Advertisement

Quick Links

CONTROL PANEL
Operation and Maintenance Manual
th
Doc:GLT-261-7-2
Issue:
001
Date: 09
September 2018

Advertisement

Table of Contents
loading

Summary of Contents for Velocity MMP

  • Page 1 CONTROL PANEL Operation and Maintenance Manual Doc:GLT-261-7-2 Issue: Date: 09 September 2018...
  • Page 2 Velocity Operation Manual ONTENTS Page Controls and Indicators ..........................System Operating Modes and Annunciation ........................ Normal Condition (Quiescent) ......................... Trouble Condition ..........................Alarm Condition ..........................Supervisory Condition ..........................Disablement Condition ............................ Test Condition ..............................Multiple Conditions .............................. Accessing the Panel ..............................
  • Page 3: Controls And Indicators

    Velocity Operation Manual Controls and Indicators Figure #1 below shows the control buttons, LED indicators and switch locations. Figure #1 a) LED: Alarm Red LED. • Flashes when there is an active alarm event present. • On steady once acknowledged.
  • Page 4 Velocity Operation Manual Off if the panel re-enters alarm, the system is reset, or if a drill is carried out. • e) LED: Power Green LED. • On steady when the panel has power. • Off when the panel has no source of power applied.
  • Page 5: Function Button: Reset

    Velocity Operation Manual • A minimum of Level 2 access (By entering the user password) is required. When the ACKNOWLEDGE button is pressed, the control panel will silence its internal sounder (buzzer) • Change all related active LED indicators from flashing to steady.
  • Page 6: Trouble Condition

    Velocity Operation Manual System Operating Modes and Annunciation During Normal operation the panel will be in one of the following states depending on the status of the devices connected to the panel, and user intervention. Below is a summary of the different conditions:...
  • Page 7: Alarm Condition

    Velocity Operation Manual Alarm Condition The following functions will be performed when in the A typical alarm display would be as illustrated below: alarm condition: Will cause the panel’s internal buzzer to sound with • a steady output. The Alarm LED will illuminate and flash.
  • Page 8: Disablement Condition

    Velocity Operation Manual Disablement Condition Disablements are indicated with the general disablement LED, and a mixture of LCD/LED indications. In this example, zone 1 is disabled. The panel shows that one zone is disabled, and that the 10 Loop (SLC) devices and 2 module inputs/outputs in that zone are also disabled.
  • Page 9: Test Condition

    Velocity Operation Manual Test Condition In this example, one Zone 3 is in test mode. A number of zones can be put into test at the same time if required. The test can be silent, or with sounders. If the sounder option is chosen, only sounders within the same zone as the test device are operated.
  • Page 10 Velocity Operation Manual Accessing the Panel The VELOCITY panel has 2 user access levels and one installer access level. Basic user access (Access level 2a) Tap LCD. Select user icon . Enter user access code (Default 0001) This allows the user to have access to the main control buttons, to silence alarms, acknowledge events and reset the panel.
  • Page 11: Navigating The Panel Menus

    5 minutes) Navigating the Panel Menus The Velocity panel has 2 menus, user and engineer. Entering the user code (Default 0001) accesses the user menu. Entering the Engineer password (Default 9999) enables access level 3.
  • Page 12 Velocity Operation Manual Table View Screen (Example) Information is presented in a table, there is editable data (e.g. device labels), and non-editable data (e.g. device types). Tapping on an editable data field will allow it to be edited. Data Field Screen (Example) Information is presented in data fields, the data will either be values, or option buttons.
  • Page 13 Velocity Operation Manual Acknowledge When an Alarm, Supervisory or Trouble event occurs in the system, the display enters the off-normal mode automatically. The events are displayed in priority order (Alarm, Supervisory, and Trouble), the local audible sounds and the appropriate LED’s will blink. After all events have been acknowledged, the buzzer will deactivate and the associated LED will stop flashing and remain on continuously.
  • Page 14: Initial Panel Setup

