Instruction Manual AirSanitizer In addition to the instructions in this guide, subject-specific standards, as well as local, national and international regulations must be observed. The instruction manual is available online, see QR-code beneath. The online version always contains the updated version.
‘AHU’. This instruction manual is part of the AHU and enable the safe and correct use of an AHU from EUROCLIMA. The target group of this instruction manual are all persons who are fa- miliar with transport, assembly, commissioning and installation, operation, maintenance, trouble- shooting and disassembling (see also chapter 2.5 (Staff selection and qualification)).
Silencer Fan / Potentiometer Motor (inside the AHU) Silencer ON / OFF HEPA filter H 13 switch (EN 1822:2019) Pre-filter ePM 85% (ISO 16890) (rear of the AHU) Micro fuse Air inlet Figure 1: Construction air purifier “AirSanitizer” V12-20.0 5/28...
Instruction Manual AirSanitizer 1.5.2 Technical data Information S-Version M-Version Dimensions 2003 x 710 x 405 mm 2307 x 710 x 710 mm (height x width x depth) Weight unpacked Ca. 135 kg Ca. 175 kg Length of cable 3 meter...
Instruction Manual AirSanitizer Warning symbol Type of hazard Warning of general danger Warning of electrical voltage Warning of pointed objects and sharp edges Warning of rotating parts Warning of tilting parts Warning of suspended load Table 2: Warning symbols of situation-related dangers 2.2 Personal protective equipment...
Instruction Manual AirSanitizer FFP3 respiratory protection: FFP3 respiratory protection is used to protect against contaminated material, such as aerosols, harmful dusts, etc. Table 3: Symbols of personal protective equipment 2.3 Indications for minimizing specific hazards Danger due to lack of missing or improper maintenance...
Instruction Manual AirSanitizer Dangers during standstill If the AHU is at a standstill, e.g. in the event of a power failure, the AHU must be disconnected from the power supply by using the power plug, as described above, and secured against unintentional reconnection before opening the AHU. Only...
When the AHUs arrive, please check the scope of delivery for completeness and damage im- mediately. Scope of delivery: o EUROCLIMA air purifier o Instruction manual (loose in transport bag on the outside of the AHU) o Tool wrench (hexagon socket / Allen bit 5 mm) (loose in the transport bag on the out-...
Instruction Manual AirSanitizer Before further lifting, check by visual inspection that no conspicuous defor- mations can be detected on the suspension means. Avoid jerky lifting. Loads must be picked up and set down in such a way that unintentional over- turning, falling apart, sliding or rolling of the load is avoided.
Instruction Manual AirSanitizer Figure 4: Center of gravity centrally between the forks 3.3 Storage The AHU is generally packed in nylon. This package is suitable to protect the AHU during loading and unloading from bad weather, but not for outdoor storage. The insertion into a dry area after un- loading is therefore essential for the preservation of the AHU.
Instruction Manual AirSanitizer 1. The mounting bracket supplied loose (see Figure 5) is to be fixed to the rivet nuts at the rear of the AHUs blow out hood in exact alignment using the enclosed fixing screws (see Figure 6), see Figure 7.
Instruction Manual AirSanitizer 4.4 Erection 4.4.1 Potential risks that may arise at the erection site Cleaning work - including wet cleaning - can be carried out on the inside and outside of the AHU. During this work, leakage / dripping of cleaning fluid is possible.
Instruction Manual AirSanitizer Commissioning 5.1 Preliminary steps Clean thoroughly the AHU and all components of dust, swarf, and other debris. Remove all loose parts like tools, documentation, etc. from the AHU. Such parts can be sucked in by the fan and lead to its destruction.
Instruction Manual AirSanitizer Danger due to rotating parts Before opening the service door, all current-carrying parts, e.g. fan, etc., must be disconnected from the power by using the power plug and the overrun time of the fan must be considered. The instructions in chapter 2 (Safety instructions) must...
VDI 6022 sheet 1 and VDMA 24186 part 1. Please note that EUROCLIMA is not responsible for damage caused by improper handling of sol- vents and cleaning agents, and not liable for mechanical damage. Solvents and cleaning agents may not contain alcohol for use on coated surfaces.
Instruction Manual AirSanitizer 7.1 Electrical connection All electrical connections must be inspected annually and deficiencies (e.g. loose cable strands, loose screw, clamp connection, etc.) must be identified and eliminated immediately. Any dust de- posits must be removed regularly. The AHU is secured with a micro fuse F1 3.15 A (see Figure 1, in chapter 1.5.1 (Overview / con- struction of the AHU)).
AirSanitizer 7.3 Air filters EUROCLIMA recommends changing the filter outside the period of use to reduce the risk of infec- tion for other persons. When checking and changing the filters, disposable gloves and FFP3 respir- atory protection must be used. The soiled filters must be disposed of in closed waste bags and in accordance with local regulations.
Instruction Manual AirSanitizer 7.3.2 HEPA filter H 13 (EN 1822:2019) The HEPA filter must be checked regularly (according to maintenance plan Table 6) for degree of contamination, damage, odor, and moisture penetration. For inspection, cleaning and mainte- nance, the HEPA filter must be pulled out (upper filter, see Figure 15).
Page 22
Instruction Manual AirSanitizer Components (examples) Material CER / EWC European Waste Code Casing panels, built-in com- VZ and VZB sheet metal 170405 ponents, base frames Aluminum 170402 Copper cable Copper cable 170411 Casing insulation Mineral wool 170604 Air filter Plastic, metal...
Page 28
Instruction Manual AirSanitizer Figure index Figure 1: Construction air purifier “AirSanitizer” ................5 Figure 2: Correct transport ......................11 Figure 3: Incorrect transport ......................11 Figure 4: Center of gravity centrally between the forks ..............12 Figure 5: Mounting bracket (supplied loose) ................. 13 Figure 6: Fixing screw for mounting bracket .................