Incon TS-STS Quick Start Manual

Sump test system

Advertisement

Quick Links

TS-STS Overview
The TS-STS system includes a TS-STS console within a convenient
portable case, leak testing probes with 50 feet of cable, and probe
hanging hardware (slip rings and chain).
After all fittings within the sump are sealed, the sump is filled with a
water-based test solution that covers all sump penetration holes. The
probe is installed so the float is floating on the surface of the test solution.
The TS-STS console is quickly programmed with the site name and
address, number of sumps, the 7-digit code-names for each sump, and
the correct Time/Day/Date before leak testing.
Pressing the Test key at the console keypad starts sump leak tests for
all sumps. The test time is 15 minutes and tests for a level change
greater than 0.002 inches. If the level of a sump drops more than the
leak limit during the test, the Sump Leak Test Report will show a fail
result when the test is finished. Leak tests can also be programmed
(scheduled) to start at desired times.
When finished, leak test reports will automatically print out at the console
printer. Extra copies of this report can be printed using the report key. A
newly completed Sump Leak Test will overwrite the previous results
stored in memory. Save sump leak test reports and provide copies as
evidence of compliance with regulations.
Recommendation: Use a computer and the Tech version of
System Sentinel™ to record site data, sump code-names, and test
results. Test results can also be extracted from Comm Port 1 at
the bottom of the TS-STS console (also see Section 4).
Reference Federal and State regulations for leak limit and test
time requirements. Recommendations for locating the TS-STS
console outside of the (Class I , Division 1, Group D) Hazardous Areas
during testing, are based on NFPA 30, NFPA 30A and NFPA 70 (NEC).
INCON P/N 000-3004 Rev.D Feb. 2009 ©
This document may change without prior notice.
TS-STS
TS-STS
www.fraklinfueling.com
INCON
®
is a Registered Trademark of Franklin Fueling Systems
Sump Test System
Sump Test System
Quick Start Guide
Quick Start Guide
1
TS-STS Installation
1.) Required Materials:
a.) Tape to secure the probe cable
c.) Grounded, 3-pronged extension cord
d.) Flat pieces of metal to suspend leak testing probe over sumps
2.)
Work safely — install Safety Cones and Signs at the site
3.)
The probes are precision instruments — handle with care!
4.)
The STS probes are shipped with cables attached, do not remove
the cable from the probe end... remove at the console case only.
5.)
Inspect probes for proper float movement before use, then install
probes as shown in Section 1
6.)
Connect the yellow probe cables to the receptacles at the TS-STS
case. Make sure to line up keyways before inserting cable and
tightening the screw-on connector.
7.)
Locate the TS-STS case outside of the Hazardous Area and tape
the cable down to prevent probe movement during the test and to
reduce tripping hazards
8.)
Setup / Program the TS-STS console per Section 2
9.)
Start sump leak test(s) on sumps that are ready
10.) Always clean, dry, and store probes in the probe carrying case after
each use
11.) Test each of the probes on a monthly basis to ensure its ability to
detect leaks. Install the probe in a test container and initiate a test.
After 5 minutes, remove about 0.12 inches of water. When the test
completes, the test report should show a Failed result if the probe
is working properly.
Pg 1
b.) Safety cones & signs

Advertisement

loading

Summary of Contents for Incon TS-STS

  • Page 1 Flat pieces of metal to suspend leak testing probe over sumps The TS-STS console is quickly programmed with the site name and Work safely — install Safety Cones and Signs at the site address, number of sumps, the 7-digit code-names for each sump, and The probes are precision instruments —...
  • Page 2 / ANGLE IRON REQUIRED TO SUSPEND PROBE RECEPTACLES (SIDE VIEW) FOR FOUR SUMP TS-STS SCREW-IN, PROBE CABLE PLUGS P O W E R C O R D WITH A GROUNDED 3-PRONGED PLUG 20 Feet - Min. Distance SUMP TEST SYSTEM...
  • Page 3 FLAT METAL / ANGLE IRON REQUIRED TO SUSPEND PROBE (SIDE VIEW) RECEPTACLES SUMP FOR FOUR TS-STS SCREW-IN, PROBE CABLE PLUGS Tank Pad TAPE / WEIGHT DOWN CABLE TO PREVENT SUMP TEST SYSTEM ACCIDENTAL 10 Feet - Min. Distance MOVEMENT DURING...
  • Page 4: Minimum Setup Requirements

    Setup - Program the Console Pg 4 Press the MENU key and follow MENU Navigating vigating vigating vigating vigating Display the highlighted sequence below to view the Setup Menus Menus: Menus: Menus: Menus: Menus: Menu Select Keys SELECT MENU OPTION (M1 –...
  • Page 5: Setup Menu

    AND DATA WILL BE LOST... LINE 1 LOCATION LINE 1 (input 24 characters Max) PRESS ENTER IF YOU ARE SURE THAT INCON Enter the Business Name YOU WANT TO CONTINUE WITH COLD BOOT LINE 2 LOCATION LINE 2 (input 24 characters Max) Setup>Sumps menu...
  • Page 6 Leak Testing / Setup>Clk/Cal menu Pg 6 Console Operation CLOCK/CALENDAR DAY SAV Displays: SYSTEM SUMP DAYLITE SAVINGS OKAY OKAY ENABLED Enable = allows daylight savings time changes Normal Display DISABLED Disable = does not Press the Check key TM STYLE Select the time style for displays &...
  • Page 7 REPORT Press the Report key at the keypad to show various report choices. — — Reports INCON INTELLIGENT CONTROLS INC. SELECT REPORT P.O. BOX 638 SUMP ALARM SACO ME 04072 1-800-984-6266...
  • Page 8 Reports Continued... Pg 8 A digital copy of the Sump Test Report can be retrieved from the TS-STS console through the communications port (Comm Port 1). This port is located at the bottom side. As with the printed reports, this data is overwritten when a new test is run, so it must be collected after each test.