User Manual Greenkeeper Feedback 2‐wire Decoder Control System with Software ® for Windows 95/98/2000/NT/XP and Windows7 User Manual Phone: +49 (0) 7051 162‐0 Perrot ‐ Regnerbau Calw GmbH E‐Mail: technik@perrot.de Industriestrasse 19‐29 Web: http://www.perrot.de Germany‐ 75382 Althengstett ® Windows 95/98/NT/XP and Windows7 are registered trademarks of Microsoft Corporation. Bed‐GK 1+2e Rev. 03.04.2019 Page 1 / 143 ...
User Manual Contents Foreword ................................. 5 Introduction .............................. 6 What is Greenkeeper Win? ........................ 6 Functional description .......................... 6 Functional description / Decoder with Feedback .................. 8 2.3.1 What means bidirectional decoder? .................... 8 2.3.2 Which signals can be transferred? .................... 8 2.3.3 PC requirement profile ........................ 8 Hardware Installation ............................ 10 ...
Page 3
User Manual 7.10.4 Modem Commands ........................ 57 7.11 Backup / Restore Data ........................... 59 7.12 System Setup ............................ 62 7.12.1 Font Select ............................. 62 7.12.2 Copying the graphic from the data medium on the hard disc: ............ 63 7.12.3 Surveillance picture ........................ 64 7.12.4 User Passwords .......................... 67 Program Configuration .......................... 68 Single Valves ............................ 69 ...
Page 4
User Manual 14.4.7 Service Menu 05 .......................... 128 Decoder .............................. 129 15.1 Programming of Decoder ........................ 129 15.1.1 To program a decoder you need the following components: ............ 130 15.1.2 Preparation for programming the Decoder ................ 131 15.1.3 Programming with DPG Programming unit (part no. ZH90022) .......... 132 15.1.4 Programming with DPK Programming cable (part no. SG50032) .......... 133 15.1.5 FB‐Decoder Indication Light ...................... 134 15.1.6 Decoder List .......................... 135 ...
1. Foreword This documentation and the programs described herein may not be transmitted, reproduced or modified either completely or in part in whatever format or by whatever media nor may they be translated into another natural or machine language. Excluded from this condition is the making of a backup copy for personal use. Any transfer of information obtained herewith to a third party is only allowed with a written permit from REGNERBAU CALW GMBH. All programs and documentation are developed with the greatest care and reviewed for correctness using state‐of‐the‐art standards. REGNERBAU CALW GMBH is only liable for damage arising, either directly or indirectly, from the use of the documentation and the related programs, as well as the accidental damage, or consequential damage, caused intentionally or due to gross negligence. All liabilities are expressly disclaimed for the loss of, or damage to, hardware, software or data, resulting from a direct or indirect fault or destruction, as well as for the costs, incl. costs for telephone connection, incurred in relation to the supplied programs and documentation and faulty installations not performed by REGNERBAU CALW GMBH. The information contained in this documentation and the related programs can be changed without special notice for the purposes of technical improvements. REGNERBAU CALW GMBH. All rights reserved. Industriestrasse 19 ‐ 29 D‐ 75382 Althengstett Telephone: +49 (07051) 162‐0 E‐mail: Perrot@perrot.de Internet: http://www.perrot.de Bed‐GK 1+2e Rev. 03.04.2019 Page 5 / 143 ...
User Manual 2. Introduction What is Greenkeeper Win? Greenkeeper Win is a PC‐computer control system with a sophisticated third generation decoder system. By clicking a button, the programs created on a PC are sent within a matter of seconds to the Valve Control Unit. From there, electric pulses are transmitted via a single 2‐wire cable to as many as 250 decoders that energize/deenergize the solenoids. This enables you to avoid expensive installations, difficult modifications or disruptive earth works during extensions as well as all costs incurred thereby. Assisted by your PC and the Greenkeeper Win software you create an irrigation program according to your wishes. The program is then downloaded via the serial port to the VCU. Functional description The Greenkeeper Control System consists of the following components (minimum configuration): 1. Valve Control Unit (VCU) 2. Windows 98/NT/2000/XP or Windows 7 ‐ compatible PC with a modem (optional) 3. 2‐wire decoder cable 4. ...
Page 7
User Manual The different valves or solenoids are given a unique name in Greenkeeper Win and are assigned to a decoder number. Greenkeeper Win will use the above data to calculate the duration if you enter the required precipitation or the precipitation if you enter the duration. The irrigation programs that you create will be downloaded to the VCU via a serial port. The VCU will then independently control the irrigation according to the data you entered while the PC can be used to serve other purposes. During irrigation the VCU stores data from the executed programs, e.g. the valve opening and closing time, precipitation density, etc. You can retrieve the data stored in the PC and print it. The Windows based program interface requires no special computer skills. On the other hand, familiarity with the Windows environment can make your work with Greenkeeper Win much easier. Data is entered by clicking with the mouse in a Data Entry or Option/Selection field. You then either type the values or select one of the proposed values in an Option/Selection field. Greenkeeper is the only program on the market offering a realistic graphic representation of the areas irrigated. In the graphic you can place valve symbols in the actual locations where the solenoids are situated. By clicking the symbol you can open and close the valve. It is also possible to energize individual valves using a hand terminal connected to a field connector. Moreover, you can control the VCU by mobile telephone* or by a PC over a telephone line. To use this function you only need a modem and a terminal program, such as the one included in the Windows installation package. The VCU has additional connection options for external sensors, e.g. precipitation meter, anemometer, flow meter, and pressure gauge. The sensors send the values measured to the VCU. The data can be retrieved in the Greenkeeper program. You then decide whether the data will only be recorded or fed into the Irrigation Control System to modify the program operation. A flow‐check device built directly into the supply pipe allows the user to carry out decoder and valve tests. Bed‐GK 1+2e Rev. 03.04.2019 ...
User Manual Functional description / Decoder with Feedback Greenkeeper Win supports the bidirectional decoders (PD/F‐1). Of course the standard decoders from Greenkeeper Win can also be used with Greenkeeper FB. But if you want to use the new features it is necessary to install the bidirectional decoders. It’s possible to mix both kinds of decoders in one system, too. 2.3.1 What means bidirectional decoder? The bidirectional decoder PD/F‐1 sends its status information back to the VCU. This information will be processed by the software. VCU and decoder are in permanent communication. All bidirectional decoders will be periodically interrogated. Due to the use of the new decoders, in combination with Greenkeeper Win, a check of the decoder, solenoids, electrical valves and the pump relays is feasible. This makes it easy to check all important parts of your system permanently. The user gets quick and specific information. At an early stage problems can be identified and be logged in a report. Depending’s on the settings of the software the system can be automatically switched off and sending additionally a message by telephone. The status information of the bidirectional decoders will be periodically integrated. Depending on this status information (combination) the VCU reacts according to the software settings. 2.3.2 Which signals can be transferred? at Greenkeeper / conventional decoder number run times at Greenkeeper / bidirectional decoder number run times valve off – no pressure ...
Page 9
User Manual Usually the requirement profile of the PC will be achieved by all PC’s in the market. Operating Microsoft Windows 98 / 2000 / NT / XP / Windows7 system (OS): complete installed and configured Intel Pentium od CPL/CPU: AMD 500 MHz or higher. min. 64 MB RAM at Windows 98 Random Access min. 128 MB RAM at Windows 2000 / NT memory: RAM min. 512 MB RAM at Windows XP Interface/Port: 2 x serial port (COM1 and COM2) ...
User Manual 3. Hardware Installation On‐site preparations for the installation of the Valve Control Unit (VCU) A “Schuko” socket is needed for the power supply. Disconnect the green‐yellow earth conductor from the socket. Grounding will be facilitated via the VCU. Plug the supplied surge protector in the socket. Mount the Valve Control Unit (VCU) to its location on the wall. Connect the available decoder cable to terminal 34/35. If you need to run multiple decoder cables (up to 3 units) use terminals 36/37 and 38/39 next. (See also User Manual Page chapter10, Wiring schematic) Connect the external interfaces such as Rain gauge Type Mini Click to their corresponding terminals. IMPORTANT: Please check the VCU version on the inside and outside label on the door!! If it does not show Greenkeeper Win, follow the instructions for a chipset update. Without the new chipset the VCU is not compatible with Greenkeeper Win. Grounding with an earth conductor to BA 10119. An earth conductor at least 20 m long shall be buried in a ditch at least 70 cm deep, in accordance with BA 10119. The earth resistance should be less than 10 Ohm. ...
User Manual This will be dealt with in greater detail later. The red LED must not be lit up. If the red LED lights up a faulty decoder cable is indicated. Please double check all cable and decoder connections. Grounding System for Greenkeeper and TWT BA10119 Bed‐GK 1+2e Rev. 03.04.2019 Page 11 / 143 ...
User Manual 4. Getting the Computer Ready for Installation Check first which interfaces are available by Windows XP. Do that like descripted as following: Click “Start ‐> Customize ‐> Control Panel” Left mouse click on the symbol [Control Panel]. In "Control panel" click on the symbol [Administrative Tools] Bed‐GK 1+2e Rev. 03.04.2019 Page 12 / 143 ...
Page 13
User Manual Left mouse click at [System] and [device manager]. Bed‐GK 1+2e Rev. 03.04.2019 Page 13 / 143 ...
Page 14
User Manual Left mouse click at [Ports (Com&LPT)]. Here are all devices are listed. Please choose the icon below. Thereupon all available ports will be shown. The VCU is connected via a serial port (RS 232). A standard PC computer has two serial ports available. The first I/O port is marked COM1. (Communication Port 1) The second I/O port is marked COM2 (Communication Port 2). To each I/O port a particular IRQ (interrupt request line) is assigned. The IRQ can only be used once for a device. It is not possible to assign two devices to one IRQ. This would inadvertently lead to a conflicting IRQ‘s problem. Bed‐GK 1+2e Rev. 03.04.2019 Page 14 / 143 ...
User Manual Modem Installation (ONLY FOR COMMUNICATOR OPERATION) Two serial ports must be free! The COM2 part is only needed for the use of the Nokia Communicator. Connect the modem to the telephone outlet using the supplied cable. (Only for Germany) Please pay attention to the coding in telephone outlets with 3 sockets. The central socket is an F‐coded socket (long distance). The modem also has an N‐coded (non‐long distance) plug that fits only in an N‐coded socket. Therefore use the left‐hand side socket. Do not use the right hand side socket, which may be disconnected. For other countries consult your telephone company. Using the cable, connect now the modem to the COM 2 serial port. Please make sure that you actually use the COM 2 port. Now connect the modem to the power supply using the adapter supplied. Switch the modem on. Switch the computer and monitor on. Windows now automatically detects the new modem and installs the appropriate driver. Windows now automatically detects the new modem and installs the appropriate driver. After a successful installation, check whether the modem has been correctly installed. Click on [control panel] Bed‐GK 1+2e Rev. 03.04.2019 ...
Page 16
User Manual The window [control panel] opens: In this window click on: [Phone and Modem…] All the modems installed will be listed in this window. You can view the modem properties in this window. Note the [Port:] field in the Properties window. It must display the correct COM port COM2. Click Ok if it is correct. Bed‐GK 1+2e Rev. 03.04.2019 Page 16 / 143 ...
