Duct temperature sensors

Advertisement

Quick Links

Caution!
The Duct Sensor Is Used For Sensing Supply
Or Return Air Temperatures. Location Of The
Sensors Is Very Important In Order To Obtain
Accurate Temperature Readings. The
Following Recommendations Should Be
Followed:
Supply Air
When Used As A Supply Air Sensor The
Sensor Should Be Mounted In The Supply Air
Duct As Close To The HVAC Unit As Possible
And Upstream Of The Bypass Damper (If
Used) For Best Results. For Best Accuracy,
Apply Insulation On The Outside Of The
Ductwork Over The Sensor. This Will Help
Thermal Gradients From Affecting The Sensor.
Return Air
When Used As A Return Air Sensor The
Sensor Should Be Mounted In The Return Air
Duct As Close To The HVAC Unit As Possible
And Upstream Of The Bypass Damper (If
Used) For Best Results. For Best Accuracy,
Apply Insulation On The Outside Of The
Ductwork Over The Sensor. This Will Help
Thermal Gradients From Affecting The Sensor.
See The Systems Installation And Operation
Manual For Other Design Considerations And
Recommendations Regarding Duct
Temperature Sensor Location.
Temp
Resistance* Voltage
°
F
Ohms
-10.............93333 ........4.620
-5...............80531 ........4.550
0 ...............69822 ........4.474
5 ...............60552 ........4.390
10 ..............52500 ........4.297
15 ..............45902 ........4.200
20 ..............40147 ........4.095
25 ..............35165 ........3.982
30 ..............30805 ........3.862
35 ..............27140 ........3.737
40 ..............23874 ........3.605
*Chart Notes:
1. Use the resistance column to check the thermistor sensor while disconnected from the controllers (not powered).
2. Use the voltage column to check sensors while connected to powered controllers. Read voltage with meter set on DC volts.
Place the "-"(minus) lead on GND terminal and the "+"(plus) lead on the sensor input terminal being investigated. If the voltage
is above 5.08 VDC, the sensor or wiring is "open." If the voltage is less than 0.05 VDC, the sensor or wiring is shorted.
Notes:
.)All Wiring To Be In Accordance With
1
Local And National Electrical Codes
And Specifications.
Duct Temperature Sensors
OE230 (6" Probe) & OE231 (12" Probe)
Temperature Sensor Resistance/Voltage Chart
Temp
Resistance* Voltage
°
@ Input*
F
Ohms
45 ..............21094 ........3.470
50 ..............18655 ........3.330
52 ..............17799 ........3.275
54 ..............16956 ........3.217
56 ..............16164 ........3.160
58 ..............15385 ........3.100
60 ..............14681 ........3.042
62 ..............14014 ........2.985
64 ..............13382 ........2.927
66 ..............12758 ........2.867
68 ..............12191 ........2.810
Thread
Together
5-1/2" (OE230)
11-1/2" (OE231)
Drill 3/8" Hole In Ductwork For Probe
Temp
Resistance* Voltage
°
@ Input*
F
Ohms
69 ..............11906 ........2.780
70 ..............11652 ........2.752
71 ..............11379 ........2.722
72 ..............11136 ........2.695
73 ..............10878 ........2.665
74 ..............10625 ........2.635
75 ..............10398 ........2.607
76 ..............10158 ........2.570
78 ..............9711 ..........2.520
80 ..............9302 ..........2.465
82 ..............8893 ..........2.407
FILENAME
G-DUCSENS1.CDR
DATE:
PAGE
1
Leads Are Non-polarized.
Butt Splice Leads To 24 Gauge
Wire Minimum. Connect Leads
To "Analog In" And "Ground"
At Controller.
4.0"
3/4"
Mounting Plate
1/4" Hex Head Sheet Metal Screws
Mounting Plate
Gasket
Adhesive Backed Drill Guide
Mounting Template
Duct Work
Temp
Resistance* Voltage
°
@ Input*
F
Ohms
@ Input*
84 ..............8514 ..........2.352
86 ..............8153 ..........2.297
88 ..............7805 ..........2.242
90 ..............7472 ..........2.187
95 ..............6716 ..........2.055
100 ............6047 ..........1.927
105 ............5453 ..........1.805
110 ............4923 ..........1.687
115 ............4449 ..........1.575
120 ............4030 ..........1.469
125 ............3656 ..........1.369
JOB NAME
DRAWN BY:
07/13/15
DESCRIPTION:
OE230 & OE231
Duct Temperature Sensor
B. CREWS

Advertisement

loading
Need help?

Need help?

