The COMMANDAIRE Model GC31 positions the actuator by applying a sufficient air pressure in the load chamber to overcome the cushion load
pressure, plus any external forces or load acting on the actuator stem. An increase in air signal pressure acts on a diaphragm and moves the yoke to
the right. This closes an exhaust port and opens the supply valve. Air flows through the supply valve into the load chamber and drives the piston
downward, extending the actuator stem. Piston movement extends the range spring,
This rotation of the bellcrank exerts a force against the yoke pin and moves the yoke towards a balanced position. A decrease in instrument air pressure
reverses the procedure, closing the supply valve and opening the exhaust port. This vents the pressure in the load chamber to atmosphere and allows
the cushion load pressure to move the piston and retract the actuator stem.
Page 1 of 8
Enidine / Conoflow
105 Commerce Way
Westminster, SC 29693
Tel: (864) 647-9521
Fax: (864) 647-7993
INSTRUCTION AND MAINTENANCE MANUAL
GC31 COMMANDAIRE POSITIONER
PRINCIPLE OF OPERATION
Conoflow products are designed and manufactured using
materials and workmanship required to meet all applicable
standards. The use of these products should be confined to
services specified and/or recommended in the Conoflow
catalogs, instructions, or by Conoflow application engineers.
To avoid personal injury or equipment damage resulting from
misuse or misapplication of a product, it is necessary to select
the proper materials of construction and pressure-temperature
ratings which are consistent with performance requirements.
which in turn
GC31-IOM Rev. B
WARNING
, causes the bellcrank to rotate counterclockwise.
07/19

Advertisement

loading
Need help?

Need help?

Do you have a question about the GC31 and is the answer not in the manual?

Questions and answers

Summary of Contents for ITT GC31

  • Page 1 PRINCIPLE OF OPERATION The COMMANDAIRE Model GC31 positions the actuator by applying a sufficient air pressure in the load chamber to overcome the cushion load pressure, plus any external forces or load acting on the actuator stem. An increase in air signal pressure acts on a diaphragm and moves the yoke to the right.
  • Page 2 (14) and lift positioner from the actuator. Filter Regulator INSTALLING POSITIONER ON ACTUATOR The Model GC31 positioner is designed for actuators having a 2 Actuator ¼” dimension between the lower face of the range spring nut (8D) and the positioner mounting flange with the actuator stem in a retracted position.
  • Page 3 When used with a Conoflow model GH232T reversing relay consists of a volume tank (pressure vessel) and a check valve rather than a cushion load regulator, the GC31 positioner will that drives the cushion load regulator and lifts the actuator piston provide maximum actuator stem thrust loads in extension and when the air supply fails.
  • Page 4 See manual C-8053 for full description of range spring configurations RANGE SPRING ADJUSTMENT CHART TRAVEL IN INCHES FOR SPAN REQUIRED NOTE: For travels greater than 10" (254mm) consult factory Page 4 of 8 GC31-IOM Rev. B 07/19...
  • Page 5 Notes: All connections are ¼” NPT unless otherwise noted. When ordering, specify model, range and stroke. For additional piping schematics, see A50-48 Vent ports can be tapped ¼” NPT for gas service. Page 5 of 8 GC31-IOM Rev. B 07/19...
  • Page 6 8-32 x 1/2" Long Round Head Machine G6900007 Spacer G6026785 Screw 4-40 x 1/2" Long #4 Self Tapping Screw Pilot Assembly G6027148 G6900545 3/8" Long Gasket G6001762 SEE NOTES ON PAGE 7 Page 6 of 8 GC31-IOM Rev. B 07/19...
  • Page 7 Notes: Recommended spare parts can be purchased individually, or as a spare parts kit, under part number G6385464, Spare Parts Kit GC31 (Consists of items 7, 13, 20 and 23). When ordering spare parts, specify complete catalog no., item no., and part no. This will permit positive identification and rapid handling of order.
  • Page 8 This Page Intentionally Left Blank Page 8 of 8 GC31-IOM Rev. B 07/19...