption
0.6 VA
Measurement range
(**)
-50 to 200°C (-58 to 392°F)
Operating Temperature
0 to 50° C / 32 to 122°F
Operating humidity
10 to 90% RH (with no condensation)
Dimensions (mm)
76 x 34 x 77 mm (W x H x D)
Cutout dimensions (mm)
X = 71±0,5 Y = 29±0,5 (see Image V)
IMPORTANT: Only sensor S1 is included with the product. Sensors S2, S3, and S4 are sold separately.
(*) Admissible variation in relation to the voltage rating.
(**) This device can measure temperatures of up to 200°C/392°F, when used in conjunction with the SB59 silicon sensor
cable (sold separately).
5. INDICATIONS AND KEYS
Sensor 3 indication LED
Sensor 2 indication LED
Sensor 1 indication LED
Quick Access
1
2
3
Menu Key (Flatec)
Set Key
e
TI-44
plus
6. WIRING DIAGRAM
6.1. Electrical connections (see Images I to IV)
SITRAD
A
B
Image I: TI-44E Plus - 115Vac
5 6 7 8
9 10 11 12 13 14 15 16 17
1
2 3 4
115 Vac
SITRAD
A
B
Image III: TI-44EL Plus - 12Vac/dc
5 6 7 8
9 10 11 12 13 14 15 16 17
1
2 3 4
12 Vac/dc
e
TI-44
FOUR-SENSOR DIGITAL THERMOMETER
WITH SERIAL COMMUNICATION
Up to four
Differential
Average
Functions
temperature
temperature
temperature
lock
sensors
calculation
calculation
Sensor 4 indication LED
Functions lockdown indication LED
Temperature unit indicator LED
4
Upper key
Lower key
SITRAD
A
5 6 7 8
1
SITRAD
A
5 6 7 8
1
plus
IP 65
FRONT
Supervisory
Serial
Protection
system
Programming
level
6.2. Temperature sensor connection
- Connect the sensor S1 wires to terminals "7 and 8": the polarity is not relevant.
- The sensor cable can be extended up to 200 meters, by the user itself, using a PP2x24AWG cable.
- For immersion in water, use a thermowell (Image VI - item 13), available in the Full Gauge Controls
product line (sold separately).
6.3. Controller power supply
Use the pins according to table below, considering the set version:
Pins
9 and 10
9 and 11
6.4. Recommendations of IEC60364 standard
a) Install overload protectors in the controller supply.
b) The sensor cables may be together, but not in the same conduit where the power supply of the
controller and/or of the loads passes through.
7. FASTENING PROCEDURE
a) Cut out the panel plate (Image V - item 13) where the controller shall be fastened, with sizes
X = 71±0.5 mm and Y = 29±0.5 mm;
b) Remove side locks (Image VI - item 13): to do that, compress the central elliptical part (with the Full
Gauge Controls logo) and displace the locks backwards;
c) Introduce the controller in the notch made on the panel, inwards;
d) Place the locks again and then displace them until they compress into the panel, fastening the
controller to the housing (see arrow indication in Image VI - item 13);
e) Perform the electric installation as described in item 6;
f) Adjust the parameters as described in item 8.
ATTENTION: for installations requiring liquid tight sealing, the notch sizes for the controller
installation should be no more than 70.5x29mm. The side locks should be fastened so that they
press the sealing rubber avoiding infiltration between the notch and the controller.
Protector vinyl - Image VII (item 13)
It is supplied with the instrument in the package.
IMPORTANT: Make the application only after completing the electrical connections.
a) Retreat the side locks (Image VI - item 13);
b) Remove the protective film from the adhesive vinyl face;
c) Apply the vinyl over the entire upper part, bending the flaps, as indicated by the arrows - Image VII
(item 13);
d) Reinstall the locks.
NOTE: The vinyl is transparent, allowing visualization of the wiring system of the instrument.
8. ADJUSTMENT OF THE SETPOINT AND PARAMETERS
8.1.
Quick Access Menu Map
To access or browse the quick access menu use the
displaying the temperature. With each touch the next function in the list is displayed. To confirm use
/
the
key (quick touch). See chapter 8.3. for more details. The map of functions is shown below:
FUNCTIONS LOCKDOWN
;
e
TI-44
plus
MIN. AND MAX. TEMPERATURE
RECORD
;
e
TI-44
plus
ERASE MAX. AND MIN.
VALUES
;
e
TI-44
plus
B
Image II: TI-44E Plus - 230 Vac
9 10 11 12 13 14 15 16 17
2 3 4
230 Vac
B
Image IV: TI-44EL Plus - 24Vac/dc
9 10 11 12 13 14 15 16 17
2 3 4
24 Vac/dc
evolution
1
plu s
e
e
plu s
TI -4 4
TI -4 4
TI-44E PLUS
TI-44EL PLUS
115 Vac
12 Vac/dc
230 Vac
24 Vac/dc
;
key (quick touch) while the controller is
EXIT THE FUNCTION
;
FUNCTION SELECTION
;
DISPLAY DIFFERENTIAL
DISPLAY AVERAGE
CALCULATION
CALCULATION
;
;
e
TI-44
plus
LEGEND:
To the terminal of
the connecting block
IMPORTANT: Only the sensor 1 is sold with the
product, the sensors 2,3 and 4 can be purchased
separately.
IMPORTANT
INSTRUMENTS IN THE EVOLUTION SERIES HAVE
TWO DIFFERENT TERMINAL SIZES, BUT BOTH ARE
COMPATIBLE WITH THE SCREWDRIVER 2.0mm.
USING THE APPROPRIATE TOOLS DURING
INSTALLATION ENSURES A LONGER LIFE AND THE
PROPER OPERATION OF THE PRODUCTS.
e
TI-44
plus
e
TI-44
plus
e
TI-44
plus

Advertisement

loading

Summary of Contents for Full Gauge Controls TI-44e Plus

  • Page 1 - The sensor cable can be extended up to 200 meters, by the user itself, using a PP2x24AWG cable. sensors. It can be connected to Sitrad real-time monitoring and management software or smartphone - For immersion in water, use a thermowell (Image VI - item 13), available in the Full Gauge Controls APP using RS485 serial communication port.
  • Page 2 8.2. Quick access keys map 8.4.2. Parameters Table When controller is on temperature display mode, the following keys can be used as a shortcut for the CELSIUS (°C) FAHRENHEIT (°F) following functions: Description Max Unit Default Max Unit Default Quick touch: confirmation of the function adjustments. [,F01] Access Code [,F02]...
  • Page 3 If in doubt, please contact Full Gauge Controls. Products manufactured by Full Gauge Controls, as of May 2005, have a two (02) year warranty, as of the date of the consigned sale, as stated on the invoice. They are guaranteed against manufacturing defects that make them unsuitable or inadequate for their intended use.