Current Protection Relay Operating Manual and Installation guide
The Current Protection Relay protects system
from the current faults. Relay protects against
undercurrent, over current and unbalance
faults.
Multiple LEDs indicate type of fault that helps
for diagnosis purpose.
Switch (Key) is provided to enable/ disable
unbalance function and to select automatic /
manual resetting of faults upon fault recovery.
Manual reset ensures safety.
Potential free relay contacts can be used for
connection / disconnection of load or trigger
alarm for annunciation purpose.
relay configuration can be ordered in fail safe
and normal operation depending upon
application The application includes motor
protection, conveyor system and for process
industry, etc.

Installation:

Installation to be carried out by qualified person along
with life protecting equipment to prevent hazardous shock.
Isolate incoming supply before connection.
Do not expose device to Rain, Dust environment.
Keep at least 10-15 mm distance on both sides of device.
Do not install near Vibrating environment.
Do not install near Heat source.
Install Fuses of 2 Amp in series with supply.
Use Sealing provision to protect from unintentional
adjustment.

Dimensions and Terminals:

53.0
2 3
4
5
1
7 8 9
11 12 14 21 22 24
5.7
13.8

Mounting:

To mount the device it should be fastened to a standard 35mm DIN rail
(DIN50022).
To remove from DIN rail use screw driver to pullout clip as shown below.
Mounting On DIN rail

Connector details:

Input connectors are marked by numbers 1, 2, 3, 4, 5, 6 and potential free
relay contacts are marked as 11, 12, 14 for relay1 and 21, 22, 24 for
relay2.Rated switchgear and fusing is required to prevent inrush. Wire of
2 sq. mm with Lug is recommended for Input connection. Use suitable
screw driver so that sufficient force can be applied, excess force may
result in damage to inside circuitry. Control voltage is to be applied with
fusing to the connector numbered as 14, 24. Refer diagrams for input
connection.
60.0 + 0.10
6
Removing From DIN rail

Connection diagram:

L1
L
L
L2
O
L3
A
N
N
D
I3
I1
I2
4
6
1 2 3
5
3Phase
L(+)
AUX
SUPPLY
N(-)

Parameter Settings:

Overcurrent Trip point
Undercurrent Trip point
Hysteresis Undercurrent , Overcurrent 5 - 50 % of trip point
Power on delay
Reset delay
Trip delay
Current unbalance Trip Point
Current unbalance Trip Delay
Current unbalance Hysteresis
Technical Specifications:
Nominal Input current In ( AC )
Maximum continuous Input current (AC) 145 % of In
Current overload withstand
Auxiliary supply range
Auxiliary nominal value
Auxiliary supply frequency
Operating measuring current range
Operating measuring frequency range
Input current burden
Auxiliary supply burden
Operating reference condition
Reference Condition
Input waveform
Input frequency
Auxiliary supply voltage
Auxiliary supply frequency
Accuracy
Measurement accuracy
Setting accuracy
Response time
Applicable Standards
IP for water & dust
Safety
Pollution degree:
Installation category:
High Voltage Test
Environmental
Operating temperature
Storage temperature
Relative humidity
Shock
Vibration
Enclosure

Relay Contacts

Types of output
Relay configuration
Contact Ratings
Mechanical Endurance
Electrical Endurance
Mechanical Attributes
Weight
Dimensions
L
Relay 1
O
COM
A
14
D
I1
NO
NC
1 2
1Phase
12
11
7
8
30 - 140 % of In
10 - 95 % of In
3 Second Approx.
1 Second
0-10 Second (Undercurrent, Overcurrent)
20 % fixed
5 Seconds fixed
5 %
1 to 5 Amps settable
20 x for 1 second, repeated 5 Times in
5 minutes
60-300 V AC/DC
230 VAC 50/60 Hz
45 - 66 Hz
5 to 140 % of nominal value
40...70 Hz
< 0.25 VA per phase at nominal
< 3 VA
23°C +/- 2°C
Sinusoidal (distortion factor 0.005)
50 or 60 Hz + 2%
Nominal value + 1 %
Nominal value + 1%
+ 2 % of nominal value
+ 6 % of nominal value
+ 0.8 second for trip delay
< 140 milisecond
IEC60529
IEC 61010-1-2010 Permanently
connected use.
2
CAT III
2.2 kV AC, 50Hz for 1 minute between
all electrical circuits
-10 to +55°C
-25 to +70°C
0...90% non condensing
15g in 3 planes
10...55 Hz, 0.15mm amplitude
Flame retardant, IP20 (front face only)
1CO, 1CO+1CO
Energised or DeEnergised
(Energised-Relay is ON under healthy
condition and DeEnergised-Relay is
OFF under healthy condition)
5A/250VAC/30VDC (resistive load)
1x10^7 OPS
1x10^5 OPS
175g Approx.
53 x 110 x 60 mm
Relay 2
COM
24
NO
NC
22
21

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Current Protection Relay and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Rishabh Current Protection Relay

  • Page 1 Current Protection Relay Operating Manual and Installation guide The Current Protection Relay protects system Connection diagram: from the current faults. Relay protects against Relay 1 Relay 2 undercurrent, over current and unbalance faults. Multiple LEDs indicate type of fault that helps for diagnosis purpose.
  • Page 2 Accuracy Test : Pass Adjustment Test : Pass Tripping Test : Pass Rishabh Instruments PVT. LTD. Trishala Unit , C-6 , NICE Area , MIDC Satpur,Nasik-422007 , India Tel : +912532202371/028 Fax:+912532351064 , Email : marketing@rishabh.co.in , www.rishabh.co.in DMAN-00IM-0754 Rev.B 10/2019...

Table of Contents