User Manual Installation of Greenkeeper Software under Windows Installation – Step by step It is assumed that a modem and a printer are installed and ready to operate. If your computer is not running, switch on the devices you will need in the following order: Monitor Modem (if available) Printer (if available) Computer When Windows are up and running you can start with the installation of the Greenkeeper software. Proceed as follows: Take the „Greenkeeper“ CD into the CD‐ROM drive and click on: Move the mouse on this button and click it Choose in the start menu ‐ Run ‐ Following window opens: Type the following in the white Command Line: D:\Setup.exe (from a CD‐ROM) or ...
Page 18
User Manual The Setup Wizard is preparing the installation. This is the Welcome screen. Should you want to terminate the installation, click [Cancel] Click [Next] to continue with the installation. Bed‐GK 1+2e Rev. 03.04.2019 Page 18 / 143 ...
Page 19
User Manual The Setup program proposes a directory for the installation. Confirm the directory by clicking [Next] once. Bed‐GK 1+2e Rev. 03.04.2019 Page 19 / 143 ...
Page 20
User Manual Click on „Next“ to continue with the installation Here you can review all information once again. Should you want to make changes, just click [Back]. By clicking [Cancel] you have the option of exiting the installation. Bed‐GK 1+2e Rev. 03.04.2019 Page 20 / 143 ...
Page 21
User Manual To confirm the settings as they are click [Next] and the installation will continue. After all the installation disks have been copied the Setup Wizard arranges the data in folders. Click [Finish] to complete the installation. Bed‐GK 1+2e Rev. 03.04.2019 Page 21 / 143 ...
User Manual Creating a Shortcut on Desktop To start „Greenkeeper Win“ by a double‐click an icon on the desktop was generated. If this is not the case: Clock on the „Start“ button. Choose in the menu [programs]. Clock on GK‐Win and move it to the desktop. The icon is generated. Graphics Installation You can use up to 10 graphic files (*.bmp). Copy the files in the C:\Program Files\Greenkeeper Win95\bmp directory. You can select the file you need in the Greenkeeper program later. Bed‐GK 1+2e Rev. 03.04.2019 Page 22 / 143 ...
User Manual 5. Starting Greenkeeper Win You can start the Greenkeeper Win in 2 different ways: By double‐click on the icon at the desktop: Move the mouse pointer on the „Greenkeeper Win“ icon and double‐click. By the Windows program list: START ‐ Programs – Greenkeeper Win One click on [Greenkeeper Win] is enough. Bed‐GK 1+2e Rev. 03.04.2019 Page 23 / 143 ...
Page 24
User Manual The opening screen. Position the mouse pointer on Ok and click it once with the left mouse button. This is the menu bar. From here you can control Greenkeeper Win The menus that are available to you depend on the Password Level. After starting the software the password level 0 is default level. Bed‐GK 1+2e Rev. 03.04.2019 Page 24 / 143 ...
User Manual 6. Password Level Greenkeeper employs 4 different Password Levels. Password Level 0 is the default level when you start the program. It is the only level accessible without a password. Consequently, its functions are limited. In Password Level 0 you have access to the following menus: File System configuration Downloading Surveillance About Password Communication setup Change active (limited) programs This Password Level provides you with everything you need for the control of Change Active Programs. To change the Password Level, position the mouse pointer over the File menu on the top of the screen. After clicking it with the left mouse button, the menu opens. Now position the mouse pointer over Password and click it with the left mouse button. Whenever you come across Click … in the following pages it always means position the mouse pointer over a particular spot and clicks the left mouse button. ...
User Manual Enter your password for the level you want and press [ENTER]. The selected Password Level will appear in the top right‐hand corner. Click OK to display the selected Password Level. If you enter an invalid password Password Level 0 is selected. You can use the Clear Password button to delete your entry. The following Password Levels are available: Password Level 1 (medium security) Password:...... (you will receive it from the System Administrator) Can be changed by the System Administrator. Access to menus: Except: Pump data hydraulic groups and sectors Valve data General External VCU interface Backup/Restore System setup Service (without submenus) ...
User Manual Password Level 3 (no security) The password cannot be changed and will be given to the System Administrator during installation. Access to menus: All With this password you can change or delete all relevant data in Greenkeeper Win. Please, be careful when you log on under this password. Passwords for Level 1 and 2 can be changed using the System configuration – System Setup menu option. Bed‐GK 1+2e Rev. 03.04.2019 Page 27 / 143 ...
User Manual 7. The Installation Data’s The master data is divided into two subgroups: Pump data / hydraulic groups and sectors Pump designation and pump capacity Pump status Pump forerunning, last running, and interval time Division of the pipe network in hydraulic groups Division of hydraulic groups in hydraulic sectors Valve data The decoder number assigned to a valve number For each valve number, the area to be irrigated Valve numbers assigned to a particular hydraulic group and a hydraulic sector Water consumption of a valve The above data is specified during installation by the installer of the irrigation system and is duly recorded. Do not change any data without discussing it first with the installer of the irrigation system. Greenkeeper uses the above data to calculate how the program will run. After an update all programs must be deleted from Change active programs and from the VCU. All program configurations must be updated with the new master data and retested. (Program test) Only then can the program configurations be downloaded to the VCU and entered in Change Active Programs. ...
User Manual Pump data / hydraulic groups and sectors Use the password to go to Password Level 3. In the System Configuration menu click Pump data/hydraulic groups and sectors. The data entry window opens: Use this window to enter pump as well as hydraulic group and hydraulic sector specific data. As a rule the values are specified during installation. The window is divided into three areas: Pump setup Hydraulic group setup Hydraulic sector setup Bed‐GK 1+2e Rev. 03.04.2019 Page 29 / 143 ...
Page 30
User Manual Pump Setup You can define up to 5 pumps here. A different decoder number is assigned to each pump. Define the status of each pump here. Select a status option from the selection list. Not installed: The pump is not installed and will be not considered by the system. Passive: The pump is installed but used for different purposes, e.g. as a service pump. It will not be considered by the system. Active: The pump is installed and will be considered by the system. Enter the pump capacity for each pump in this field. Values: 0,0 ‐ 999,9 m³/h The capacity entered will only be taken into consideration for pumps with Active status. Bed‐GK 1+2e Rev. 03.04.2019 Page 30 / 143 ...
Page 31
User Manual Enter forerunning here. In the broadest sense also the delay. Values: 0 ‐ 250 seconds. After the start of the last pump the opening of the first valve is delayed by the Forerunning entered. Example: Pump 1 starts..5 s forerunning ..first valve opens. Enter the pump interval here. Values: 0 ‐ 30 seconds Only possible when more than one pump is used. The Interval is a pause in seconds between the activation / deactivation of two pumps. When the system is under full load (5 pumps) the Interval will be employed 4 times. Enter last running of the last pump here. Values: 0 ‐ 100 seconds. Last running is a period of time during which the pump continues running after the valve is closed. NOTE: Depending on Forerunning and Interval in extreme cases it can take up to 370 seconds before the first valve opens! Bed‐GK 1+2e Rev. 03.04.2019 Page 31 / 143 ...
User Manual 7.2.1 Example of Pump Start with Forerunning and Interval Pumps 1, 3, and 5 are installed and active. Forerunning: 50 seconds Interval: 20 seconds Program start, Pump 5 starts at the same time The pump with the highest number starts always first. The interval entered runs next. Pump 3 starts after the interval expires. The interval runs again. Pump 1 starts after the interval expires. Now Forerunning runs. The first valve opens after Forerunning expires. Second Operation 0 Program starts, Pump 5 starts 20 (Interval) 20 seconds later Pump 3 starts 40 (Interval) 20 seconds later Pump 1 starts (Relay 1 is energised) ...
User Manual 7.2.2 Example of Program End with Last running and Interval Pumps 1, 3, and 5 are installed and active. Last running: 50 seconds Interval: 20 seconds Program ends, all valves are closed, all pumps continue to run. Last running runs next. Pump 1 stop after Last running expires. The pump with the lowest number is always switched off first. The interval runs now. Pump 3 stops after the interval expires. The interval runs again. Pump 5 stops after the interval expires. Seconds Operation 0 Last valve closes 30 (Last running) Pump 1 stop (Relay 1 is deenergised.) 50 (Interval) Pump 3 stops 70 (Interval) ...
User Manual Hydraulic Groups During irrigation "Greenkeeper" tries to open as many valves as the pump capacity allows. When the valves are not assigned to a hydraulic group/sector the way the program runs is controlled by an algorithm which takes into consideration the flow of the different valves but disregards the pipe network arrangement and pipe dimensions. While in terms of irrigation efficiency it would be bad practice to supply the valves that are in operation simultaneously from the same pipe branch (pressure drop) it is essential to give Greenkeeper the information about which valves are supplied from which pipe branch and what the permitted maximum flow of the pipe branch is. By subdividing the pipe network into hydraulic groups and hydraulic sectors Greenkeeper is capable of making optimum use of the pipe network resources. Consequently, the irrigation time can be reduced to a minimum. Bed‐GK 1+2e Rev. 03.04.2019 Page 34 / 143 ...
User Manual 7.3.1 Example of a Pipe System In the example on the previous page each independently controlled sprinkler on the green has a water consumption of approx. 10 m³/h and the manifolds on the tee have consumption of 6 m³/h or 8 m³/h. The pump capacity of 40m³/h would make it possible for all the 4 sprinklers on the green to be in operation simultaneously. However, as the pipe supplying Green 1 would be overloaded while the other lines remain unused, the resulting pressure drops would be excessively high. For this reason it would be beneficial to arrange the valves from the example by dividing them in hydraulic groups and hydraulic sectors. When the flow for the hydraulic groups / sectors from the example is then entered, a maximum of 2 sprinklers can be in operation on the green simultaneously. The following flow diagram illustrates the example once again. Bed‐GK 1+2e Rev. 03.04.2019 Page 35 / 143 ...
User Manual Hydraulic Sectors Hydraulic Sectors are a subdivision of hydraulic groups. A hydraulic sector is always assigned to a hydraulic group. You cannot define hydraulic sectors without defining hydraulic groups first. A maximum of 40 sectors may be defined. Define hydraulic sectors here. Each sector is assigned a number from 1 – 40. Later you will only refer to a particular number. Click in the [Flow m³] field and type the required flow in m³. After clicking in another field the values entered will be saved. The flow of a sector depends on the flow of a hydraulic group and can never exceed the total pump capacity. Value range: 0 ‐ 999 m³ No hydraulic sector is assigned / created when 0 is entered. (The sector is deleted!) It is possible to assign multiple hydraulic sectors to a hydraulic group. The actual assignment does not take place until the valve data is entered. Bed‐GK 1+2e Rev. 03.04.2019 Page 37 / 143 ...
