Advertisement

Quick Links

Application
Duomo is recognised within the gas industry for
providing a comprehensive range of low cost, high
reliability gas detection for many applications. We have
installed and commissioned natural gas and carbon
monoxide sensors in applications such as boiler rooms,
kitchens, car parks, aircraft hangers, factories and
shopping centres. The BX216 is the command centre for
the complete range of Duomo gas sensors. All Duomo
products are manufactured to meet relevant European
Normatives and proposals for explosive and toxic gases.
Operation
The BX216 can detect both explosive and toxic gases.
When the remote sensor detects the presence of the
target gas a 4 - 20mA signal is sent to the detector,
proportional to the level of gas. The BX216 then
operates a pre-alarm relay - used for remote sirens or
visual indicators. If the level of gas continues to rise then
the second pre-alarm is actuated. In the case of
explosive gases, when the gas reaches a preset level, the
main alarm relay is activated to break the electrical
supply to the gas safety shut-off valve (SSOV).The BX216
also has a separate volt-free sensor fault relay that
actuates if the correct return signal is not sensed by the
detector. There is also the provision of a fire alarm
interface. This controller can be interlinked with a fire
alarm so that in the event of a fire, it would shut down
the gas supply.
w: www.duomo.co.uk
-
e: sales@duomo.co.uk
BX316 Gas Detector
Microprocessor control
Wall mounted
16 zone protection (across 1 or 2 zones)
4 - 20mA signal input
Relay outputs (incl. fire alarm interface)
Positive safety feature
Measuring range 0 - 20% LEL/0 - 300ppm
IP65 protective rating
EN50194 for explosive gases
EN50291 for toxic gases
3 year guarantee
Features
The BX216 is a wall mounted microprocessor based gas
detector control unit. It can be configured to meet
customer requirements. The following parameters can
be changed using the on board menu:
Number of sensors from 1 to 16
Type of gas to be sensed (explosive or toxic)
Pre-alarm level for each sensor
The number of zones (1 or 2)
Main alarm relay action (latching or auto-reset)
Positive safety feature
Alarm logging function
Event history
The BX216 has five main terminal blocks for the
following;
The incoming mains supply
The alarm circuit wiring (including fault, siren,
pre-alarm and main alarm relays)
The power supply to the sensors
The 4 - 20mA return cable from the sensors
A 0 - 10V output to BMS proportional to the 4 - 20mA
return signal
The front panel has an LCD display showing the date,
time, current sensor levels and much more. LED's on the
panel indicate what alarm status the unit is in, as well as
any faults present on the connected sensors.
-
t: 01905 797989
-
f: 01905 774296
|
© Duomo (UK) Ltd. 2007

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the BX316 and is the answer not in the manual?

Questions and answers

Summary of Contents for Duomo BX316

  • Page 1 Number of sensors from 1 to 16 shopping centres. The BX216 is the command centre for Type of gas to be sensed (explosive or toxic) the complete range of Duomo gas sensors. All Duomo Pre-alarm level for each sensor products are manufactured to meet relevant European The number of zones (1 or 2) Normatives and proposals for explosive and toxic gases.
  • Page 2: Overall Dimensions

    19. Mains Supply Terminal Block - Connections for the incoming mains supply. 20. External Alarm Terminal Block - Connections for a fire alarm / external emergency stop etc. w: www.duomo.co.uk e: sales@duomo.co.uk t: 01905 797989 f: 01905 774296 © Duomo (UK) Ltd. 2007...
  • Page 3 ZONE 1 ZONE 2 ZONE 1 ZONE 2 RELAY RELAY ZONE 1 ZONE 2 ZONE 1 ZONE 2 3/5A 3/5A Power Power Supply Supply 230V 230V w: www.duomo.co.uk e: sales@duomo.co.uk t: 01905 797989 f: 01905 774296 © Duomo (UK) Ltd. 2007...
  • Page 4: Electrical Installation

    The sensor this gas detector Duomo will not be held responsible or can be located up to 100m from the gas detector. Cable liable.
  • Page 5: Time Settings

    An x means that that zone has been The last option is the Advanced Features menu. disabled i.e. there is no sensor detected. A means it has w: www.duomo.co.uk e: sales@duomo.co.uk t: 01905 797989 f: 01905 774296 © Duomo (UK) Ltd. 2007...
  • Page 6: Advanced Features

    To go back to the top menu, press Enter when on Use the up and down keys on the keypad to move w: www.duomo.co.uk e: sales@duomo.co.uk t: 01905 797989 f: 01905 774296 © Duomo (UK) Ltd. 2007...
  • Page 7: Test Probes

    B a c k Select Back to return the previous menu. w: www.duomo.co.uk e: sales@duomo.co.uk t: 01905 797989 f: 01905 774296 © Duomo (UK) Ltd. 2007...
  • Page 8: Maintenance Procedure

    It is prudent to make electrical connection to the detector terminal plus when withdrawn and leave the plug off the detector so that the Duomo Engineer is the first to power up the unit on site. This allows wiring to be checked prior to commissioning and avoids damage due to incorrect connection.
  • Page 9: Troubleshooting

    Sensor is connected, but no information is shown on Check that the sensor is enabled in the internal the display. menu. If you are experiencing difficulties, having made the checks listed above call Duomo on 01905 797989 for technical assistance. In case of alarm Extinguish any naked flames.
  • Page 10: Technical Specification

    SGM595, CO100Ar, CO200A, SG895 Maximum distance for sensor connection Cable diameter for sensors Dimemsions x 320 x 135 Protective rating IP65 Guarantee 3 years from date of manufacture w: www.duomo.co.uk e: sales@duomo.co.uk t: 01905 797989 f: 01905 774296 © Duomo (UK) Ltd. 2007...