Pyrotector 30-3013 Instructions Manual

Pyrotector 30-3013 Instructions Manual

Explosion proof smoke detector

Advertisement

Instructions
Explosion Proof Smoke Detector
30-3013
3.1
Rev: 11/2020
95-8746

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 30-3013 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Pyrotector 30-3013

  • Page 1 Instructions Explosion Proof Smoke Detector 30-3013 Rev: 11/2020 95-8746...
  • Page 2: Table Of Contents

    Accessories..... . . 13 30-3013 Model Matrix ....13 APPENDIX A –...
  • Page 3: Overview

    • Ideally suited for classified areas in the variety of port configurations for simplified wiring petrochemical, oil, and gas industry and installation. See Figure 1 for all the 30-3013 • DCS, PLC, integration with milliamp or relay Smoke Detector components.
  • Page 4: Specifications

    I.S. SENSOR MODULE RETAINING RING JUNCTION BOX A2679 Figure 1—30-3013 Components SPECIFICATIONS INGRESS PROTECTION— IP44 Note: Applicable to ceiling mount only OPERATING VOLTAGE— 12-30 Vdc (24 Vdc nominal) CURRENT OUTPUT— 0-20 mA (±0.3 mA) dc current, with maximum loop SMOKE DENSITY—...
  • Page 5: Operation

    If the detector is unable to reach the normal operating mode, the warm-up period may extend This 30-3013 provides a 0 to 20 mA dc current for to five seconds, followed by a critical fault or an transmitting detector status information to other advisory fault (see Table 1 for all current levels).
  • Page 6: Integral Wiring Compartment

    During normal operation, the detector performs is monitored by the fault detection circuitry the Self-Test function automatically in the of the 30-3013. Therefore, an open circuit on background once per second. During the test, the loop will cause the fault relay to change detection is not interrupted and no indication is state.
  • Page 7: Important Safety Notes

    The recommended lubricant is a silicone-free grease, available from Det-Tronics. CAUTION For devices with NPT threads, Teflon tape or The 30-3013 is to be installed in locations thread seal lubricant must be used for enhanced where the risk of mechanical damage is low. sealing capabilities.
  • Page 8: Protection Against Moisture Damage

    Wall Mount The 30-3013 can also be mounted on a side wall TRANSPORT COVER (see Figure 6). The exact location of the detector The Transport Cover (see Figure 4) keeps dust...
  • Page 9: Mount The Detector

    A minimum of 12 Vdc must be present at the 30- 3013 to ensure proper operation. The maximum cable length from power source to 30-3013 is 2000 feet (610 m). When the 30-3013 Smoke Detector is mounted remotely using an STB termination box, maximum cable length from 30-3013 to STB is 500 feet (150 m).
  • Page 10: Wiring Procedure

    Slightly loosen the three setscrews located NO FAULT on the retaining ring (see Figure 7). RETAINING RING SET SCREWS (3) A2683 Figure 9—30-3013 Wiring Terminals – Figure shows ground locations. – Figures 12 and 13 show wiring for single detector configurations.
  • Page 11: Maintenance

    ROUTINE INSPECTION Regularly scheduled maintenance required, however, the 30-3013 cover and smoke chamber should be inspected periodically when detectors are located in abnormally dirty or dusty environments, to ensure the smoke chamber is not blocked by dirt or debris.
  • Page 12 Control Panel – AT 24 VDC – RELAY OUTPUTS POWER NO AUX POWER SUPPLY & 0-20 mA OUTPUT COM AUX – mA NC AUX – Vin NO ALARM + Vin COM ALARM – Vin NC ALARM + Vin COM FAULT 2 WIRE CLASS B NO FAULT...
  • Page 13 95-8746...
  • Page 14 95-8746...
  • Page 15: Device Repair And Return

    If it is determined that the problem is 30-3013 Explosion Proof Smoke Detector caused by an electronic defect, the device must Refer to the 30-3013 Model Matrix for details. be returned to the factory for repair. The sensor module is field replaceable in case of dirtiness, For assistance in ordering a system to fit your damage, or failures incurred in the field.
  • Page 16: Appendix A - Fm Approval Description

    “i" Special Conditions For Safe Use X: The 30-3013 is to be installed in locations where the risk of mechanical damage is low. Potential electrostatic charging hazard please see instructions for proper installation. All unused device openings must be closed using a suitably certified plug.
  • Page 17: Appendix B - Csa Approval Description

    APPENDIX B CSA APPROVAL DESCRIPTION 30-3013 Class - C481804 - Signal Appliances - Systems - For Hazardous Locations Ex db ia IIC T4 IP44 Applicable Requirements C22.2 No. 0-M91 General requirements - Canadian Electrical Code, Part II C22.2 No. 60529: 2015 Degrees of protection provided by enclosures (IP Code).
  • Page 18: Appendix C - Iecex Approval Description

    Intrinsic Safety explosive atmospheres Equip protection by Intrinsic Safety Special Conditions For Safe Use X: The 30-3013 is to be installed in locations where the risk of mechanical damage is low. Potential electrostatic charging hazard please see instructions for proper installation.
  • Page 19 This page intentionally left blank 95-8746...
  • Page 20 95-8746 Corporate Office Phone: 952.941.5665 All trademarks are the property of their respective owners. © 2020 Carrier. All rights Reserved. Toll-free: 800.765.3473 6901 West 110 Street Fax: 952.829.8750 Minneapolis, MN 55438 USA Det-Tronics manufacturing system is certified to ISO 9001— the det-tronics@carrier.com world’s most recognized quality management standard.