Page 38
User Manual When entering data pay attention to the following notes: The maximum flow rate is given by the pump capacity. When more than one pump is used the sum of all pumps is valid. If a value is higher than the maximum flow rate given you will receive an error message: Code:003 ‐ xx above limit The value entered is too high. The flow rate of the hydraulic groups and sectors must be higher than (or identical with) the flow rate of the valves assigned to them. If a value is entered that is lower you will receive an error message: Code:023 ‐ xxxx invalid flow The value entered is invalid. xxxx represents the valve in question. If the value entered is below the valid value range the following error message is sent: Code:002 ‐ xx below limit Enter a higher value. By changes all simulated programs will be deleted. Programs stay on the hard disk. All programs on the VCU have to be deleted. Repeat a new simulation and transfer the program again at the VCU. Bed‐GK 1+2e Rev. 03.04.2019 Page 38 / 143 ...
User Manual Valve Data In the System Configuration menu click the Valve Data option. All valve data is entered and stored here. Here the serial number of the valve is shown which is identical with the actual decoder number. Here you can change the order in which the individual valves are displayed. Normally, they are displayed according to the decoder number in ascending order. Value range: 1 ‐ 240 Default: Decoder number Bed‐GK 1+2e Rev. 03.04.2019 Page 39 / 143 ...
Page 40
User Manual Here enter a unique valve name assigned to a decoder number. Only one valve can be referred to under this designation. Value range: 1 ‐ 8 characters All letters will be automatically capitalised. Error messages: Code:008 ‐ xxx is already used (the valve name has already been used) Code:006 ‐ xxx exceed valid length (the valve name is too long, max. 8 characters) When entering valve names always start with the name of the area to be irrigated. There are sorting functions in Greenkeeper Win that always sort by the first letter. Example: G 01 ‐ 1 Valve sequence number Green 1 ...
Page 41
User Manual Areas to be irrigated by sprinklers located downstream from the valve. Value range: 0 ‐ 99999 m² The area, along with the water consumption and duration data, will be used to calculate precipitation. Assign the valve to a hydraulic group here. There are a maximum of 9 hydraulic groups available. Value range: A ‐ I No assignment: Empty field Assign the valve to a hydraulic sector here. The sector will then be assigned to a hydraulic group. Value range: 1 ‐ 40 No assignment: 0 NOTE: A hydraulic sector can only be used with a hydraulic group. The hydraulic groups and sectors must be predefined in the Pump Data menu. The maximum number of valves assigned to a sector may not exceed the sector capacity. (see the Pump data / hydraulic groups and sectors menu) The maximum number of sectors assigned to a group may not exceed the hydraulic group capacity. (See the Pump data / hydraulic groups and sectors menu) The maximum group capacity depends on the pump capacities. Bed‐GK 1+2e Rev. 03.04.2019 ...
Page 42
User Manual The theoretical flow based on the number and size of the jets of a valve. Value range: 0 ‐ 999 m³/h The program uses the flow rate to calculate the required duration or precipitation. NOTE: The flow must be identical or lower than the capacity (volume delivered) of the pump(s). The flow must be identical or lower than the flow of the hydraulic group or sector assigned to the valve. Here it will be defined if it is a „normal“ or a „bi‐direction“ decoder. A x represents a bi‐directional decoder. X = bi‐directional decoder Empty = „normal“ decoder This field is just valid if in the field „bi‐direct” a bi‐directional decoder was chosen. With this the pressure sensor can be activated or deactivated. X = pressure sensor connected Empty = no pressure sensor connected Print: ...
User Manual When data is updated By changing the valve data all simulated programs are deleted. The program stays on the PC. The program configurations must be removed from the VCU. All existing programs must be updated and retested. Finally all retested programs can be downloaded to the VCU. System Data Max. weather station stop time Should the irrigation be stopped by the weather station, the station will check within the time entered here, whether irrigation can be resumed. Unless the weather station restarts irrigation within the time entered, the program will end and will not start again automatically. Value range: 0 ‐ 999 min. Default: 60 min. Bed‐GK 1+2e Rev. 03.04.2019 Page 43 / 143 ...
User Manual Valve overlap / delay This field shows the valid overlap/delay values for Single Valve and Sectors programs. + indicates a delay between valve closing and valve opening. ‐ indicates an overlap between valve closing and valve opening Value range: ‐30 to + 30 seconds Default: 0 seconds Manual control program overlap Enter in this field the overlap/delay value for Manual programs. Value range: 0 ‐ 30 seconds. The values are incremented by 3 seconds. 7.6.1 Update time – pump control (program) This and the next input field is only required, when more than one pump is controlled by the pump‐ decoder. The pump manager, which is a part of this program, adapts the pump capacity to the water consumption of the irrigation system. The update time, which is entered in this field, determines the sequence, in which the pumps are started / stopped. The update time is valid for all irrigation programs without the Manual programs. Input range: 0 – 30 sec. (step of 3 sec.) Default: 0 sec. NOTE: If „0“ is entered, the optimal pump‐function is turned off, and all the installed pumps are running during the irrigation program. 7.6.2 Update time – pump control (Valve) The input in this field is valid for valves which are activated by: ...
User Manual 7.6.3 Minimum pump run time: (SPECIAL FUNCTION) The minimum pump run time will be entered in this field. This avoids a permanent start/stop (in short intervals) of the pumps. This function is just active if irrigation programs (automatic or manual start) are active. Input range: 15 – 60 sec. (only 3 sec. Steps allowed) Standard: 15 sec. 7.6.4 Interval time to calculate the flow: (SPECIAL FUNCTION) During an irrigation program the optimum pump sequence will be determined depending on the current calculated flow. Through this the influences of a variable flow will be reduced. It creates an optimal pump sequence, determined by the integrated average flow calculation. This represents the time how often in the irrigation cycle the average should be calculated, depending on the current flow of the valve. The 60 sec. flow of the valve is the decisive factor for an optimal pump sequence, depending of the average value in the last 60 sec. Standard: 0 sec. 7.6.5 Maximum retention time to open the valves (ONLY FOR BI‐DIR‐DECODER) This time represents how many seconds the system accepts the status „valve closed“ until an error message will be created, if a decoder will be activated. This function asked for the status of the flow sensor, if a decoder will be activated. 7.6.6 Maximum retention time to close the valves (ONLY FOR BI‐DIR‐DECODER) This time represents how many seconds the system accepts the status „valve closed“ until an error message will be created, if a decoder will be activated. ...
User Manual 7.6.7 Accepted number of error messages for solenoid short circuits (ONLY FOR BI‐DIR‐DECODER) Withe that parameters will be defined how many solenoid errors per decoder are accepted until the VCU stops. With the standard settings 3 the decoder have to report and to record 3 times a solenoid error, not till then the VCU has the status „ALARM“ Input range: 1 – 9 Standard: 3 VCU time / date You can download your computer time and date to the VCU. Click to save the data and exit the dialog box. 7.6.8 Possible Error Messages Code: 002‐% too low Code: 003‐% too high Code: 005‐% invalid input Code: 014‐ no connection to the VCU 7.6.9 The Pump manager In case that more than one pump has to be controlled by the pump decoder, the pump manager of the Greenkeeper is acting in that way, that the flow capacity of the activated pumps meets the required flow of the irrigation system as good as possible. 7.6.9.1 The Pump management of irrigation programs ...
User Manual External VCU interface Go to System setup – External VCU interface In this window you can configure external VCU interfaces. The following interfaces can be connected to the VCU. Closer (digital input 1) VCU terminal 11 + 12 These terminals are used for inputs from the weather station. Opener (digital input 2) VCU terminal 13 + 14 These terminals are used for inputs from the weather station. E.g. MiniClik Rain stop Relay 1 (output 1 VCU terminal 27 + 28) This output becomes energised when Pump 1 is running. The voltage on Terminals 27 + 28 is then 24 V AC. The maximum load may not exceed 0.5 A. Bed‐GK 1+2e Rev. 03.04.2019 Page 47 / 143 ...
Page 48
User Manual Relay 2 (output 2 VCU terminal 29 + 30) This output becomes energised when Pump 2 is running. The voltage on Terminals 29 + 30 is then 24 V AC. The maximum load may not exceed 0.5 A. V/I (analogue input VCU terminal 19 + 20) This input is used for a flow meter. Range: 0 ‐20 mA P/I (analogue input VCU terminal 21 + 22) This input is used for a pressure gauge. Range: 0 ‐ 20 mA Q/I (analogue input VCU terminal 23 + 24) This input is used for an anemometer. Range: 0 ‐ 20 mA Frequency 1 + 2 VCU terminal 15 + 16 / 17 + 18 These are two additional inputs designed as frequency inputs. The frequency applied should be higher than 5‐10 Hz. Value range: 0 ‐ 1000 Hz. Application Type a name for the external VCU interface. A max. of 8 characters is allowed. Scale Since the VCU only provides values in mA or Hz and we want the reported values to be expressed in appropriate measuring units, the values in mA or Hz must be scaled. This is made possible by using the Scale field. Bed‐GK 1+2e Rev. 03.04.2019 Page 48 / 143 ...
Page 49
User Manual Example 1: Connection of Pressure Sensor with Analogue Output A. Suggested pressure sensor Kobolt Typ 3373.078.092 0 ... 25bar 4 .. 20ma (Price: ca. .230.‐ €) B. Wiring schematic Hints and tips: After the connection of the pressure sensor, it will be best, to open the menu „VCU‐ Status“. In the column on the left side of the menu you will find the current values for the analogue inputs 1 to 4. When the sensor is connected according the above sketch, the measured current value is shown under “Analogue 2”. If there is no pressure applied to the pressure sensor, the correct reading is: 4ma If there is no reading, please check whether the polarity of the wiring is exchanged. Please check furthermore, whether a change of pressure will lead to a change of the readings. If yes, the sensor is wired in the right way. C. Readings The specified range of the pressure sensor is 0 – 25 bar and are linear covered by the current value of 4 – 20 ma. Bed‐GK 1+2e Rev. 03.04.2019 Page 49 / 143 ...
Page 50
User Manual D. Greenkeeper Hereby you can calculate the scale value, which has to be entered in the menu: „External VCU interface“ at S6. Scale: = 1,56 Hereby you can calculate the Offset, which has to be also entered to the menu: “ External VCU interface” at S6. Offset: 4ma x 1,56 = 6,24 The Offset value has to be subtracted from the total amount. Therefore it is necessary to put a (‐) sign in front of the figure Offset: ‐ 6,24 Now we have done all necessary inputs. Greenkeeper is currently measuring the actual pressure. These values are reported in the menu: “ actual irrigation report” and ”weather station” Example 2: Frequency input 1 (Anemometer) During one rotation an anemometer generates 4.4 pulses per second (4.4 Hz). One rotation corresponds to a wind speed of 1 m/s. The total measuring range is 0.5 ‐ 35 m/s Then: ...
