Entering incorrect settings may result in damage to equipment. If the SP6R-X controller was shipped pre-installed in a control panel, some default values may have been changed at the factory in order to properly test the control panel operation. The user must adjust the settings...
INTRODUCTION & SPECIFICATIONS Thank you for your purchase of the SP6R-X controller. This manual explains the features and operations of the SP6R-X controller which was designed to monitor a 4-20mA input signal. The controller features six programmable relay outputs that can be used for control and alarm puposes.
PRESS FOR ENTER • Press knob for ENTER or to save settings. Button Returns To Previous Menu Back Button for Stepping Screen, and Exits a Parameter Edit Backward and Changing Value Screen Without Saving Changes. Adjustment Scale. SP6R-X Controller User Manual ®...
Depending on the specific adjustment, hundreds may not be an option. To adjust the scale, click the ◄ button until the desired increment is highlighted. Ones will be adjusted Tens will be adjusted Hundreds will be adjusted SP6R-X Controller User Manual ®...
This can be helpful for troubleshooting a system to ensure the controller is functioning correctly without actually having various level scenarios available. Rotate the selector knob to make fine adjustments. To make coarse adjustments, press and hold the ◄ button while rotating the selector knob. SP6R-X Controller User Manual ®...
Set this value to the displayed level reading that should correspond with the bottom of the bar graph. BAR GRAPH MAXIMUM Set this value to the displayed level reading that should correspond with the top of the bar graph. SP6R-X Controller User Manual ®...
(below 3.75 mA or above 20.25 mA). By default, the relay outputs are off (open) when the analog input is out of range. Within the allowable range, the relays operate accord- ing to the relay setpoints. SP6R-X Controller User Manual ®...
MODBUS SETUP MENU The Modbus Setup menu contains the following two settings: NODE ADDRESS This is the Modbus address of the SP6R-X. BAUD RATE The Modbus communication baud rate can be set to the following: 1200, 2400, 4800, 9600, 19.2K, 38.4K...
For an emptying application, the ON setpoint must be greater than the OFF setpoint. For a filling application, the ON setpoint must be less than the OFF setpoint (See below). NOTE: For proper operation of the SP6R-X controller, the ON and OFF setpoints must not be set to the same value.
I/O TERMINAL CONFIGURATION 24VDC IN SHIELD A OUT AO COM +24 VDC SUPPLY AI LEVEL AI COM SHIELD RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED SP6R-X Controller User Manual ®...
Protective Earth Ground at terminal PROGRAMMABLE RELAY #4 J1-11 or J1-12. PROGRAMMABLE RELAY #5 Use Copper Conductors, rated 60°C (140°F) PROGRAMMABLE RELAY #6 Apply Torque Value of 4.5 In-lbs to Field Wiring Terminals. SP6R-X Controller User Manual ®...
MODBUS COMMUNICATION The SP6R-X is equipped with Modbus RTU support using the D+ and D- RS-485 terminals. The Modbus registers and communications specifi cations are designed to work with an SJE Panel Link Gateway right out of the box. ™...
SP6R-X CONTROLLER SETPOINTS LIST STATION NAME: START UP DATE: CONTROLLER REV: DEFAULT VALUE USER SETTING RELAY SETPOINTS Relay 1 On 999.9 Relay 1 Off 999.9 Relay 2 On 999.9 Relay 2 Off 999.9 Relay 3 On 999.9 Relay 3 Off 999.9...
Need help?
Do you have a question about the SP6R-X and is the answer not in the manual?
Questions and answers