    Velocity Operation Manual Initial Panel Setup The Velocity panel is supplied configured ready for installation. But there are a few settings that may need to be altered. Setting Date and Time Press the screen. The panel prompts for a user and password.
  • Page 15: Creating An Installation Name

    When you select the SLC it will become highlighted. Press the green tick to confirm the selection. The port number will be labelled on the TRM PCB inside the panel and are also shown in the Velocity Installation manual (Doc: GLT-261-7-1). www.velocitydetection.com...
  • Page 16: Zone Labels

    However, it is assumed that a zone will not contain more than 32 fire detectors and/or manual call points, since this would correspond to an unacceptably large search area. The Velocity panel has 254 zones. There is capability in some panel models (MMP10/64 &...
  • Page 17 SLC Device Text and Zoning Velocity is an addressable panel, i.e. it will indicate the address or location of a fire that has been detected. The address number of each point or device on the loop has already been set with the address programming tool VDOT-AD2. See Manual GLT-303-7-1 for details.
  • Page 18 Velocity Operation Manual Press the ‘zone’ field to edit the device`s zone number if required. Edit another device, or press to exit the device list and save the changes. The Device list screen also shows the current mode of each device, i.e. ENABLED or DISABLED Press the MODE field of a device to toggle its state between enabled and disabled.
  • Page 19 SLC Device Options Each addressable Velocity device has a number of configuration settings that can be programmed at the panel. The configuration screen is accessed by selecting the device on the options tab. The options for each device are:-...
  • Page 20 Velocity Operation Manual VDOT-H2-H (Addressable High Heat Detector) Available options: Led Flash: (Off) / (On) VDOT-DPH (Addressable Dual Optical/Heat Detector) Available options: Led Flash: (Off) / (On) Day settings: (Opt. On) / (Opt. Off) (Heat On) / (Heat Off) Night settings: (Opt.
  • Page 21 Velocity Operation Manual (Off) / (On) Note: Turning on priority polling will make the panel prioritise events from this device. This can only be used on 50 devices per loop. VDOT-SCM-SCI (Addressable Sounder Control Module with SCI) Available options: Led Flash:...
  • Page 22 Velocity Operation Manual VDOT-MiniIP (Addressable Photoelectric Smoke Detector) Available options: Input Style: (ClassB [NO]) / (ClassB [NC/SC]) / (ClassB [NO/SC]) Input Event: (Alarm) / (Supervisory) / (Trouble) P. Priority: (Off) / (On) Note: Turning on priority polling will make the panel prioritise events from this device.
  • Page 23 The below is an example on how to change the VL/NCB options. The procedure to change the settings for the VL/NCA is the same. Note that the cause & effect for the Velocity MMP panel has 3 tone options for the NACs: ANSI -3 tone, March tone and continuous.
  • Page 24 VL/ZMB (Zone Monitor – 6 x Class B) = Zone Class B VL/MIM (Multi Input – 6 x Class B) = Input Class B The port number will be labelled on the TRM PCB inside the panel and are also shown in the Velocity Installation manual (Doc: GLT-261-7-1). www.velocitydetection.com...
  • Page 25 Velocity Operation Manual The module settings screen will be displayed. In this example, the input address is shown as: (4.1). The first number represents the TRM port (The RJ45 port on the TRM PCB that the module is plugged into).
  • Page 26 VL/MRM (Multi Relay – 3 x Form C) = Relay The port number will be labelled on the TRM PCB inside the panel and are also shown in the Velocity Installation manual (Doc: GLT- 261-7-1). The module settings screen will be displayed.
  • Page 27 Velocity Operation Manual Trouble: Relay will act as a common trouble relay, and will react to ANY trouble condition on the panel. Cannot be disabled or controlled by cause & effects. Relay will become normally energised. Supervisory: Relay will act as a common supervisory relay, and will react to ANY supervisory condition on the panel.
  • Page 28: Event Logs

