PHASE 2 - TRANSMITTER INSTALLATION
H
L
C
A
B
C
B
H
L
C
drain
A
B
valve
A
B
3-valve
3-valve
C
L
manifold
manifold
A
H
L
H
gate
valves
Flow
Flow
Flow measurement with gas or liquids with solids in suspension
1. Place the taps to the top or side of the line.
2. Mount the transmitter above the taps.
Max. Level
L
H
gate valve
Min. Level
Level measurement with open tanks
1. Mount the transmitter at the same height or below the lowest level to be measured.
2. Connect the + (H) side of the transmitter to the bottom of the tank.
3. Vent the - (L) side of the transmitter to the atmosphere.