Page 51
User Manual B. Wiring diagram: C. Measuring values: The rated measuring range of the flow meter, e.g. 2‐80 m³/h will be measured by linear measuring signal 0‐20 mA. This means: 1 mA = 4 m³/h. The correct function of the transducer can be checked by measuring the voltage across Pin 19 and 20 of the VCU. During maximum flow, in this example 80 m³/h, the voltage drops from 24 V to approx. 17 V. At the same time the voltage between earth and Pin 20 goes up by the same amount. D. Greenkeeper The value arrived at in C. above, in this example 4m ³ /h per mA, will be typed in the "Scale" entry field for S5 in the "External VCU interface" dialog box. Offset ‐999.9 to 999.9 This is a correction value affecting only the Scale factor for the analogue and frequency inputs. The correction value will be either deducted from or added to the Scale factor entered. The corrected scale factor is then used for the calculations. The following error messages can be encountered with: ...
User Manual Weather Station The weather station can stop (suspend) automatic irrigation program execution. This is done by using the values from System Setup – External VCU interface. By clicking in the box you can select here which interfaces Greenkeeper should take into consideration. A checked box indicates that Greenkeeper Win will consider this interface. To give Greenkeeper the threshold value for the interface to respond, type the required value in the Limit field. Should these values be exceeded irrigation will be stopped (suspended). As soon as the values get within the limit again irrigation will be resumed provided the following conditions are met: The actual weather station stop time is no longer than the max. weather station stop time specified in the General dialog box. Resuming the irrigation program will not lead to two programs overlapping. Note: T he weather station does not take into consideration manually open valves and manually started programs! Do not activate interfaces for sensors that have not been installed! Bed‐GK 1+2e Rev. 03.04.2019 Page 52 / 143 ...
Page 53
User Manual The limit range is calculated using the scale factor and the offset value in System configuration – General. Max. input value x Scale + Offset = Limit range The max. input value is: In analogue inputs: 20 mA In frequency inputs: 1000 Hz Example: Analogue connection 1 Scale factor = 5,0 Offset value = ‐1,0 Limit range = 20 x 5,0 + 1,0 = 101,0 The limit range is then 0,0 – 101,0 Example: Frequency connection 1 Scale factor = 0,6 Offset value = 1,0 Limit range = 1000 x 0,6 – 1,0 = 559,0 ...
User Manual 7.10 Port Settings In this dialog box you can set up communication via the serial port as well as enable/disable the Remote Control (Modem Control). There are two Remote Control options. VCU Remote 1. This function allows you to control a remote VCU from your computer. To facilitate the VCU and the PC must be connected with a modem. Remote Terminal Active 2. This function allows you to control the VCU from a mobile phone* or from another computer (Greenkeeper not required). If the telephone is off the hook, Modem Control is disabled. Bed‐GK 1+2e Rev. 03.04.2019 Page 55 / 143 ...
User Manual 7.10.1 VCU Port Settings Serial port: Select the serial port for connection with the VCU. COM ports that are not available appear grey. Setting options: COM 1 ‐ 6 Default: COM 1 When using the VCU Modem control you must select the COM port of the modem. Otherwise the modem will not dial! Change the VCU COM port accordingly. Baud rate: A baud is the unit of signalling rate ( 1 Bd=1 s) i.e. a measure of signal changes that take place in a transmission channel during one second. Default setting: 57600 baud 7.10.2 Remote Terminal Port Settings ...
User Manual Password timeout time: The log‐on password remains valid for the period of time entered. After the time expires the password must be re‐entered. Value range: 100 ‐ 3600 seconds Default: 1800 sec. Example: 1. The password was entered in Remote Control. 2. The connection was terminated. If the connection is not re‐established within the given period of time the password must be re‐entered. Exit the entry mode by clicking Ok. To save the updated data, press yes to confirm it. For details on incoming information please refer to the Remote Terminal Control chapter 14 in the User Manual. 7.10.4 Modem Commands ...
Page 58
User Manual En‐ Command Echo to Host With this command you can select whether your modem will return commands as echo or not. E0 = Echo off (Default) E1 = Echo on Vn‐ Word or Digit Response This command allows you to determine whether the response sent by the modem to the connected computer will be sent as digits or words. V0= Response as digits V1= Response as words (Default) Yn‐ Configuration Profile Selection This command determines which of the two stored configuration profiles will be loaded on modem power‐on. &Y0= Profile 0 will be loaded (Default) &Y1= Profile 1 will be loaded Qn‐ Enable/Disable Modem Responses Using this command you can disable the responses that the modem sends to the connected computer, either completely (Q1) or in the Answering Mode (Q2). Q0= Responses on (Default) Q1= ...
User Manual &W‐ Store Profile Settings Use this command to store the configuration profile in the modem. The default initialization string that allows Greenkeeper to answer incoming calls is the following: AT &F S0=1 E0 V1 Y0 Q0 &D3 &W This initialization string allows the modem to establish a connection to a remote VCU: AT &F S0=0 E0 V1 Y0 Q0 &D3 &W The only difference is in the S0= command! 7.11 Backup / Restore Data BACKUP YOUR DATA REGULARLY! This includes both system data, that is all system related data such as pump flow, valve names, irrigated area, etc. and program data, which is all settings, etc. To backup / restore data proceed as follows: In the System configuration menu click Backup/Restore Bed‐GK 1+2e Rev. 03.04.2019 Page 59 / 143 ...
Page 60
User Manual The Backup / restore dialog box will pop up. First of all select which type of data you want to backup. As a rule it may be system data and program data. Click Backup system data and Backup program data. The selected data is marked with a tick (). Select the backup drive where the data will be stored. As a rule the diskette drive in the computer case is marked [A:]. Bed‐GK 1+2e Rev. 03.04.2019 Page 60 / 143 ...
Page 61
User Manual Insert an empty and formatted 3,5“ floppy disk in drive A: or plug an USB‐stick into the PC. Click Start Backup. The backup program begins to back up the system and program data. After a successful backup you will receive the following information: Acknowledge the message by clicking OK. Your data has been stored on the data storage medium you have selected. Exit the Backup dialog box by clicking OK. To restore data on your computer click Restore system data and Restore program data. The options you have selected will be marked with a tick (). Select the drive with the data storage medium on which your data is stored. Insert the floppy or plug the USB‐stick into the PC. Bed‐GK 1+2e Rev. 03.04.2019 Page 61 / 143 ...
User Manual Now click Start Restore. The backup data will be copied back in the Greenkeeper directory. After the data has been successfully restored you will receive the following message: Acknowledge the message by clicking OK. Your data has been successfully restored. You can now exit the Backup/restore dialog box by clicking OK. 7.12 System Setup In this dialog box you can setup the following functions: 7.12.1 Font Select Actual font: The name of the current font is displayed here. Bed‐GK 1+2e Rev. 03.04.2019 Page 62 / 143 ...
User Manual Change font: Here you can change the current font. Default font: This button restores the current font to the default font settings. The default font is [Arial] Greenkeeper only supports changing the font itself. You cannot change the font size or colour. It is recommended to use the default font ‐ Arial! 7.12.2 Copying the graphic from the data medium on the hard disc: Open windows-explorer. Copy your graphic in folder Programm Files/ GreenkeeperWin/ bmp.
User Manual 7.12.3 Surveillance picture Change picture: You can change the graphic file here. The graphic files are used as the background picture in the Surveillance menu. The graphic depicts the irrigated area (a golf course, etc.). It must be stored in the bitmap format (*.bmp). After entering the password (Level 3) choose the menu item System configuration/System setup click „change picture“ Bed‐GK 1+2e Rev. 03.04.2019 Page 64 / 143 ...
Page 65
User Manual Once you click the Change picture button, the following window is displayed: You have the option of selecting up to 10 different graphic files (bitmap). Click in the empty NAME field. The Select picture dialog box with the graphic files will open. Select the bitmap file(s) from the C:\Programm Files\Greenkeeper Win\bmp\ directory. Bed‐GK 1+2e Rev. 03.04.2019 Page 65 / 143 ...
Page 66
User Manual The complete graphic can be divided in up to 10 files. It is required that the graphic files be stored in the above described directory on the hard disk. Finally click Open. The file name will be automatically inserted in the Name field. Type a description of the graphic. For example Green1‐6, etc. To delete a graphic file from the list click Clear. The file name and the description will be removed from the list. They remain to be stored on the hard disk. After all the files have been entered and a description added, click Ok. Confirm the Save data ? message By clicking OK Bed‐GK 1+2e Rev. 03.04.2019 Page 66 / 143 ...
User Manual 7.12.4 User Passwords Level 1: You can change the existing password for Level 1 and Level 2 here. Level 2: Changes can only be made if you are currently in Password level 3. Ok: Save the changes and exit. Bed‐GK 1+2e Rev. 03.04.2019 Page 67 / 143 ...
User Manual 8. Program Configuration In Greenkeeper Win you create various irrigation program configurations. These are then tested using an internal program test. During the test the Pump Flow Manager which is integrated in Greenkeeper uses the master data to calculate an optimum way of how the program will run. Finally the resulting data is, within a matter of seconds, downloaded to the VCU. Greenkeeper supports 3 different program types. Description of program types 1. Single valves All the valves, for which Precipitation Volume or Duration have been entered in the program, taking into consideration the pump data and the values for the valves entered, until the optimum pump capacities are achieved. The sequence of valve opening is determined by the program. It is, however, possible to change the sequence. 2. Sectors In this program all the valves within a pre‐defined sector open, taking into consideration the pump data. Only the optimum flow rate within a sector is calculated. The sequence of the sectors is determined by the program. However, in the sectors program it is possible to enter the sequence you require. 3. Manual programs This program is not supervised by the Flow Manager. You explicitly define which valves are to open in a particular step. You also determine which pump(s) will start. The program operates in steps. This means that one step is executed after the other. A maximum of 8 valves can be assigned to each step. All valves in a step open simultaneously. It is, however, possible to set a delay for the individual valves. See Chapter 7.6 (General) Please check the pump capacity. Incorrect data may cause pump overloading. Bed‐GK 1+2e ...
User Manual Single Valves In this type of program all the defined single valves open, taking into consideration the maximum pump capacity, in the sequence of decoder numbers or in an ascending order should the sequence be explicitly entered. The Flow Manager provides for the optimum pump loading. Select the Single valves option by clicking it with the left mouse button. To create a new program, click the New program button. 8.1.1 Creating a New Program Type the new program name in the field. Give your new program a unique name. The maximum length is 8 alphanumeric characters. Confirm the entry by left‐clicking the OK button. Bed‐GK 1+2e Rev. 03.04.2019 Page 69 / 143 ...
Page 70
User Manual A program name is always unique. Each program, regardless of whether it is a Sectors or a Manual program, must be given a unique name. Should the program name already exist you will receive the following error message: Code: 008 ‐ xxx already exists Please type a name which has not been used. After you have entered a unique name for the new program the following window opens: Your program name is displayed her Position: For information only, sequence numbers, defined in the Valve data dialog box. Valve name: For information only, valve name Sequence: Defining the sequence Values: 0 ‐ max. number of valves For the default value (0) the Flow Manager calculates the sequence automatically. You can change the sequence by entering, in an ascending order, the numbers from 1 to nn (nn being the number of installed valves). The valve with the lowest number, from 1, will open first. You must enter the sequence for all valves. Either all valves 0 or 1 ‐ nn. Bed‐GK 1+2e ...