    Velocity Operation Manual Event Logs The Velocity event log has a capacity of storing 8032 events. It saves all alarm, trouble, supervisory and test events that occur on the system. From the ENGINEER MENU, press the ‘log’ icon. The panel will display the log file.
  • Page 29 Velocity Operation Manual Supervisory events are shown with a BLUE highlight. The highlighted section gives the time, date and the device type that has caused the supervisory alarm. The table shows more detail of the supervisory event (Address, Device text label, zone, zone text label).
  • Page 30 Buzzer Resound 24H Settings The Velocity has the option to configure whether the panel shall resound its internal buzzer every 24 hours. Any alarm, supervisory or trouble events that have been acknowledged but not cleared, will resound the buzzer every 24 Hours until they have been cleared from the panel.
  • Page 31 Flash Mute Settings The Velocity MMP has the ability to control the flasher operation of the panel. The flashers of a notification appliance can be configured to remain flashing after the chimes/horns have been silenced. The flashers can only be stopped by pressing the panel reset button to clear the event.
  • Page 32 Cause and Effect The Velocity system has very comprehensive, but simple to use Cause and Effect capabilities. The Default factory configuration is that any alarm will activate all outputs on the panel. Like most addressable systems, the panel allows comprehensive programming of the sounders, NAC outputs and relays.
  • Page 33 Velocity Operation Manual Point Address: • Device Loop Address: 1-254 Device Port: 0-15 (Select 0 for all ports) For a ‘Local I/O’ cause the options are:- Local I/O causes: • Trouble Alarm Supervisory ON Supervisory OFF Local module: • 1-26 Module Port: •...
  • Page 34 Velocity Operation Manual An AND / OR cause will request more inputs before activating the output. Select up to 8 causes. Press the OUTPUT icon when finished. After selecting the input cause(s), the panel displays a screen to select the following effect options:...
  • Page 35 Velocity Operation Manual For Local I/O effects, the options are:- Day Delay: • 0-600 seconds Night Delay: • 0-600 seconds (This is the delay used if Day/Night timer is not set) Local I/O effect: • Evacuation Warning Beacon Switch OFF...
  • Page 36: Outputs And Delays

    Velocity Operation Manual Evacuation on outputs Warning on outputs Switch OFF output Disable sounders Enable sounders Disable relays Enable relays Disable output Enable output The panel shows the Programmed cause and effect. It shows: First row • Event type (Direct, AND, OR), and entry number •...
  • Page 37 Mains Fault Relay Output Delay In the event of a mains power failure, the Velocity can be programmed to delay its TRM trouble relay for a time of between 0-240 minutes. This is normally used when operators do not require momentary mains power failures to send trouble notifications to monitoring stations.
  • Page 38 Velocity Operation Manual Enter the required mains relay delay time using the onscreen number pad. The time entered is in MINUTES. Press tick to save the changes, or press discard. When finished, press the exit icon . The panel will ask if you want to save the changes.
  • Page 39: Day/Night Mode

    Day/Night Mode The Velocity panel has a day night timer that allows certain system responses to be altered at certain times of the day. It allows for different delays for the day and night times, and it also allows the sensitivity of certain detectors to be set differently for the day and night.
  • Page 40 Velocity Operation Manual The screen shows the programmed day slice(s). Press the add icon to add a slice, or press exit icon if all slices are entered. When there are more than 4 slices programmed, the panel displays up /down scroll arrows in order to view the other slices.
  • Page 41 Velocity Operation Manual Setting Day-Time and Night-Time Delays The day and night time delays are set through the cause and effect programming. Enter the required cause (as described in the Cause and Effect section). When the panel asks for the output effect, enter the day time delay in the first delay field.
  • Page 42 Velocity Operation Manual Setting Day-Time and Night-Time Detector Sensitivity The day and night time detector sensitivities are set through the Device options screen. Go to the engineer menu, and select the point Icon Select the Option tab. The panel displays the Options table.
  • Page 43 Velocity Operation Manual Indication of Day/Night Mode The panel indicates its current operating mode by means of a circle in the top left corner of the LCD. No Day / Night timer set. No circle in top left corner. Day / Night timer set. Panel in Day Mode.
  • Page 44: Alarm Verification