Do you have a question about the OE230 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for WattMaster OE230

  • Page 1 Duct Temperature Sensors OE230 (6" Probe) & OE231 (12" Probe) Leads Are Non-polarized. Caution! Butt Splice Leads To 24 Gauge The Duct Sensor Is Used For Sensing Supply Wire Minimum. Connect Leads Or Return Air Temperatures. Location Of The To "Analog In" And "Ground"...
  • Page 2 The OE230 Duct Sensor Threads Into Leads Are Non-polarized. The OE291 Stainless Steel Thermowell. Butt Splice Leads To 24 The OE291 Thermowell Threads Into A Gauge Wire Minimum. 1/2” FPT Elbow or Tee in the Water Piping Connect Leads To of the Water Coil at Which You wish to "Analog In"...
  • Page 3 Butt Splice Or Wire Nut Wire Leads And Extend Wire To Controller Terminals. Connect One Wire Lead To Return Water Temperature Or Supply Water Temperature Terminal At The Controller As Required By Intended Use. Secure Other Wire Lead To Ground Terminal At The Controller. See Note 3. Secure Sensor Element And Thermal Mastic Strip To Pipe With Supplied Wire Tie.
  • Page 4 Gasketed Cover CAUTION! Cover See Note3 Mounting Closure Plug 2.70” CAUTION! Screw - Typ. 2.30” See Note 2 3.00” 0.21" Dia. x 0.73 Lg. Slot - Typ. Mounting Tab & Screws - Typ. Mounting Tab & Screw - Typ. Closure Plug CAUTION! See Note 2 Incorrect...
  • Page 5 Right Side View Front View Installation Instructions: 1.) Place The SpaceHumidity Sensor Where It Is To Be Mounted. See Note 1 Below For Important Mounting Information And Considera tions. 2.) Remove The Humidity Sensor Cover By Screwing In The 2 Allen Screws That Secure It To The Base. 3.) Connect All Of The Wires From The Controller Board To The Corresponding Terminal Blocks Per The Wiring Diagram On Page 2 Of This Drawing.
  • Page 6 CONNECT TO SPECIFIED AIx TERMINAL FOR YOUR NOTE: RESISTOR IS NOT APPLICATION. SEE SPECIFIC REQUIRED FOR CONTROLLERS WIRING DIAGRAM FOR YOUR THAT HAVE JUMPER 24 VAC or VDC THE PULL-UP RESISTOR (PUx) APPLICATION FOR CORRECT SELECTABLE ANALOG INPUTS. FOR THE ASSOCIATED ANALOG AIX TERMINAL TO BE USED.
  • Page 7 View Right Left Side Side View View Front 7.21 View Installation Instructions: 1.) Place The Outside Air Humidity Sensor Where It Is To Be Mounted. See Note 1 Below For Important Mounting Information And Considerations. Mark The (4) Mounting Holes. Secure The INCORRECT Humidity Sensor By Using The Four #10 X 1.5"...
  • Page 8 0-5 VDC Output Wiring (24VAC Power) CONNECT TO 24 VAC POWER Warning Be Sure To Observe Polarity Or Serious Damage To The Board Could Result SENSOR TERMINAL BLOCK Humidity Sensor RH/Voltage Chart Output Output 5 ..0.25 55 ..2.75 10 ..
  • Page 9 See Note #1 Mounting Sensor to Duct View Left Right Side Side View View Front View Installation Instructions: 1.) Drill a 1" Diameter Hole In The Duct Wall In the Location Where The Humidity Sensor Is To Be Mounted. Insert The Probe Of The Return Air Humidity Sensor Through The Hole.
  • Page 10 0-5 VDC Output Wiring (24 VAC Power) CONNECT TO 24 VAC POWER Warning Be Sure To Observe Polarity Or Serious Damage To The Unit Could Result SENSOR TERMINAL BLOCK Humidity Sensor RH/Voltage Chart Output Output 5 ..0.25 55 ..2.75 10 ..
  • Page 11 OE271 - Airflow Sensor Applications Requiring 0-5“ H O Pressure Range 2.50" 0-5“ H O Pressure Range - 5 VDC Operation 2.20" Minimum Typical Maximum Full Scale Output 3.92 VDC 3.95-4.05 VDC 4.08 VDC (Positive Pressure) Null Offset 0.17 VDC 0.2-0.3 VDC 0.33 VDC 12.0"...
  • Page 12 OE274 - Airflow Sensor For Applications Requiring 0-1.5“ H O Pressure Range 2.50" 0-1.5“ H O Pressure Range - 5 VDC Operation 2.20" Minimum Typical Maximum Full Scale Output 3.92 VDC 3.95-4.05 VDC 4.08 VDC (Positive Pressure) Null Offset 0.17 VDC 0.2-0.3 VDC 0.33 VDC 12.0"...
