Download Print this page

FCI 2400 Series Quick User Manual

Photoelectronic detector

Advertisement

Quick Links

DESCRIPTION
The System Sensor 2400 Series photoelectronic smoke de-
tectors are specifically designed to meet the performance re-
quirements of fire detection/alarm systems. These detectors
use state-of-the-art optical sensing chambers. The detectors
are designed to provide open area detection and are compati-
ble with FCI fire alarm control panels. The detectors' opera-
tion and sensitivity can be tested in place. The Model 2400T
unit has the same specifications as the Model 2400, but in ad-
dition it features a built-in fixed temperature (135
detection unit.
Each detector has an LED which flashes every ten seconds
indicating that power is being applied to the detector. The
LED lights steadily when the detector is in alarm. A remote
LED annunciator is available as an optional accessory.
The 2400 and 2400T detectors include a tamper-resistant
feature that, when used, prevents removal of the detector
without the use of a tool.
Sensitivity testing is performed either by inserting a tool
into the recessed test switch opening or inserting a calibrated
test card according to the test procedures.
Field metering of detector sensitivity may be performed
with the aid of a voltmeter and test kit MOD 400R.
APPROVALS
Nominal sensitivity
Operating voltage
Operating current
Operating temperature
Operating humidity
Air velocity
Construction
Diameter
Height
Weight
NOTE: Alarm current is limited by control panel initiating device circuit.
Part Number
16 Southwest Park, Westwood, MA 02090 USA TEL: (781) 471-3000 FAX: (781) 471-3099
o
F) thermal
TECHNICAL SPECIFICATIONS
3.0%/ft. obscuration
8.5 - 35 VDC (24 VDC nominal)
120 uA maximum
o
32
to 120
10% to 93% relative humidity
3,000 fpm max.
Off-white flame-retardant plastic
5.5 inches (14 cm)
3.19 inches (8.0 cm) high,
0.7 lb. (310 gm)
ORDERING INFORMATION
Model
Description
2400
Photoelectronic Detector
2400T
Photoelectronic Detector w/135
An ISO 9001 Certified Company
2400
SYSTEM SENSOR
PHOTOELECTRONIC
SMOKE DETECTOR
FEATURES
·
Built-in Tamper-resistant Feature
·
Built-in Test Switch
·
Built-in Visual Alarm Indicator
·
Remote LED Option
·
Compatible with FCI Control Panels
·
Field Metering of Detector Sensitivity
·
Removable Insect Screen and Cover
for Field Cleaning
·
Sealed against Dirt, Insects, and Back
Pressure
·
Insect-resistant Screening
(.020"/.508mm openings)
·
Convenient Terminal Strip Wiring
o
o
o
F (0
to 49
C)
o
F thermal
9020-0587/Ver. 1.0

Advertisement

loading

Summary of Contents for FCI 2400 Series

  • Page 1 The detectors are designed to provide open area detection and are compati- ble with FCI fire alarm control panels. The detectors’ opera- tion and sensitivity can be tested in place. The Model 2400T unit has the same specifications as the Model 2400, but in ad-...
  • Page 2 WIRING DIAGRAM FOR USE WITH FCI CONTROL PANELS Specifications are provided for information only, are not intended to be used for installation purposes, and are believed to be accurate. However, no responsibility is assumed by Fire Control ©...

This manual is also suitable for:

24002400t