2.2 Residual risks due to electrical energy Before all work on the device: have the device fully disconnected by a qualified electrician. Product codes 400B19EN01 | 401B19EN01 5/28 ENR 300 level controller | ETS 100 and ETS 200 signalling devices...
DANGER High Death or serious injury will result WARNING Moderate Death or serious injury are possible CAUTION Minor injuries are possible 6/28 Product codes 400B19EN01 | 401B19EN01 ENR 300 level controller | ETS 100 and ETS 200 signalling devices...
Minimum/maximum control using the ENR 300 level controller When the highest or lowest fill level is reached, the relays switch over. 8/28 Product codes 400B19EN01 | 401B19EN01 ENR 300 level controller | ETS 100 and ETS 200 signalling devices...
With level probe NS, the reference potential is on terminal 11. The reference potential is connected to functional earth conforming to VDE 0100. MTS insulated floating switches do not require any functional earthing. 14/28 Product codes 400B19EN01 | 401B19EN01 ENR 300 level controller | ETS 100 and ETS 200 signalling devices...
Page 15
Centre tapping of the changeover floating switches contacts Depending on the application, connect the changeover contacts as NC or NO contacts. Product codes 400B19EN01 | 401B19EN01 15/28 ENR 300 level controller | ETS 100 and ETS 200 signalling devices...
Depending on the application, connect the floating relay outputs as NC or NO contacts. Take the active status of the relays into account: Chapter 6.3 Setting the active status of the relays 16/28 Product codes 400B19EN01 | 401B19EN01 ENR 300 level controller | ETS 100 and ETS 200 signalling devices...
Device in conjunction with MTS2u and MTS3u float switches Set the switch to "Func." for the function test. Set the "SENSITIVITY" rotary switch to "3". Product codes 400B19EN01 | 401B19EN01 17/28 ENR 300 level controller | ETS 100 and ETS 200 signalling devices...
When all LEDs and switch outputs have responded, the sensitivity is correctly set. Recommendation: to partially compensate for the conductivity change of the liquid, set the "SENSITIVITY" rotary switch one step higher. 18/28 Product codes 400B19EN01 | 401B19EN01 ENR 300 level controller | ETS 100 and ETS 200 signalling devices...
Can the response sensitivity be set? ■ Device is functioning. ■ Check wiring to sensor. Test conductance of the medium. 22/28 Product codes 400B19EN01 | 401B19EN01 ENR 300 level controller | ETS 100 and ETS 200 signalling devices...
M & E3 are wetted M & E1 are wetted, E2 was previously wetted LED off E1 & E2 are not wetted E3 is not wetted Product codes 400B19EN01 | 401B19EN01 23/28 ENR 300 level controller | ETS 100 and ETS 200 signalling devices...
7 Diagnostics Changeover conditions of the "RELAY 1" LED with ENR 300 level controller The status of the "RELAY 1" LED is based on a logical AND operator (&). The status remains in force until one of the changeover conditions is met: ■...
– Avoid penetration of liquids or powdered substances into the housing. For queries relating to the cleaning, please contact Mazurczak GmbH. Product codes 400B19EN01 | 401B19EN01 25/28 ENR 300 level controller | ETS 100 and ETS 200 signalling devices...
The cleaning procedure depends on the process liquid and the ambient conditions. Contact the manufacturer of the process liquid for the relevant cleaning procedure. Neutralise hazard substance residues. 26/28 Product codes 400B19EN01 | 401B19EN01 ENR 300 level controller | ETS 100 and ETS 200 signalling devices...
Remove the device from the bearing rail. The device must be disposed of in an environmentally friendly manner in line with local regulations. Product codes 400B19EN01 | 401B19EN01 27/28 ENR 300 level controller | ETS 100 and ETS 200 signalling devices...
Page 28
Distribution as well as duplication of this document, usage and communication of its content are forbidden, unless explicitly permitted. Infringements will result in damage claims Subject to technical modifications. Mazurczak GmbH Schlachthofstraße 3 91126 Schwabach/Germany Phone: +49 91 22 98 55-0 Fax: +49 91 22 98 55-99 kontakt@mazurczak.de...