Installation & Operation Instructions
AFP
GENERAL INFORMATION
The AFP allows an analog (voltage or current)
signal to control a
converts an analog signal into two relay contact
outputs (one increase/one decrease). The isolated
oating point output can be controlled by any one
of nine analog input signal ranges (using an o set
jumper). Upon power-up, the decrease relay will
drive 100% of the chosen timing range to ensure
that the output is at its minimum position. On a
loss of power, the output relays will be open and
no signal will be generated. The actuator will
remain at the last commanded position unless it
has "spring return". The AFP output rate of change
(sixteen ranges, in eight versions) is DIP switch
selectable.
MOUNTING INFORMATION
Circuit board may be mounted in any position. If
circuit board slides out of snap track, a
non-conductive "stop" may be required. Use only
ngers to remove board from snap track. Slide
out of snap track or push against side of snap
track and lift that side of the circuit board to
remove. Do not ex board. Use no tools.
WIRING INSTRUCTIONS
PRECAUTIONS
• Remove power before wiring. Never connect
or disconnect wiring with power applied.
• When using a shielded cable, ground the
shield only at the controller end. Grounding
both ends can cause a ground loop.
• It is recommended you use an isolated
UL-listed class 2 transformer when powering
the unit with 24 VAC. Failure to wire the
devices with the correct polarity when sharing
transformers may result in damage to any
device powered by the shared transformer.
• If the 24 VDC or 24VAC power is shared with
devices that have coils such as relays,
solenoids, or other inductors, each coil must
have an MOV, DC/AC Transorb, Transient
Voltage Suppressor (ACI Part: 142583), or
diode placed across the coil or inductor. The
cathode, or banded side of the DC Transorb or
diode, connects to the positive side of the
power supply. Without these snubbers, coils
produce very large voltage spikes when
de-energizing that can cause malfunction or
destruction of electronic circuits.
• All wiring must comply with all local and
National Electric Codes.
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
oating point actuator. It
FIGURE 1: DIMENSIONS
3.25"
(82.55mm)
3.25"
(82.55mm)
Page 1
Phone: 1-888-967-5224
Website: workaci.com
4.00" (101.60mm)
3.88"(98.55mm)
0.70"
(17.78mm)
Version: 7.0
I0000584

Advertisement

loading

Summary of Contents for aci AFP Series

  • Page 1 MOV, DC/AC Transorb, Transient Voltage Suppressor (ACI Part: 142583), or diode placed across the coil or inductor. The cathode, or banded side of the DC Transorb or diode, connects to the positive side of the power supply.
  • Page 2 FIGURE 2: WIRING Relay Common To Floating N.O. (Counter-clockwise or DOWN) Point Actuator N.O. (Clockwise or UP) (+) 24 Volt Accessory (Option) (+) Analog Input (-) Analog, Power and Accessory Common (+) Power - 24 VDC/VAC @ 50/60Hz Floating Point Actuator Optional Wiring Setup 4 - 20mA Loop Powered Signal...
  • Page 3 SETUP Version #1 - Program AFP_0101.hex 30, 60, or 90 seconds Analog input signal ranges are jumper selectable by using Jumper J3, see Figure 3. The output of the AFP has two relays. One relay Switch (SW1) controls UP (increase), the other DOWN (decrease) depending, of 30 sec.
  • Page 4: Troubleshooting & Testing

    21 to 25 VDC. Please note supply and Vout voltages if unit is not functioning properly. Contact technical support at ACI. 3.) Y2 will drive the actuator down 105% of selected range (200% on Version 2, 105% up on Ver 7) if power is removed and reapplied.
  • Page 5 “Vout+” to “24V-“ terminals. Resistance in the voltage modes will be around 10K Ohms and greater. If input is shorted contact tech support at ACI. If not shorted remove the controller input common and connect power only to AFP. NOTE: Place meter in voltage mode and measure VAC and VDC from analog input common wire to power supply common.
  • Page 6: Product Specifications

    Snaptrack Material: Polyvinyl Chloride (PVC) WARRANTY The ACI AFP Series is covered by ACI’s Two (2) Year Limited Warranty, which is located in the front of ACI’S SENSORS & TRANSMITTERS CATALOG or can be found on ACI’s website: www.workaci.com. Page 6 Automation Components, Inc.
  • Page 7 NOTES Page 7 Automation Components, Inc. Version: 7.0 2305 Pleasant View Road | Middleton, WI 53562 I0000584 Phone: 1-888-967-5224 | Website: workaci.com...
  • Page 8 Automation Components, Inc. 2305 Pleasant View Road Middleton, WI 53562 Phone: 1-888-967-5224 Website: workaci.com Page 8 Automation Components, Inc. Version: 7.0 2305 Pleasant View Road | Middleton, WI 53562 I0000584 Phone: 1-888-967-5224 | Website: workaci.com...