    Retard time of up to 30 seconds and the detector’s alarm condition is automatically reset. There will be no alarm indication at the Velocity MMP panel during the Retard period, only an indication that an alarm is being verified.
  • Page 45 Velocity Operation Manual The panel shows the Delays screen. See the ‘Alarm Verificat’ with Off & On options. Select ON to enable, or select OFF to keep the verification disabled. The ‘Retard Time’ is the duration that the alarm signal is initially delayed and can be configured between 1-30 seconds.
  • Page 46 Velocity Operation Manual Multiple Detector Operation The panel is equipped to satisfy those who require a Multiple Detector Operation feature that is used to reduce unwanted false alarms. If a multiple detector operation has been programmed, the panel will require the activation to two automatic detection devices before it will enter the alarm condition.
  • Page 47 Velocity Operation Manual After selecting the input cause, the panel displays a screen to select the following effect options: Panel address: Leave as zero if the output effect is on this local panel, otherwise set to the network address of the destination panel.
  • Page 48: Positive Alarm Sequence

    Positive Alarm Sequence The Velocity MMP is equipped with a positive alarm sequence that will program a delay to the NAC’s, Alarm relays and Auxiliaries for a period of between 1-15 seconds. If the alarm is acknowledged, it will silence the piezo sounder and start a timer which will prevent activation of these outputs for an additional time duration which can be user programmed between 1-180 seconds.
  • Page 49 Velocity Operation Manual The ‘Ext. Time’ is the duration of the second time delay and can be configured between 1-180 seconds. To change the time, press either the + or – button to increase or decrease the zone number. You can also type in the number via the panel numerical keyboard, to do this press on the zone number field.
  • Page 50 PRE-SIGNAL shall only be used when the panel is constantly monitored by an Operator. Pre-Signal Setup Below is just an example of how pre-signal can be achieved on a Velocity MMP system. Ensure that when pre-alarm operation is used, that it complies with UL864 10 Edition requirements.
  • Page 51 This flow chart is a breakdown of the pre-signal operation that has been programmed into the Velocity MMP cause & effects. When finished, press the exit icon . The panel will ask if you want to save the changes.
  • Page 52: Zone Disablement

    Disablements To aid commissioning and assist routine maintenance checks, various functions of the Velocity fire alarm system can be disabled. The Velocity allows disablement of Inputs in a zone, Outputs in an alarm group, individual devices and individual module ports.
  • Page 53 Velocity Operation Manual When zones have been disabled, the LCD display changes from SYSTEM NORMAL to Disablement/Test. The screen shows:- The number of zones disabled. The number of zones with just their inputs disabled. The total number of disabled devices in those zones.
  • Page 54 Velocity Operation Manual SLC Device Disablement Rather than disable an entire zone, it is often useful to just disable one or more devices or points (detector, call point, interface or sounder) within a zone, especially if they are malfunctioning and likely to cause an unwanted alarm or repeatedly indicate a trouble condition.
  • Page 55 Velocity Operation Manual To re-enable a device, use the same procedure, pressing the ‘Mode’ field until it shows ‘Enabled’. Once a SLC device is disabled, the panel ignores any alarm or trouble generated by the device. If all devices in a zone are disabled, the panel will indicate a zone disablement.
  • Page 56 Velocity Operation Manual When global relays have been disabled, the LCD display changes from SYSTEM NORMAL to Disablement, as shown. The screen shows the number of relay output interfaces disabled. The General Disablement LED will be lit. Details of the disabled relay outputs can be viewed by...
  • Page 57 Velocity Operation Manual Details of the disabled sounder outputs can be viewed by pressing the disabled loop devices icon or the disabled local I/O icon . If any zones have all of their outputs disabled, it will be indicated by the disabled zone...
  • Page 58 Velocity Operation Manual For further options, press the ‘Out’ field again. The status will change from ‘Relay disabled’ to ‘All disabled’. This would disable all sounder and relay outputs in that alarm group (zone). When Alarm group mode has been disabled, the LCD display changes from SYSTEM NORMAL to Disablement.
  • Page 59 Velocity Operation Manual A local I/O can be disabled as follows: Enter the Engineer or User Password, Press the menu access icon , select the ‘local I/O’ Icon (The disabling function is available to engineer & users). The panel shows the module selection menu.
  • Page 60 Velocity Operation Manual ‘Disabled’ selection circle, then press to cycle through more outputs, or the exit icon . The panel will ask if you want to save the changes. Press tick to save the changes, or press discard. NCA/NCB Disablement The module settings screen will be displayed.
  • Page 61: Why Use Test Mode

