AAF AstroFan EC FFU Installation, Operation And Maintenance Manual

AAF AstroFan EC FFU Installation, Operation And Maintenance Manual

Advertisement

AstroFan
EC FFU
INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
E508161

Advertisement

Table of Contents
loading

Summary of Contents for AAF AstroFan EC FFU

  • Page 1 AstroFan EC FFU ™ INSTALLATION, OPERATION, AND MAINTENANCE MANUAL E508161...
  • Page 2: Table Of Contents

    Insulation Options ......................12 Double Poly Bag Option ....................12 Power and Electrical ......................13 Wiring Diagram for EBM Blowers and AAF Flanders Control Interface ......14 Appendix A – Warranty Information ..................15 Appendix B – Manual Revision History ................16...
  • Page 3: Introduction And Precautions

    These instructions are specific to the AAF Flanders AstroFan EC FFU units and incorporated filters. All ancillary tasks including, but not limited to, electrical and mechanical work, equipment handling, and safety procedures must be performed in accordance with industry-accepted practice and all relevant local, state, and federal government codes, laws, and policies.
  • Page 4: Important Safety Instructions

    IMPORTANT SAFETY INSTRUCTIONS 1. READ AND SAVE THESE INSTRUCTIONS 2. WARNING – To reduce the risk of fire, electrical shock, or injury to persons, observe the following: a. Use this unit in the manner intended by the manufacturer. If you have questions, contact the manufacturer.
  • Page 5: Equipment Overview

    HEPA/ULPA filter at an industry-leading efficiency and reduced sound level. The AstroFan EC FFU is available in Aluminum or Stainless Steel options and as either a Top Side Serviceable (TSS) or Room Side Replaceable and Serviceable (RSR) configuration, white powder coat finish also available.
  • Page 6: Transport

    EQUIPMENT OVERVIEW Transport Deliveries are to be immediately checked in the presence of the carrier as being intact and complete. Units must be properly transported. Improper transport can lead to: • Impeller interference with inlet ring • Motor shaft deformation •...
  • Page 7: Installation

    INSTALLATION CAUTION: • Mounting may only be carried out by trained personnel in accordance with these instructions and with regards to regulations in force. • Safety devices that have been removed for mounting work must be replaced immediately afterwards, and before electrical connections are made. •...
  • Page 8: Room Side Replaceable Units

    INSTALLATION Room Side Replaceable Units Gasketed AstroFan • Install the RSR Adaptor Frame into Channel Housing the ceiling grid such that the gasketed channel is pointing upward. • Using the integral handles, carefully lay the AstroFan unit onto the RSR ™...
  • Page 9: Permaframe For Hard/Gypsum Ceiling

    INSTALLATION (CONTINUED) PermaFrame for Hard/Gypsum Ceilings The PermaFrame provides a support structure and room-side finish trim in one piece. It is supplied with predrilled mounting holes located on the vertical flanges, which are used to easily level and anchor the frame to customer-supplied studs above the ceiling structure. Manufactured of 16 gage cold rolled steel or stainless steel and welded on all exposed corners to guarantee a smooth, cleanable surface.
  • Page 10: Grille Installation And Removal

    INSTALLATION (CONTINUED) Grille Installation and Removal The RSR unit is supplied with a standard removable grille made of 40% open area in Painted Steel, Aluminum, and Stainless Steel. Grille mounting is supplied as standard four (4) corner acorn nut design for 2x2 & 2x4 units and eight (8) acorn nuts for 3x4 & 4x4 units. The grille is fastened onto threaded studs using acorn nuts, one in each corner for 2x2 &...
  • Page 11: Filter Unpacking, Installation, Storage And Operation

    • Before removing the filter from the carton, carefully read the removal and handling instructions printed on the outside of the carton. • AAF Flanders Cleanroom filters may come packaged in suitcase-style cardboard sleeves. If so, simply reach into the box and grab the handles pre-punched within the insert.
  • Page 12: Storage

    FILTER UNPACKING, INSTALLATION, STORAGE AND OPERATION (CONTINUED) Storage • Location: Storage should be indoors (under roof and enclosed) and absolutely protected from moisture. • It is strongly recommended that the storage space be climate-controlled. – Temperature Limits: Maximum temperatures of 250°F (121°C) intermittent, and 100°F (38°C) steady state.
  • Page 13: Inlet Options

    FILTER UNPACKING, INSTALLATION, STORAGE AND OPERATION (CONTINUED) Inlet Options The AstroFan EC FFU is available as standard for plenum supply applications and is also available ™ with the option for prefiltration, either particulate or AMC, or in a ducted supply configuration. The prefilter option is designed to accommodate standard 20"x20"x2"...
  • Page 14: Power And Electrical

    FILTER UNPACKING, INSTALLATION, STORAGE AND OPERATION (CONTINUED) Power and Electrical Install wires and make electrical connections to appropriate voltage, matching the nameplate information on unit. Install wires in accordance with all local, state, and nation electrical codes. Power into the unit should be connected to the L1, L2, and Ground pins on the power terminal block. Appropriate gauge wire, cabling, and strain relief should be utilized per governing code.
  • Page 15: Wiring Diagram For Ebm Blowers And Aaf Flanders Control Interface

    WIRING DIAGRAM FOR EBM BLOWERS AND AAF FLANDERS CONTROL INTERFACE...
  • Page 16: Appendix A - Warranty Information

    To obtain assistance under this limited warranty please contact the selling agency. To obtain information or to gain factory assistance, contact AAF International Warranty Claims Department, 9920 Corporate Campus Drive, Suite 2200, P.O. Box 35690, Louisville, Kentucky 40223-5000; Telephone (502) 637- 0011, FAX (888) 223-6500.
  • Page 17: Appendix B - Manual Revision History

    APPENDIX B – MANUAL REVISION HISTORY Revision Revision Description of Change Approval Version Date...
  • Page 18 Momence, IL Yuki, Japan (Nippon Muki) Smithfield, NC Contact your local AAF Flanders representative Tijuana, Mexico for a compete list of AAF Flanders Air Filtration Votorantim, Brazil Product Solutiobns. Washington, NC AAF Flanders has a policy of continuous product research and improvement. We reserve the right to change design and specifications without notice.

Table of Contents