Page 71
User Manual Density: Type the required precipitation. 0 ‐ 999 mm The required precipitation in mm is entered here. Based on your entry and taking into consideration the master data, the Flow Manager calculates the necessary open time as well as the water consumption in m³/h and inserts the values automatically in their respective fields. Time: Enter the required valve open time. 0 ‐ 479 minutes The duration entered is used to automatically calculate precipitation. Consumption: For information only, the calculated water consumption (m³/h) Print: Print the program data Common precipitation: Copy the same precipitation value to multiple valves. In the Enter valve search text field, type the initial characters of a valve name. If you want the same precipitation for all G01‐1, G01‐2, etc. valves, type G01, click in the empty Enter common density ...
User Manual All valves, whose name begins with G01, will have the same precipitation value. During installation, select the valve names so that the first letter designates the area that will be irrigated. G01‐1 Green 1 Sprinkler 1 G01‐2 Green 1 Sprinkler 2 etc. 8.1.2 Program Test The program test feature is a tool for checking program configurations. Click Program test. A program configuration that you created will be checked and made ready for a download to the VCU. Without going through the test a program cannot be downloaded to the VCU and therefore cannot be used. You can see in the window the detailed timing of the program operations as calculated by the Flow Manager. This is how the program will be executed by the VCU. By clicking the Print button you can print the program data to have an overview of the program operation. To end the Program test click OK. You will return to the Single Valves window. Bed‐GK 1+2e Rev. 03.04.2019 Page 72 / 143 ...
User Manual Now click the Ok button to save the program on the hard disk. To make the program executable you must download it to the VCU. Refer to Chapter 9 ‐ Downloading Sectors For this program type it is necessary that you pre‐define the sectors. Go to Program configuration / Sector configuration where you can define the sectors. Click Sector configuration. Bed‐GK 1+2e Rev. 03.04.2019 Page 73 / 143 ...
User Manual Give each sector a unique name and assign the valves to the sectors. A valve can only be assigned to one sector. Confirm the entry by clicking Ok. 8.2.1 Creating a Sectors Program Go to Program configuration / Water programming / Sectors where you can configure a sectors program. Click Sectors. Bed‐GK 1+2e Rev. 03.04.2019 Page 74 / 143 ...
Page 75
User Manual Type a unique program name. Finally click Ok. The Sector name field shows your pre‐defined sector. You can now enter the required precipitation in the Density field. The Flow Manager will automatically calculate the valve open time. The water consumption of the whole sector is displayed in the Consumption field. The Flow Manager takes into consideration one sector only. After the first sector has finished, the next sector starts. You can enter the sequence in which the sectors will run. Print: Printing program data Program test: Program test to check the program configuration. The program configuration you created will be tested and made ready for a download to the VCU. Without going through the test run the program cannot be downloaded to the VCU and executed. Bed‐GK 1+2e Rev. 03.04.2019 Page 75 / 143 ...
User Manual 8.2.2 Common Precipitation: Here you can assign the same precipitation to multiple sectors. For example, if you enter G in the Enter valve search text field all sectors that start with G will be assigned the same precipitation. Click Ok to exit the dialog box. Ok: Save the program and exit You must run the Program test. Otherwise the program cannot be downloaded to the VCU and executed. Bed‐GK 1+2e Rev. 03.04.2019 Page 76 / 143 ...
User Manual Manual Programs This program type allows you to specify how the program will run. This means, you define which valves open at what time and for how long. Normally this data is determined by the Flow Manager. If you want to avoid using the Flow Manager you can do this by creating a manual program. Programming procedure: Select pump(s) Select and assign valves to program steps Specify duration of each step Run program test Exit programming window Download the program to the VCU Start the program using Change Active Program Important: If you do not select any pumps, only valves will open. The system will not send you a warning message! Please check the pump capacity! Do not open more valves than the pump capacity permits! Greenkeeper does not monitor the flow! Bed‐GK 1+2e Rev. 03.04.2019 Page 77 / 143 ...
Page 78
User Manual Select the pump(s) here. From the list box select the valve. You can assign up to 8 different valves to one step. An error message will be returned if you attempt to assign a valve twice within one step. You can define a maximum of 100 steps, each with 8 valves. Select the duration of a step from the Step time list box. The step time options are incremented by 5 minutes. The pump efficiency is displayed here. Make sure the pumps are used effectively. Incorrect data can lead to pump damage. There are always 8 steps displayed in the Manual program window. Scroll this bar to display the next 8 steps (place the mouse pointer over the bar, hold down the left mouse button and pull the bar downwards). Now click Program test to check the program. Acknowledge the Program test completed message by clicking OK. Exit programming by clicking OK. The program will be saved on your hard disk. You must now download the program to the VCU and enter it in Change Active Programs or start it manually. Refer to Chapter 9. Bed‐GK 1+2e Rev. 03.04.2019 Page 78 / 143 ...
Page 79
User Manual Manual programs operation is governed by the following rules: If no delay has been entered in System configuration / General, the steps will start one after the other. Once the first step finishes (or the first valve within the step closes) the first valve of the next step starts. Should a delay have been defined in System configuration / General, the valves within a step will start in intervals equal to the delay entered. Once the first valve within a step closes, the first valve within the next step opens. When the second valve within a step closes, the second valve within the next step opens, etc. This means that, between the individual steps, the valves overlap. However, this is only possible if a value (max. 30 seconds) has been entered in System configuration / General / Manual Control Program Overlap. (See Chapter 7.6) Bed‐GK 1+2e Rev. 03.04.2019 Page 79 / 143 ...
Page 80
User Manual Example: Pos. Status Valve Time m³/h ‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐ 1 On G1 12.08 21,0 2 On G2 12.08 42,0 3 On G3 12.09 63,0 4 Off G1 ...
User Manual 9. Downloading Programs Before program configurations can be used they must be downloaded to the VCU. Click Downloading: And then Download/delete program The following window will open: The following window will open: The window is divided into two areas. The left‐hand side area shows the currently available and tested programs stored on your hard disk. An arrow sign (>) in the Position column indicates that the program has already been downloaded to the VCU. The right‐hand side area shows the programs that are currently available on the VCU. In the example above, only the Test program is stored on the VCU. Click a program name in the left‐hand side area. The box with the name will now be bordered with a light grey line. Press the right mouse button. The Download program box will pop up to the right from underneath the mouse pointer. Click the box. The program will be downloaded within a matter of seconds to the VCU. During downloading you will receive the following message: Bed‐GK 1+2e Rev. 03.04.2019 Page 81 / 143 ...
Page 82
User Manual After a successful download the program will also be displayed on the right‐hand side and the position number will be marked with an arrow. Click Ok. The program is now available in the VCU and ready for activation. Both versions of the program must be identical. A change in the program is followed by an error message: Should this happen delete the program in the VCU and download the updated version. Versions must be identical!! Bed‐GK 1+2e Rev. 03.04.2019 Page 82 / 143 ...
User Manual Removing Programs from the VCU To remove a program from the VCU clicks the program name in the right‐hand side area. The box with the name will now be bordered with a light grey line. Press the right mouse button. The Delete program box will pop up to the right from underneath the mouse pointer. Click the box. The program will be removed from the VCU. However, it remains stored on your hard disk. Once a program has been removed from the VCU it cannot be invoked from Change Active Programs. But as the program remains stored on the hard disk it can be, at any time, downloaded to the VCU again. Before you update or delete any program always end all control programs in Change Active Programs. A maximum of 20 programs can be stored in the VCU. These include a maximum of 12 single valves / sectors programs and a maximum of 8 manual programs. Should the limits be exceeded the limits you will receive the following error messages: Code:042‐Max number of manual programs in VCU exceeded Code:043‐Max number of programs in VCU exceeded Bed‐GK 1+2e Rev. 03.04.2019 Page 83 / 143 ...
User Manual 10. Change Active Programs Change Active Programs serves as an independent control function. Here you specify which program on which day, in which week and at which time will automatically start. You can either start the programs immediately by manual start or automatically at a predefined time. An automatic program execution can be programmed up to two weeks in advance. After the second week has passed Change Active Programs automatically begins with the first week. Each day within the two week period can hold up to seven programs, each with a maximum of 3 start times. Also you can globally change, with a mouse click, Precipitation or Duration for each program separately. Irrigation status shows the current status of the VCU. The following status information is displayed: Active: A program is currently running. (Do not make any changes when in the active status) Stopped: A control program has been stopped. However, the program continues to run internally. Waiting: Change Active Programs has been activated through Start irrigation. The VCU is waiting for the Start time entered. Inactive: Neither automatic nor manual program has been started. The VCU cannot start a ...
Page 85
User Manual Irrigation status is displayed in the top left corner. VCU time is shown here. The current day and week are always marked with an asterisk and capitalized. If you want to select another day, click on the day of your choice. The programming is valid for the selected day only. Should the program run every day it must be entered (along with the start times) for each day in Change Active Programs. The same procedure applies to the first and second week. Single: If you want a program to be removed from Change Active Programs after it has been invoked for the first time, click the Single field to check it. After the first start, the marked program will be removed from the irrigation schedule (Change Active Programs) for the particular day and week. However, it remains stored on the VCU and can be reactivated at any time. Progr. name: Select a program in the Program name field. Only programs downloaded to the VCU are available for selection. If a program you created is not listed it has not been downloaded to the VCU. Refer to Chapter 9. Bed‐GK 1+2e Rev. 03.04.2019 Page 85 / 143 ...
Page 86
User Manual Start times: You have the option of selecting three start times. Click the first start time selection field, from left to right. Select a start time. The times are incremented by 5 min. End: Shows the time when the irrigation program will be finished. NOTE: Regardless of the program type a delay of at least 10 minutes must be maintained between the Stop time of one program and the Start time of another. Otherwise you will receive the following error message: Code: 048‐"xxx" Overlap time Example: Start time 19:00 Duration: 2 hrs. = Stop time 21:00 The second Start time or the first Start time of the next program may start no sooner than 21:10. Correction: Here you have the option of increasing or reducing the percentage of Duration or Precipitation. Default: 100 % min. 10% max. 300 %. Duration: This column lists for each program Duration per start time. ...
User Manual NOTE: Make changes in Change Active Programs only when the VCU is in the inactive status. To invoke the inactive status click Reset irrigation. 10.1 Manual program start Each program that you created can be started independently of the actual time. By clicking Reset irrigation end all programs that started automatically. Then click Manual irrigation. The following dialog box will be brought up. Select your program and confirm your choice by clicking Ok. The selected program will start immediately. The following box will appear in the top section of the screen: Your program name Stop time: Click here to check the Repeat program option to automatically repeat the program after it has been executed. It will be rerun until you click Reset irrigation or remove the check by clicking again the Repeat program field. Do not exit Change Active Programs once you have selected Repeat program. The process can only be controlled in this menu. Bed‐GK 1+2e Rev. 03.04.2019 ...
User Manual 10.2 Irrigation Supervision At home 07051162 10.2.1 Maximum number of faulty opened valves permitted If the number of the alarms e.g. “valve open fault” exceeded the entered limit the entire irrigation will be stopped. (Every active program will be stopped; all manual opened valves will be closed). The correspondending alarms are display on the right below side of the screen/monitor. Input range: 0 ‐ 9 Standard adjustment: 0 (not activated) Bed‐GK 1+2e Rev. 03.04.2019 Page 88 / 143 ...