    Velocity Operation Manual Test Mode Why Use Test Mode? To aid commissioning and assist routine maintenance checks, a non-latching ‘one man test’ facility is available. Test mode can be used either with or without sounder operation, depending on the engineer’s requirements.
  • Page 62 Velocity Operation Manual To view which zones are in test mode, press the zones in test icon Proceed to test the devices. As we are checking the devices, the test alarms are reported on the supervisory screen. When the testing is complete, take the panel out of test mode by entering the Engineer level menu and selecting the ‘zone’...
  • Page 63 Velocity Operation Manual NETWORKING The Velocity requires a VL/NWM module to network to another Velocity system. Up to 64 control panels (CIEs) can be connected together, i.e. networked. The maximum distance between nodes is 1 km using a screened data cable, or 100m using a standard fireproof cable.
  • Page 64: Configuring The Network

    Press the green tick to confirm the selection. The port number will be labelled on the TRM PCB inside the panel and are also shown in the Velocity Installation manual (Doc: GLT-261-7-1). The panel shows that the network connection is disabled (It`s default state).
  • Page 65 Running the Network On a Velocity panel, running in a network, all events are reported at all panels. All panels are able to silence & reset the system, when a suitable access code has been entered.
  • Page 66 Velocity Operation Manual Configuring TCP/IP Connection The Velocity panel has an optional TCP/IP module that allows the panel to report events to a central server. To do this, first the TCP/IP address must be set. From the Network Menu , select the TCP/IP module.
  • Page 67 Configuring the Cloud Settings The Velocity MMP panel has been designed to report events to a central server. This will allow authorised users to view the current status of the panel. The settings are usually set at the factory, but can be configured by the installer if required.
  • Page 68 Velocity Operation Manual Configuring the RS232 Panel Printer The Velocity panel has been designed to report events to a panel printer. This will provide automatic, or on demand copy listings of the event log or status information. Enter the engineer menu.
  • Page 69: Maintenance

    Fire Alarm System. VELOCITY control panels do not require any specific maintenance but should the control panel become dirty it can be wiped over with a damp cloth and should then be dried with a dry, lint free cloth. Solvents or detergents should not be used to clean the panel and take care not to allow any water to enter the enclosure.
  • Page 70 Velocity Operation Manual Enter access code and go to the menu. Press the LED Test icon. Check that all LEDs light, and the buzzer sounds. • Annual Test (to be carried out by authorised service personnel only) Check every detector, call point, sounder and all auxiliary equipment for correct operation.
  • Page 71: Troubleshooting

