APPLICATION
Honeywell HUVF Series is designed for installation inside
the air handling units or ductwork of the HVAC system for
the purpose of surface disinfection using ultraviolet
germicidal irradiation. This system is uses UV-C
technology which is effective in killing mold, bacteria and
viruses. This system is effective in coil cleaning and helps
in maintaining the cooling coil efficiency. This UV based
system is effective in deactivating the microbes and
improving the overall indoor air quality by reducing the
microbial load on the indoor air.
FEATURES
• Suitable for mounting in AHU near Cooling coil.
• Plug and Play design enables ease of installation.
• Effective on all types of pathogens.
• HUVF58C2000 / HUVF58S2000: 2 Lamps - 23W max.
each.
• HUVF58C1000 / HUVF58S1000: 1 Lamp - 23W max.
• Effective in IAQ improvement.
• Effective deactivation of viruses and bacteria killing
with 254 nm wavelength UVC.
• Effective in reducing microbe generated VOCs in
AHU.
SPECIFICATIONS
Model: See Table 1.
Electrical Ratings:
Power Consumption: See Table 1.
Voltage Rating: 230 Vac ±10%, 50/60 Hz
Operating Environment:
Temperature: 5 °C to 40 °C
Humidity: 0 to 90% RH (non-condensing)
Mounting:
Mounts into the AHU between the pre-filters and cooling
coils with lamps facing the cooling coils.
Application .....................................................................................
Features ..........................................................................................
Specifications ...............................................................................
Planning the Installation .........................................................
Installation ....................................................................................
Wiring ..............................................................................................
Operation and Maintenance ..................................................
Service .............................................................................................
Electrical Troubleshooting ......................................................
Parts List ........................................................................................
PRODUCT DATA
Contents
1
1
1
3
4
5
5
6
7
7
31-00455-01

Advertisement

loading

Summary of Contents for Honeywell HUVF Series

  • Page 1 • Effective in reducing microbe generated VOCs in AHU. APPLICATION SPECIFICATIONS Honeywell HUVF Series is designed for installation inside the air handling units or ductwork of the HVAC system for Model: See Table 1. the purpose of surface disinfection using ultraviolet germicidal irradiation.
  • Page 2 , using regular lamps under standard conditions. Ballast Type: High frequency electronic Repair Parts: See Table 2. Regulatory Approvals: CE, RoHS Fig. 1. Dual lamp HUVF Series dimensions. IMPORTANT This symbol on our product shows a crossed-out 102.4 mm 350.0 mm “wheelie-bin”...
  • Page 3 The HUVF Series is used in forced air heating, cooling, or ventilating systems. The system is mounted in the air handling unit (AHU) or ductwork where there are cooling coils or other surfaces that require ultraviolet treatment.
  • Page 4 HUVF SERIES DUCT MOUNTED UV SYSTEM Power Connection To adjacent unit Fig. 5. Array interconnections. Constructing Array Support WARNING Structure UV Light Hazard. Harmful to bare skin and eyes. Can cause temporary or permanent loss of vision. WARNING Do not look at the UV lamp when lighting is on. Use indicator light on the ballast to check status.
  • Page 5 HUVF SERIES DUCT MOUNTED UV SYSTEM Connect the Lamps MERCURY NOTICE This device contains mercury in the sealed WARNING ultraviolet bulb(s). Do not place your used bulb(s) in Breakable Glass Hazard. the trash. Dispose of properly. Can cause personal injury.
  • Page 6 See Table 2 for replacement ELECTRONIC BALLAST FOR UV LAMPS lamp part numbers. For replacing the lamp(s) on the HUVF series first disconnect the power of the system. Remove the 4-pin holder on top of the lamp by pulling the lamp out of the Fig.
  • Page 7 HUVF SERIES DUCT MOUNTED UV SYSTEM ELECTRICAL Troubleshooting Procedure TROUBLESHOOTING The power supply to the system is connected using plug and play connector arrangement. Make sure that proper PPE are used before start of any testing. Please note that UV is harmful to human being and hence the system must...
  • Page 8 HUVF SERIES DUCT MOUNTED UV SYSTEM Honeywell Building Technologies Honeywell International (India) Pvt. Ltd. 1120-21, 11th Floor, Tower A, DLF Tower Jasola District Centre Jasola, NEW DELHI, 110025, India 1-800-103-4761 Honeywell Building Technologies Honeywell GmbH Böblinger Strasse 17 71101 Schönaich, Germany...