• Please report any errors or questions about the information in this manual to your local supplier� • These instructions are written specifically for the 4411 IP Transducer, and do not apply for other instruments or IP transducers outside of this product line�...
Brief User Guide This is a quick guide to connecting the instrument for the conven- ience of personnel who are familiar with this type of product� DO NOT use a voltage source; it will irreversibly damage More comprehensive instructions are contained later in this the converter�...
30psig (2 bar). in this condition� The instrument cover must be unscrewed to obtain access to The Model 4411 approximates a constant voltage load of 6�5 the trimpots� volts across the loop terminals, therefore it is essential that the loop controller be capable of providing a constant current in the range 4-20mA with an output voltage of at least 6�5 volts�...
Technical Specifications Functional Input: 4-20mA (0-100%) Output: 3-15psi and 15-3 psi or 6-30 psi and 30-6 psi Minimum output greater than 0�2psi Supply Pressure: 150psi maximum, minimum 3psi above max required output pressure Supply Pressure Effect: Span over full supply pressure range <0�1% Medium: Standard instrument quality air to 50 micron Air Consumption:...
8� Only approved cable glands are to be used which must SIRA 01ATEX1223 maintain an Ingress Protection of IP66� 1. The Model 4411 is Triple Certified, and may be installed 9� Unused entry port hole must be blanked off using as intrinsically safe, flameproof or Type n: suitably approved blanking plug�...
Page 16
DIRECT SALES OFFICE LOCATIONS AUSTRALIA ITALY SOUTH AFRICA Brisbane: Phone: +39-081-7892-111 Phone: +27-11-452-1550 Phone: +61-7-3001-4319 Fax: +39-081-7892-208 Fax: +27-11-452-6542 Fax: +61-7-3001-4399 JAPAN SOUTH & CENTRAL Perth: Chiba AMERICA AND THE CARIBBEAN Phone: +61-8-6595-7018 Phone: +81-43-297-9222 Phone: +55-12-2134-1201 Fax: +61 8 6595-7299 Fax: +81-43-299-1115 Fax:...