    SLC Trouble Finding The Velocity panel will monitor the SLC for open or short circuit faults. The panel’s SLC isolator monitors for both open and short circuit faults; the faults are reported as ISOLATOR FAULTS along with a description. The faults reported are:-...
  • Page 72 Velocity Operation Manual If the panel reports a loop short side B , then there is a short circuit fault on the Short circuit on side B SLC, somewhere between the panel (side B), and the last device with a short circuit isolator on the loop.
  • Page 73 Velocity Operation Manual SLC Contents Trouble Finding If the SLC contents are different to what was expected, then there two probable causes: The panel has detected two or more devices answering at the same address (each device on the loop should have a unique address) •If a device has just been added or...
  • Page 74 24V power is low. Investigate the PSU powering the interfaces Devices not seen on a loop Check that the wiring polarity to the search device is correct. Check that the device has the correct address Check that the device is compatible with the MMP panel www.velocitydetection.com...
  • Page 75: Power Supply Trouble

    Velocity Operation Manual Power Supply Trouble Carefully check that you have mains voltage at the fused terminal block Check that the mains fuse is intact Mains Supply Fault If mains & fuse are OK, Check that the PSU cage is giving out 30V DC (will need charger cover to be removed to check.
  • Page 76 Similarly, a A ground fault to the NAC - terminal would produce a positive earth fault message. Most Earth faults occur on the field wiring. As a first check, disconnect field wiring from the Velocity Panel. If no earth fault is reported then fault is on the field wiring. Locate the fault...
  • Page 77 Velocity Operation Manual Local I/O Faults The panel has stopped communicating to the module unexpectedly. Check coms heartbeat LED on front of module, it should be blinking. Module Removed Check the RJ45 connection between the module and the TRM PCB.
  • Page 78: Network Faults

    Velocity Operation Manual Network Faults NET 1 IS DOWN The network module has lost communications with the panel connected to it`s NET 1 Port. Check for cable breaks Check for cable shorts. Check the heartbeat LED on the network module in both panels...
  • Page 79: Appendix A: User Menu Summary

    Velocity Operation Manual Appendix A: User Menu Summary Default Password 0001 – Access level 2b Icon Tab Screen Description View Zone text label Zone Zone Explorer View Quantity of devices per zone View Zone text label Zone Edit View Quantity of devices per zone View/Edit zone mode (Enabled/Disabled/Test/Test+Sounder) View Address &...
  • Page 80 Velocity Operation Manual View/Edit output (1) mode (Disabled/Enabled) View output (1-2) text label View output (1-2) zone allocation Sounder Class B View output (1-2) type (Sounder/Bell/Voltage) View/Edit output (1-2) mode (Disabled/Enabled) LCD/LED Test panel LEDs, LCD & Buzzer Delays Toggle panel delays on or off...
  • Page 81: Appendix B: Engineer Menu Summary

    Velocity Operation Manual Appendix B: Engineer Menu Summary Default Password 9999 – Access level 3 Icon Tab Screen Description Select Loop Module to automatically search for all devices on Loop Module Selection the loop. Summary Summary of all devices found on loop...
  • Page 82 Velocity Operation Manual for details) View/Edit input (1-3) text label View/Edit input (1-3) zone allocation Local I/O Zone Class A View/Edit input (1-3) type (Alarm/Supervisory) View/Edit input (1-3) status (Disabled/Enabled) View/Edit input (1-6) text label View/Edit input (1-6) zone allocation...
  • Page 83: Appendix C: Cause And Effects Settings Summary

    Velocity Operation Manual Appendix C: Cause and Effects Settings Summary The table below shows the list of options available for each type of input (cause) and Output (Effect): Select CAUSE Input Type Selection 1 Selection 2 Causes • Alarm Point Address •...
  • Page 84 Velocity Operation Manual • Enable relays • Disable Output • Enable Output • Evacuation on sounders • Warning on sounders • Activate Beacon • Switch off SND/Beacon • Switch ON Relays • Switch OFF Relays • Evacuation on Outputs Panel...

Table of Contents