User Manual 10.2.2 Monitoring of pump alarm active This wills activate the pump control. Decoder no. 245 has to be connected with the pump‐status‐relays. Status: Relays open: no error Relays closed: error Continuation The decoder solenoid cables have to be connected with the pump‐status‐relays. 2 different statuses will be reported from the decoder to the VCU. No error in the pump system In this case the pump‐status‐relays are open and the decoder reports following status: „Coil shortcut >xx Ohm“. This means the pump system is Ok. Error in the pump system In this case the pump‐status‐relays is closed and the decoder reports following status „Coil shortcut<xx Ohm“. This means the pump system has an error. If decoder 245 reports an error the entire irrigation stops (each active program stops, all manual opened valves will be closed.) The corresponding alarms are displayed on the right below side of the screen/monitor. And, if active, the alarm will be sent additionally by telephone. Standard adjustment: no activated 10.2.3 Emergency call in case of too much faulty opened valves ...
User Manual 10.2.5 Name Just for information about the phone number Standard adjustment: empty 10.2.6 Phone number Phone number, which should be called from Greenkeeper Win in the case of alarm. Check the phone number! Greenkeeper Win will not check any phone number! If you call from an extension line it’s necessary to add a 0 in front of the phone number. Ask your telephone administrator. 10.2.7 Puls dial Here the dialling method will be determined. Deactivated: tone dialling (standard) Activated: puls dialling Here the input is just possible if the field “phone number” is filled. IMPORTATNT: To use the alarm messages by telephone, the „dialled terminal“ in the menu ...
User Manual 11. Surveillance 11.1 Open graphic Greenkeeper is the only program on the market offering a realistic graphic representation of the areas irrigated. In the graphic you can place valve symbols in the actual locations where the solenoids are situated. By clicking the symbol you can open and close the valve. In the menu bar click Surveillance – Surveillance picture. The graphic will load automatically. The top bar of the screen displays the following information: Irrigation status Running program Calculated pump flow The calculated pump flow in shown in this field. If the calculated pump flow exceeds the pump capacity, the fields is blinking in red colours. Actual pump flow (a flow meter is required for this) VCU time Active Pumps In the left down corner of the screen the status of the pumps is shown. Red: Pump stopped Green: Pump is running The indicated pump flow is based on the running pumps. Bed‐GK 1+2e Rev. 03.04.2019 Page 91 / 143 ...
User Manual In the Edit mode you can place valve symbols in their actual locations in the graphic. This is only possible in Password level 3! Close all manual valves will close all valves that have been opened manually. Exit the graphic by clicking Ok. 11.2 Edit Mode The Edit mode is used for placing valve symbols. Click the Edit mode button. The Select valves window will pop up. The window lists all valves that have not been placed. To place a valve, position the mouse pointer over the valve name. Hold down the left mouse button. Now drag slowly the valve name out of the window into the graphic. Release the mouse button. The valve symbol is now in the graphic. The valve name has disappeared from the list. After all valve symbols have been placed, close the window by clicking the Close button. You will exit the Edit mode. Bed‐GK 1+2e Rev. 03.04.2019 Page 92 / 143 ...
User Manual 11.3 Graphic map selection You have the option to select from as many as 10 different Graphics, or 10 different areas. To do this, right‐click in the graphic. The selection window will open. Now select the graphic or area that you want. Should the graphic be larger than the screen you can move the graphic up and down or sideways using the scroll bars on the right and at the bottom edge of the screen. You can now open a valve by clicking the valve symbol. Enter the valve open time from 1 ‐ 99 minutes. The default value is 15 minutes. Click OK to open the valve selected. 11.4 Pump management The system will then start a pump (pumps) with the required capacity. Example: 2 pumps are installed Pump 1: 20 m³/h Pump 2: 10 m³/h 3 Valves are opened Valve 1: ...
Page 94
User Manual NOTE: The system only starts pumps when no other programs are currently running. Should another program be in operation only the valves will open. After the system opens the first valve the following dialog box is displayed. All manually open valves are displayed in the list. To close a valve again, click the valve symbol. The valve will close and it will be removed from the list. The Close all manual valves button can be used to close all manually open valves in one go. Click OK to exit the graphic. WARNING: Manually open valves which have been opened using the graphic will not close automatically after exiting the graphic! Bed‐GK 1+2e Rev. 03.04.2019 Page 94 / 143 ...
User Manual 12. Reports Greenkeeper stores all irrigation processes in the VCU. These can be then summarised and presented in the form of reports. Two different reports are available: 1. Irrigation report This report shows the total precipitation and water consumption for each valve for the current and previous year. 2. Actual watering report This report shows all valve activities from the recent irrigation programs. 12.1 Irrigation Report To view the Irrigation report click: Reports / Irrigation report This report lists the total precipitation, active time, and water consumption per year for each valve. Bed‐GK 1+2e Rev. 03.04.2019 Page 95 / 143 ...
Page 96
User Manual Click Print to print a hard copy of the list on your printer. Click Toggle Year to change between the previous / current year. To exit the report click Ok. In the head line the accumulated values for the corresponding year are shown. 12.2 Actual Watering Report To view the Actual watering report click: Reports / Actual watering report This report shows valve activation data from the last 15 irrigation programs. As only a total of 15 reports can be stored the oldest report (with the highest Report No.) is always deleted. The remaining reports then move down one number and the latest report becomes Report No. 1. Report name: Name of the irrigation program. Start time: Start time of the irrigation program. Report number: Sequential number of the report 1 ‐15 (the latest report is always No. 1). S 9: Name and value of Frequency input 1. S 10: ...
Page 97
User Manual Stop time: Stop time (program stopped by the weather station or manually). Position: Sequential number 1 ‐ 1600 (480 for Single valves / Sectors program). State: Valve state. 2 states per valve. ON / OFF. Time: Start time of the irrigation program. Status valve: Status message from the decoder (ONLY FOR BI‐DIR‐DECODER) OK (green) no error Error (red) Error (see status report) ...
User Manual 12.3 System Error Status (ONLY FOR BI‐DIR‐DECODER) To see the status of the decoder feedbacks please click: Reporting / System error status Following status can be displayed: OK (green) no error FEHLER (red) error NA (grey) no FB‐ decoder installed If there is an error in the irrigation system, it will be documented and displayed. Important: Eliminate primary always the reason for the alarm message, otherwise ...
Page 99
User Manual To delete a single error click with the left mouse button on the red marked error message. Afterwards click in the new window on the RESET button. If you want to delete several error messages in one step click with the left mouse button at RESET DECODER LOG and confirm this afterwards in the new window with OK. To delete the VCU Error click with the left mouse button on RESET VCU ERROR. If all errors are resolved the status must be: 100‐OK! Bed‐GK 1+2e Rev. 03.04.2019 Page 99 / 143 ...
User Manual 13. Service Menu The menu is only accessible in Password level 3 ! VCU status Actual VCU input and output values Actual decoder status Functions to open and close all decoders by a mouse click Decoder programming functions VCU version information The current VCU software version is displayed here VCU version update For downloading a new software version to the VCU Reset VCU error To send commands to the VCU. After an error message the VCU error must be reset in this menu option. Active decoder and valve check You can check the functioning of all valves and decoders here. Transmitter download To download all valve names with their respective decoder numbers to the transmitter. Bed‐GK 1+2e Rev. 03.04.2019 Page 100 / 143 ...
Page 101
User Manual 13.1 VCU Status Status: Shows the current VCU status 100‐No error No error, the desired VCU condition 101‐Line init: VCU is establishing a connection to decoders 102‐Sync error: VCU 50 Hz power supply is not synchronised. 103‐Ground error: Leakage current limit value exceeded The leakage current may not exceed the following values. More than 0.7 A for 8 seconds ...
Page 102
User Manual 105‐Volt error: Voltage limit value exceeded. Less than 20.0 V for 32 seconds Analogue 1‐4: Value in mA of analogue inputs 1 ‐ 4 Dig‐in 1‐4: Status of digital inputs 1 ‐ 4 Freq 1‐2: Frequency in Hz Grnd curr: Leakage current of decoder line Out A: Output voltage (V) of decoder line A Out B: ...
Page 103
User Manual The square boxes to the left of each decoder number show the current status of the decoder. The status is indicated by different colours. The square boxes to the left of each decoder number show the current status of the decoder. The status is indicated by different colours. Green: Decoder is closed Yellow: For decoders up to No. 240: just received an open command from VCU For decoders from No. 241 upwards: decoder open Red: Decoder activated manually Blue: Decoder activated by irrigation program White: ...
Page 104
User Manual 13.2 VCU Version Update This menu option is used for downloading new control software to the VCU. When the new software is downloaded all programs and reports in the VCU will be deleted. The function is to be executed only when a new version of the software is available. The VCU contains special software stored in Flash PROM memory. It can happen that, for example when you are updating the program, you will also need to update the software. After the chipset update the yellow LED of the VCU may not be flashing. In this case you must download the VCU software to the VCU. The software is included as a program file on the installation CD. Go to Password Level 3. Click Service –download new VCU program. Single click on [Select Program]. Look for [Programm Files / Greenkeeper Win / VCUPRG] or insert the CD (D: oder E:) GREENKEEPER WIN in drive D: / E: And click on [Select Program]. Bed‐GK 1+2e Rev. 03.04.2019 Page 104 / 143 ...
Page 105
User Manual Click the Pe_main.hex file. The file name will automatically appear in the File name field. Click Open. Here you can watch the download status. To download the VCU program click [Start Programming] Bed‐GK 1+2e Rev. 03.04.2019 Page 105 / 143 ...
Page 106
User Manual First the software that may still be stored in the VCU is deleted. All VCU information, e.g. the Irrigation Programs and Report Schedule, is lost. As a rule, it takes about 25 seconds to delete the information. Should the deleting process last an extremely long time (approx. 50 s), the computer has been disconnected from the VCU. Click Cancel to abort the downloading. Refer to troubleshooting! Should this not be possible with the Cancel button you can end the complete Greenkeeper program in the Task Manager. To start the Task Manager hold down the [Ctrl] / [Alt] key combination and then press [Del]. Select the Greenkeeper program and click [End Task]. DO NOT CLICK THE SHUT DOWN BUTTON ! Bed‐GK 1+2e Rev. 03.04.2019 Page 106 / 143 ...
Page 107
User Manual After the deleting has finished Greenkeeper begins to download the new VCU program. In the top line you can follow the overall progress. One after the other, Layers 1 – 7 and then the Base Layer will be transferred. After the Base Layer has been transferred the complete VCU program is stored in the VCU. The Status has now changed to Project Transfer Ok. Click Ok to close the window. The "Program configuration" LED should then flash. Bed‐GK 1+2e Rev. 03.04.2019 Page 107 / 143 ...
