DRAWN 12/4/08 PROPRIETARY SPECIFICATION OUTLINE PROJECT ENGR THIS DRAWING IS THE PROPERTY OF SURE POWER INC. and shall not be SIZE CAGE CODE NO. DRAWING NO. copied, reproduced, lent, or disposed of, nor used for any purpose other than 3104...
Page 2
OVERVIEW The 3104 is a 300A integrated solenoid and control module for 14V systems. The unit features a bi-stable solenoid that can remain open or closed without a coil current draw. The unit can be utilized in four different modes of operation based on settings of jumpers external to the unit.
LED output - Pin F TITLE This is the LED drive output. This output indicates the status of the MODEL NO: 3104 unit. This output is a 20mA ± 5mA current source. The LED is INTERCONNECT CONTROLLER powered when the solenoid is open and off when the solenoid is 12V,300A closed.
Lockout input is grounded, the solenoid will close if it is open and will not open for TITLE either low voltage or a ground signal on the Switch input. If the unit was placed in MODEL NO: 3104 MANUAL MODE before grounding the lockout pin, the 75-second delay must INTERCONNECT CONTROLLER timeout before lockout mode takes precedence.
Once the short is removed, the ISW input can be utilized to put the relay in its intended state. MECHANICAL SPECIFICATIONS: Weight: 1.6 LBS (0.74Kg) M10 Lug Installation Torque: 112.5 In-lbs, 12.71N-m TITLE MODEL NO: 3104 INTERCONNECT CONTROLLER 12V,300A SPECIFICATION OUTLINE SIZE CAGE CODE NO.
S,MAXO Rupture current 3000 Current above which solenoid may explode. S,RUPT Electrical Isolation V AC All terminals together with respect to ground. TITLE MODEL NO: 3104 INTERCONNECT CONTROLLER 12V,300A SPECIFICATION OUTLINE SIZE CAGE CODE NO. DRAWING NO. 3104 55156 SHEET...
On models with suffix numbers, the suffix Disconnect Voltage: 12.5 12.7 13.0 DCON specifies the disconnect voltage, e.g. 3104-125 has a 12.5V disconnect voltage. Connect Voltage 12 to 14 9 to 16 CONR Factory and Customer set range Adjust Range -0.3...
Page 8
Error Mode 1 voltage Voltage across solenoid to enter error mode 2. ERR2 Error Mode 1 flash rate EFLSH1 Error Mode 2 flash rate EFLSH2 TITLE MODEL NO: 3104 INTERCONNECT CONTROLLER 12V,300A SPECIFICATION OUTLINE SIZE CAGE CODE NO. DRAWING NO. 3104...
(Solenoid is not current limited. Connecting battery banks of opposite polarity will damage solenoid). Solenoid drive lines, LED output and ALRM outputs are protected from continuous shorts to ground. Jumper inputs, ISW, and LOCK inputs are protected from connection to battery inputs. TITLE MODEL NO: 3104 INTERCONNECT CONTROLLER 12V,300A SPECIFICATION OUTLINE SIZE CAGE CODE NO.
Page 10
REVISIONS REV ECO DESCRIPTION DATE - SEE SHEET 1- TITLE MODEL NO: 3104 INTERCONNECT CONTROLLER 12V,300A SPECIFICATION OUTLINE SIZE CAGE CODE NO. DRAWING NO. 3104 55156 SHEET SCALE: NONE FILE: 3104-006 F04-019-006...
Page 11
STRT SPST N.O. MOMENTARY CLOSE TO TOGGLE SBAT ABAT INDICATOR START START LOADS LOADS ISOLATOR PLUS INTERCONNECT APPLICATION TITLE MODEL NO: 3104 INTERCONNECT CONTROLLER 12V,300A SPECIFICATION OUTLINE SIZE CAGE CODE NO. DRAWING NO. 3104 55156 SHEET SCALE: NONE FILE: 3104-006...
Page 12
(2.53 [64.3]) (.28 [7.1]) 1.180 [29.97] 3.25 [82.6] 3.63 [92.2] 3.56 [90.4] NOTE: Connection diagram is oriented as facing relay side on unit. TITLE MODEL NO: 3104 INTERCONNECT CONTROLLER 12V,300A SPECIFICATION OUTLINE SIZE CAGE CODE NO. DRAWING NO. 3104 55156...