INSTALLATION AND MAINTENANCE INSTRUCTIONS
GENERAL
These instructions must be carefully read before any work involving products supplied by VALSTEAM ADCA
ENGINEERING S.A. is undertaken.
The installation procedure is a critical stage in a life of a steam trap and care should be taken to avoid damage
to the trap or equipment.
Warning!
- At start up, the presence of small particles in the water (dirt, scale, weld splatters, etc) may cause an imperfect
closure of the seat. If this occurs, proceed to an accurate cleaning.
- Do not touch the equipment without appropriate protection during working operation because it may conduct heat
if the used fluid is at high temperature.
- Before starting maintenance be sure that the equipment is not pressurized or hot.
- The equipments must be used within the working temperature and pressure limits laid down for them, otherwise
they may fail (refer to nameplate and/or IS- Information Sheet).
- Do not remove the nameplate attached to the equipment. Serial number and other useful information is stamped
on it.
INSTALLATION
- Before to install remove plastic covers placed on flanges or connection ends. The equipment has an arrow or
Inlet/Outlet designations. Be sure that it will be installed on the appropriate direction.
- Install the steam trap in the point of the system, where the condensate tends to collect. It must be installed with the
float lever in horizontal plane, so that it rises and falls vertically. An ADCA strainer should be installed upstream of
the trap.
BODY LIMITING CONDITIONS
FLANGED
PN16 *
ALLOWABLE
PRESSURE
16 bar
15,5 bar
14,7 bar
13,9 bar
PMO – Max. operating pressure
TMO – Max. operating temperature
*Acc. to EN1092-2:2007 ; **Acc. to EN1759-1:2004
Body limiting conditions PN16 or below, depending on the
type of connection adopted. PN16 for thread.
ADCA
VALSTEAM
FLOAT & THERMOSTATIC STEAM TRAPS
FLANGED
ANSI 150 lb **
RELATED
TEMPERATURE
ALLOWABLE
PRESSURE
15,4 bar
100 ºC
14,6 bar
150 ºC
13,8 bar
200 ºC
12,1 bar
250 ºC
14 bar
198 ºC
FLT17
We reserve the right to change the design and material of this product without notice.
IMI 1.335 E 03.14

Advertisement

loading

Summary of Contents for VALSTEAM ADCA FLT17

  • Page 1 FLT17 GENERAL • These instructions must be carefully read before any work involving products supplied by VALSTEAM ADCA ENGINEERING S.A. is undertaken. • The installation procedure is a critical stage in a life of a steam trap and care should be taken to avoid damage to the trap or equipment.
  • Page 2: Maintenance

    When reassembling make sure that all gasket faces are clean and always use a new gasket. Tighten cover bolts uniformly in a diagonal sequence. • For further information refer to the relevant FLT17 brochure or consult our Sales Office. TROUBLESHOOTING If the malfunctions cannot be solved with the help of the following chart, please consult the manufacturer.
  • Page 3 1Set DN1/2”-1” A.92.1502.115 Float & gasket 3, 7 1Set DN1/2”-1” A.92.1502.215 Air vent & gasket 3, 8 1Set Recommended tightening torques FLT17 DN 1/2”-1”, DN15-DN25 TRAP SIZE POS.NR. 1/2”-1” 50±5 1/2”-1” 50±5 1/2”-1” 70±5 Remarks: Tighten cover bolts uniformly. ADCA VALSTEAM We reserve the right to change the design and material of this product without notice.
  • Page 4 DN11/2”-2” A.92.1502.140 Float & gasket 3, 7 1Set DN11/2”-2” A.92.1502.240 Air vent & gasket 3, 8 1Set Recommended tightening torques FLT17 DN 11/2”-2”, DN 40-50 TRAP SIZE POS.NR. DN11/2”-2” 10-15 (4xM16) DN11/2”-2” 50±5 DN11/2”-2” 85±5 Remarks: Tighten cover bolts uniformly.
  • Page 5 Valsteam ADCA engineering. Health and safety data sheets regarding substances identified as hazardous or potentially hazardous must be provided with the information mention above.

This manual is also suitable for:

Flt17hc