Page 108
User Manual 13.3 VCU Commands You can use this menu option to send commands to the VCU. VCU commands: Reset VCU error: You must use this button to reset the VCU after an error has occurred (red LED is on). All programs remain to be stored in the VCU. All reports remain to be stored in the VCU. The decoder line will be initialised. Should the error reappear, check the decoder and ...
Page 109
User Manual 13.4 Active Decoder and Valve Check This menu option allows you to check the function of decoders and valves. As the test gives you only a quantitative overview of the function of the decoders and valves it is necessary to check their perfect function on the spot. WARNING: The test starts the pumps and opens the valves. The sprinklers are in operation! Before you can carry out a decoder or decoder/valve test you must first select the decoders/valves in the Selected valves box. Position the mouse pointer over the valve name and click it with the left mouse button. A tick () will appear in front of the valve name indicating that the valve has been selected for the test. Proceed in the same way to select multiple valves. If you want to check all the valves click in the box with the right mouse button. An option/selection box will pop up with two options. Select all valves: To mark all the valves for the test. Deselect all valves: To remove all marks. No valve is selected for the test. Bed‐GK 1+2e Rev. 03.04.2019 Page 109 / 143 ...
Page 110
User Manual Start decoder check: This test checks the function of the decoder. First the decoder line is initialised. Then the pump decoder is started. 30 seconds after the pump decoder has been activated the current consumption of the decoder line is measured. This value is then used as a reference value and is recorded in the decoder current (A) field. Now the decoders marked for the test will be activated one after the other. 30 seconds after a decoder has been activated the current consumption of the decoder line is measured and compared with the reference value. The difference is recorded in the decoder current (A) field. Should the value displayed be equal to 0,000 the decoder must be checked on the spot. Start decoder/valve check: Same as the decoder check but including an additional flow paddle (S3) check. Print test result: After the test has finished you can print out all test results. ...
Page 111
User Manual Click the Start Downloading button. The data will be downloaded to the transmitter. After a successful download click OK. The data remains stored in the Transmitter even when it is disconnected from the decoder control system. On energising a valve through the transmitter only Pump 1 (Decoder No. 246) is started automatically. The remaining pumps must be activated manually through a separate decoder no. LCD‐Display Valve number Valve name Open time remaining ...
User Manual 13.6 Transmitter Status 13.6.1 Download Status Clearing terminal The valve names in the transmitter are deleted XX ‐ Downloading ‐ YY XX indicates the current position. YY represents a valve name. Downloading completed All data has been successfully downloaded to the transmitter. 13.6.2 Transmitter Status Transmitter‐Ready The transmitter is properly connected and is ready to download data. Transmitter‐Busy The transmitter is receiving data or data is being deleted. Transmitter‐Timeout This message is displayed when connecting to the transmitter for the first time. The last command has not been completely executed. Transmitter‐No connection The transmitter has not been connected with the decoder line. Bed‐GK 1+2e Rev. 03.04.2019 Page 112 / 143 ...
User Manual 14. Remote Control 14.1 Kinds of remote control The VCU can be controlled using different control modes. Remote control via a Transmitter TM1 Remote control via a Wireless Transmitter Remote control via a Mobile Phone (Nokia Communicator) Your PC must be connected to a modem. 14.2 Remote control via the transmitter TM1 The hand terminal consists of a 2 x 16‐stelligen digital display and 7 function keys. The communication as well the power supply occurs by the 2‐wire decoder cable. The plug has to be connected with the field connector. The transmitter provides following functions: Valve open Valve immediately clos All valves immediately close The transmitter will be connected with the 2‐wire cable system via the field connector. After the transfer of the station names the Transmitter can be used at all field connectors. Clear identification of the valve names by text indicator ...
User Manual 14.3 Remote control via Wireless Transmitter The WT allows the communication with the control system about an autarkic radio network. The radio network will be installed at site (see picture – scheme drawing). With a free view to the antenna a coverage up to 2km is possible. If there is any obstacle due to the area, buildings or trees you can expand to the requested coverage with the installation of additional repeater stations. The WT can be used in all European countries without radio license. Antenna VCU for Greenkeeper control system Antenna cable PC with Perrot Satellite control system WBU base Wireless unit transmitter Power supply unit Cable interface Application The WT is very robust and easy to use with just 5 buttons. Ideal for manual watering and for function tests of the system. Functions Open and close the valves with adjustable time standards. Start and stop the irrigation programs. Easy valve searching by choosing different criteria. Automatic synchronisation of the valve‐ and ...
User Manual 14.4 Remote via Mobile Phone The Remote terminal active function in "Communication setup" dialog box must be checked! You can control a variety of functions of the Greenkeeper system via a mobile phone. 14.4.1 Communicator Specification The Mobile Phone must support VT 100/ANSI Emulation. Currently, only Nokia Communicator complies with this requirement. For operating Nokia Communicator please refer to the product‘s instruction manual. There must be installed a licensed „newDIALin“ software in the Nokia Communicator. Therefore you can send the device to Regnerbau Calw GmbH Configuring Greenkeeper Win for Remote Control Click System configuration / Communication setup: Click in the Remote terminal active box to enable remote control Make sure that the VCU Remote option is disabled!! The option will be checked (). Finally click OK. Confirm the Save data? Message by clicking OK. Bed‐GK 1+2e Rev. 03.04.2019 Page 115 / 143 ...
Page 116
User Manual !!!! Do not exit the program!!! !!!! Switch the monitor off !!!! The computer is now in the Waiting mode. When an incoming call is detected the modem picks up the call and establishes a connection. Make sure that this telephone line is not used for normal voice telephone calls. Take your Nokia Communicator and dial the number of the telephone line on which the computer with Greenkeeper has been installed. If the connection is to be made from a remote computer you must start a terminal program on the computer first. For configuration details please refer to Chapter 4. The menus and commands are identical with the Communicator environment. Bed‐GK 1+2e Rev. 03.04.2019 Page 116 / 143 ...
User Manual 14.4.2 Initiation of Communicator Before initial operation you must assure that the “newDIALin” Software is installed. Press control key Extras (topside right) after open the Communicator. Move cursor with help of the arrow key to the right to the menu “newDIALin” Open menu „newDIALin“ with function keys Bed‐GK 1+2e Rev. 03.04.2019 Page 117 / 143 ...
Page 118
User Manual Choose with the same key “connection” In the file/line telephone you can now put in the connecting number, with that number the modem will be connected, for example to 07051‐162100 Note: There is the possibility to reset wrong input with help of the key backspace You only have to input the connecting number once. The connection will be activated through pressing OK Bed‐GK 1+2e Rev. 03.04.2019 Page 118 / 143 ...
Page 119
User Manual Once Greenkeeper acknowledges the connection, type your password. PERROT REGNERBAU REMOTE TERMINAL‐PASSWORD MENU 1 6.01.12 12:22:15 Enter new password: ______________________ After you have typed the password press the [ENTER] key. You will be now in the Password menu. PERROT REGNERBAU REMOTE TERMINAL‐PASSWORD MENU 16.01.12 12:22:17 Remote password level: Password Level 3 Change remote password level by pressing [Enter] Using the key select the Main menu. PERROT REGNERBAU REMOTE TERMINAL‐MAIN MENU 16.01.12 12:22:48 1 Password 2 Manual open valves 3 Download 4 Change Active Programs ...
User Manual 14.4.3 Password Menu 01 Enter the password in this menu according to access type. PERROT REGNERBAU REMOTE TERMINAL‐PASSWORD MENU 16.01.12 12:22:17 Remote password level: Password Level 3 Change password level by pressing [Enter] The display shows the current password level. Press [Enter] to enter a new password. PERROT REGNERBAU REMOTE TERMINAL‐PASSWORD MENU 1 6.01.12 12:22:15 Enter new password: ______________________ Type the password and press the [ENTER] key. Password level 0 allows you to access the Password menu only. Password level 1 allows you to access Menus 1 – 4. Password level 2 or higher allows you to access all menus. ...
User Manual 14.4.5 Download Menu 03 In this menu you can download programs from the PC to the VCU and remove programs from the VCU. PERROT REGNERBAU REMOTE TERMINAL‐ DOWNLOAD 16.01.12 13:06:02 Program in Pc Program in VCU 1‐TEST1 4‐AGRIC 1‐TEST1 2‐FLIK 2‐FLIK 3‐SECTEST [1]‐Download program to VCU [2]‐Next PC programs [3]‐Prev. PC programs [4]‐Delete program on VCU [5]‐Next VCU programs [6]‐Prev. VCU programs On invoking the menu a program version check is performed. The following error messages can result: Code:041 – VCU program "xxx" do not exist on PC The "xxx" program is no longer available on the PC. In this case please delete the program on the VCU. Code:040 ‐ Version conflict of VCU program "xxx" After downloading to the VCU, the "xxxxx" program has been updated. Delete the "xxxxx" program ...
Page 124
User Manual Delete program Press the [4] key. The system prompts you: Select a program to delete: __ Type the program number and press [ENTER]. The program will be, within a matter of seconds, removed from the VCU. However, as the program remains to be stored on the hard disk it can be, at any time, downloaded to the VCU again. Programs on disk Here you can see all the currently available and tested programs stored on your hard disk. A ] maximum of 6 programs are displayed at a time. To view the next 6 programs press the [2 key. For the 6 previous programs press [3]. You can store as many as 99 programs on your hard disk. Programs on VCU Here you can view all the programs that are currently available on the VCU. You can delete only programs that are listed here. A maximum of 6 programs are displayed at a time. To view the next 6 ] programs press the [5 key. For the 6 previous programs press [6]. You can store a maximum of 8 manual programs and 12 single valves and sectors programs on the VCU. Important: Never use the Remote control and PC functions simultaneously. This could lead to unforeseeable faults. When using Remote control the "Terminal active" message will show at the bottom left of the screen. Bed‐GK 1+2e Rev. 03.04.2019 Page 124 / 143 ...
User Manual 14.4.6 Change Active Programs ‐ Menu 04 In this menu you can change the program schedule for a selected day. PERROT REGNERBAU REMOTE TERMINAL‐CHANGE ACTIVE PROGRAMS 16.01.12 16:31:19 Program Start time Corr. Dur. Consump. VCU Programs 1: 1‐FLIK 2: 3: 4: Irrig. St.‐Inactive VCU time ‐16:29 [1]‐Start [2]‐Stop [3]‐Reset [7]‐Next VCU Prg [9]‐ Prev. VCU Prg Single: Select here, whether the program should be removed from Change Active Programs after it has been invoked for the first time. Enter [0] if: The program is not to be removed. Enter [1] if: The program is to be removed after it has been invoked for the first time ! Progr. Name: Type the program name for your program. For a selected day you can enter a maximum of 4 different programs with 3 start times each. On entering a program ...
Page 126
User Manual The following error messages can be displayed: Code:049 ‐ xxx Overlap correction Your entry causes program overlapping. Select another value. Code:037 – Max program water consumption Your entry causes excessively high Water consumption. Select a lower value. Code:036 – Max program duration Your entry causes excessively long Duration. Select another value. Max. Duration = 23 hrs. and 55 min. Duration: The duration of the complete program in hours and minutes. After modifying the value through Correction it will be recalculated. W. consumption: Water consumption in m³/h After modifying the value through Correction the water consumption will be recalculated. Status: Irrigation status shows the current status of the VCU. The following status information is displayed: Active: A program is currently running. ...