  • Page 13 2.00“ 2.75“ 0.88“ 0.25“ Wall Cut-Out Dimensions When Sensor Is To Be Mounted Without Room Sensor Typical Dimensions Handy Box (By Others) OE213 OE210 OE211 OE212 Room Sensor - Plain Room Sensor Room Sensor Room Sensor With Setpoint Adjust With Override With Setpoint Adjust &...
  • Page 14 Static Pressure Pickup Tube OE290 Connect This End Of Tubing To “Hi” Port Of Pressure Sensor 1/4“ O.D. X 3/16” I.D. x 14” Long - Fire Rated Tubing Slide Over 1/4“ Barb Fitting Tubing Not To Exceed 250 Ft. Length. Do Not Splice Tubing.
  • Page 15 40F to 120F Wire Terminals Range RH = 0-100% 3.2 oz. Ambient Weight -40F to 180F Temperature Limits Accuracy RH +/-3%, Temp +/- .8F Three Year Warranty WattMaster reserves the right to change specifications without notice Page 1 of 1 Form: AZ2-OE217-02-03-EBUS-DRS-1D.doc...
  • Page 16 40F to 120F Wire Terminals Range RH = 0-100% 3.2 oz. Ambient Weight -40F to 180F Temperature Limits Accuracy RH +/-3%, Temp +/- .8F Three Year Warranty WattMaster reserves the right to change specifications without notice Page 1 of 1 Form: AZ2-OE217-04-EBUS-DRS-1D.doc...
  • Page 17 Diffusion Or Flow—through Measurement Range 0 to 2000 ppm 50-100 ml/min 1 ppm Sensitivity Resolution <20 ppm Analog Output 0-5 VDC Communications E-BUS One Year Warranty WattMaster reserves the right to change specifications without notice Page 1 of 1 Form: AZ2-OE256-05—EBUS-CO2Sensor-1C.doc...
  • Page 18 <20 ppm 50 ppm @ 1000 ppm Accuracy Communications E-BUS or 2% measured value One Year Warranty WattMaster reserves the right to change specifications without notice ration box assembly, cutting the tubing to fit. Page 1 of 1 Form: AZ2-OE256-07-E-BUS-DUCT-CO2-01B.doc...
  • Page 19 Hysteresis 0F to 150F  0.05% of full scale Circuit 3 Wire Non-repeatability  1% of full scale Accuracy Weight 3 ounces WattMaster reserves the right to change specifications without notice Eighteen Month Warranty Page 1 of 1 Form: AZ2-OE258-01-BPS-01B.doc...
  • Page 20 1/4” SAE Female Hysteresis Schrader Fitting  0.05% of Full Scale Non-repeatability  0.05% of Full Scale Weight 2.3 Ounces Response Time WattMaster reserves the right to change specifications without notice Three Year Warranty Page 1 of 1 Form: AZ2-OE275-03-A-SuctPressSensorKit-1B.doc...
  • Page 21 UL Listing No. CMP/CL3P/FPLP Conductor Terminations Cable – 2 EBC Connectors Cable Sheath White, Plenum Rated CL3P/CMP Color with “WATTMASTER EBUS” marking every foot. WattMaster reserves the right to change specifications without notice Three Year Warranty Page 1 of 1 Form: AZ2-EBC-XXXF-Cables-1B.doc...
  • Page 22 UL Listing No. CMP/CL3P/FPLP Conductor Terminations Cable – 2 EBC Connectors Cable Sheath White, Plenum Rated CL3P/CMP Color with “WATTMASTER EBUS” marking every foot. WattMaster reserves the right to change specifications without notice Three Year Warranty Page 1 of 1 Form: AZ2-ModularCable-TSDRSC-1B.doc...
  • Page 23 Hub - (4) EBC Connectors Cable Sheath White, Plenum Rated CL3P/CMP Color Cable – 2 EBC Connectors with “WATTMASTER EBUS” marking every foot. WattMaster reserves the right to change specifications without notice Three Year Warranty Page 1 of 1 Form: AZ2-HZ-EBC-248-EBUS-Adapter-1B.doc...
  • Page 24 E-BUS cables between the Sensors, Modules, and the AZ 2 or GPC-XP Controllers. Technical Data MS000248 E-BUS Adapter Hub Terminations Hub - (4) EBC Connectors WattMaster reserves the right to change specifications without notice Three Year Warranty Page 1 of 1 Form: AZ2-MS000248-EBUS-Adapter-1B.doc...

This manual is also suitable for:

Oe231