Page 127
User Manual Manual: A program has been started manually. Fault: A fault has occurred in the VCU. Identify the fault cause in the Service menu. No irrigation can be performed when in this status. Programs on VCU This shows you all the programs stored in the VCU. The VCU can only execute programs that are displayed here. You can store a maximum of 8 manual programs and 12 single valves and sectors programs in the VCU. Functions: (not available in the Edit mode) [1] Start This will bring the VCU to the ready state. The VCU is waiting for the first start time entered in Change Active Programs to arrive so that the program can be started provided the weather station does not inhibit irrigation. [2] Stop This will stop (suspend) the program. However, the program and the duration continue to run internally. After the program has been restarted it resumes exactly from the point that has been calculated provided it will not lead to overlapping with the program that is scheduled next. [3] Reset This function completely cancels the execution of a program. The VCU will immediately attain Inactive status. No programs will be started automatically. ...
User Manual 14.4.7 Service Menu 05 Two different service functions are available in this menu. PERROT REGNERBAU REMOTE TERMINAL ‐ SERVICE 16.01.12 13:02:19 VCU Status :100‐No error [1]‐Reset VCU error [2]‐Close all manual open valves Last command: [2]‐close all manual open valves The VCU Status field indicates the current status of the decoder line. The following messages can be displayed: 100‐No Error No error has been detected. 101‐Line init If this message shows up the decoder line is being initialised. Once the initialization is finished a message follows. 100 to 105. 102‐Sync error The decoder line cannot be synchronised. Contact a Perrot representative near you. 103‐Ground error The earth current in the decoder cable is too high. Check the decoder cable for defects. (Cable connections, etc.) 104‐Load error ...
User Manual Options: [1] Reset VCU error Use this function to resets the VCU after an error has occurred. The decoder line will be initialised. This function must be executed after an error has occurred. Otherwise irrigation is impossible. [2] Close all manual open valves Use this function to close all manually open valves. Last command Your last command is always shown here. 15. Decoder 15.1 Programming of Decoder Attention: Only in Password level 3 ! Before a new decoder is installed an address (number) must be programmed into it. Decoder numbers 1 ‐ 240 are reserved for valves. Only these numbers can be activated by an irrigation program. The pump decoders have the following numbers: 246 ‐ Pump 1 ...
User Manual If frequenz 2 will be activated, decoder 251 will be simultaneously activated to start an irrigation program. Decoder 252 will only be activated, if the recorded value is exceeded. In all other situations both decoders are inactive. Programming of Decoder The only external difference of the FB decoder is the rectangular housing (Standard decoder square housing) Description of FB decoder: Type PD/F‐1 part‐no. ZH90384 The description of the new standard decoder: Type PD5/AC‐X (X is for number of stations) All decoders are infinitely programmable. 15.1.1 To program a decoder you need the following components: PC with Greenkeeper program installed and VCU Programming unit ‐FB (part no. ZH90022) or Programming cable. (Part no. SG50032) Decoder Bed‐GK 1+2e Rev. 03.04.2019 Page 130 / 143 ...
User Manual 15.1.2 Preparation for programming the Decoder Open the door of the VCU case. Connect the cable of the programming unit, to the terminals 34/35 on the VCU terminal strip. Therefore you have to disconnect the connector from the decoder cable. Start the Greenkeeper program using the appropriate password. Go to Password level 3 Click [Service –VCU status] The VCU status window opens. (Loader program) VCU‐STATUS Bed‐GK 1+2e Rev. 03.04.2019 Page 131 / 143 ...
User Manual 15.1.3 Programming with DPG Programming unit (part no. ZH90022) Connect the new decoder to the programming unit. Red cable to red terminal Blue cable to blue terminal Black cables always to black terminals Adjust the switch on the programming unit to position „0“ Click with the mouse to the required decoder number to select it. The white circle will be marked with a black point inside. Now press the F6 key or click the [F6 – program decoder] button. The LED of the decoder should be on steadily. Ready to program Press the switch into position „program“ on the programming unit earliest after 2 seconds to confirm the address Now the decoder should give 5 short flashes. Address accepted ...
User Manual 15.1.4 Programming with DPK Programming cable (part no. SG50032) Start with the steps described in item B Connect both black cables of the decoder, one to each clamp, of the programming cable. Click with the mouse to the required decoder number to select it. The white circle will be marked with a black point inside Now press the F6 key or click the [F6 – program decoder] button. The LED of the decoder should be on steadily Ready to program Do a short cut between the red and the blue cable of the decoder earliest after 2 seconds, in order to confirm the address Now the decoder should give 5 short flashes. Address accpted Should this not be the case, repeat the procedure starting with item 3 Note: With the programming cable it is not possible to check the function of the decoder. If you want to ...
User Manual 16. Error Codes Code:000‐No Error The system operation is error‐free. Code:001‐Database Error The system data is corrupted. Restore the data using the Restore function. Code:002‐%s below limit The value entered is too low. Enter a higher value. Code:003‐%s above limit The value entered is too high. Enter a lower value. Code:004‐"%s" is outside valid range The value entered is invalid. Enter a valid value. Code:005‐%s is not valid input Your entry is incorrect. Enter only numeric characters in numeric fields. Enter only alphabetic characters in alphabetic fields. Code:006‐"%s" exceed valid length Your entry has too many characters. Reduce the number of characters. Code:007‐length of the name is too short The name you selected is too short. Enter a name that is longer. Code:008‐"%s" is already used The name you entered (valve name, sector, etc.) already exists. Choose another name that is not in use Code:009‐"%s" is represented in other groups The sector you selected is assigned to another group. Choose another sector or cancel the assignment. Code:010‐Sector flow exceeded The total water consumption of valves assigned to the sector is too high. Reassign some valves to another sector. ...
Page 138
User Manual Code:012‐ Selected comport is not available select new port in "Communication Setup" and end program The COM‐Port you setup on your PC is not available. It is either not installed or is being used by another program. Code:013‐ Illegal telegram size Call the service engineer. Code:014‐ VCU‐Communication error Press the [Esc] key once. Should the message reappear check whether the power LED (green) on the VCU is on. Check COM‐port settings. Code:015‐ Wrong telegram format Call the service engineer. Code:016‐ VCU‐Storage limit exceeded The VCU program memory is full. Remove programs and/or reports you no longer need from the VCU. Code:017‐ VCU‐Unknown program name The program selected is not stored in the VCU. You have to download the program. (see Downloading programs) Code:018‐VCU‐Wrong telegram bytes Call the service engineer. Code:019‐VCU‐Illegal command Call the service engineer. Code:020‐ Max number of stored programs The VCU program memory is full. Remove programs you no longer need from the VCU (See Removing programs from the VCU) Code:021‐"%s" exceed max time The time entered is too long. (Over 24 hrs.) Enter shorter time. Code:022‐"%s" below min time The time entered is too short. Make the time longer. ...
Page 139
User Manual Code:024‐"%s" exceed max density Your entry caused high water consumption / time. Enter lower precipitation density. Code:025‐ "%s" invalid area Enter a valid area unit. Code:026‐"%s" exceed max consumption The value entered is too high. Enter a lower value. Code:027‐"%s" do not exist The selected name / sector do not exist. Code:028‐Date conflict Code:029‐ No valves No valve names have been selected. Choose the valve names. Code:030‐ No valves in sector "%s" No valves have been assigned to the sector. Code:031‐"%s" not present in program Code:032‐ Pump flow below limit Code:033‐ Closing valve Code:034‐ Program test system Code:035‐ Valve min time Code:036‐ Max program duration Code:037‐ Max program water consumption Code:038‐ Pump "%s" is not installed The pump selected does not have an "Active" status. Set the pump status in the Pump data menu to active. Code:039‐ Program "%s" exists in VCU ...
Page 140
User Manual Code:040‐ Version conflict of VCU program "%s" The PC program does not match the program in the VCU. Remove the program from the VCU and run Program test. Then download the program to the VCU. Code:041‐ VCU program "%s" do not exist on PC The PC program has been deleted. Remove the program from the VCU. Check whether Program test was run. Code:042‐ Max number of manual programs in VCU The limit of max. 8 manual programs have been exceed. Delete the manual programs you no longer need from the VCU. Max. 12 single valves‐sectors programs and max. 8 manual programs. Code:043‐ Max number of programs in VCU The limit of max. 20 programs in the VCU have been exceed. Delete the programs you no longer need from the VCU. Max. 12 single valves‐sectors programs and max. 8 manual programs. Code:044‐"%s" invalid program Code:045‐"%s" invalid start time Code:046‐"%s" invalid correction Code:047‐ Program is running Code:048‐"%s" Overlap time The start time entered causes overlapping. As a rule a delay of 10 minutes must be maintained between the stop time and start time of two programs. Code:049‐"%s" Overlap correction Correction causes overlapping. Change the correction setting. Code:050‐ The irrigation state is not inactive, reset irrigation Code:051‐ Downloading is active For your information only Code:052‐ Loading image error ...
Page 142
User Manual Code:054‐ Pump flow leak The message appears only when a flow meter has been installed. Check the pressure pipes and all valves for leaks. Code:055‐ Decoder test is running, stop test For your information only. Code:056‐ Download active, stop download Code:057‐Not enough free disk space There is not enough free storage space on your disk. Delete the programs or files you no longer need. Code:058‐ Error during backup sequence Code:059‐file "%s" is missing on restore disk Call the service engineer. Code:060‐ Port not available to remote transmitter, change settings Code:061‐Step"%s" No step time You have not entered step time for a step in the Manual program menu. Code:062‐Printer not installed You want to print but there is no printer installed. Install a printer under Windows. 100‐ No error Decoder line status. 101‐ Line init Decoder line is being initialised. Connection to decoders is being established. 102‐ Sync error The power supply of 230 V / 50 Hz is not synchronised. Restart the VCU. 103‐ Ground error The earth current is too high. Check the decoder cable for damaged insulation, valve boxes for water flooding, etc. ...
Page 143
106‐Pump alarm (ONLY FOR BI‐DIR‐DECODER) Decoder no. 245 reported a pump alarm. Eliminate the error in the pump system and delete the error. See chapter 12 107‐Decoder failure (ONLY FOR BI‐DIR‐DECODER) The accepted number of errors exceeded. Check the decoder, solenoids, etc. and delete afterwards the error messages. See chapter 12 108‐Decoder check (ONLY FOR BI‐DIR‐DECODER) The accepted number of errors from the FB‐decoder is not exceeded. Check the decoder, solenoids, etc. and delete afterwards the error messages. See chapter 12 Subject to change without prior notice. We remain at your full disposal for any further information you may require! REGNERBAU CALW GmbH Industriestrasse 19‐29 75382 Althengstett / Germany Tel. +49 / 7051 / 162‐0 technik@perrot.de http://www.perrot.de Bed‐GK 1+2e Rev. 03.04.2019 Page 143 / 143 ...