Temperature Monitoring
Installa on of the BriteSpot Fiber-Op c Temperature Sensor has been engineered to be simple and straigh orward. The
following manual will describe in detail the 3 steps needed for installa on. No specialized knowledge of fiber op cs is
necessary. A basic understanding of switchgear topology and moun ng methods is required.
Required for Installa on
Tools for Fiber Moun ng:
Adjustable Wrench
1.5 mm Allen Key
Guillo ne Cu er
1- Moun ng Fixture and Op cal Fiber Installa on
A - Secure the Moun ng Fixture to Busbar and Connect Fiber
I. Insert the screw with the washer through the
fixture and busbar.
B - Route the Fiber to Low-Voltage Cabinet
!
Do NOT bend fiber ghter
than 12 mm (1/2") radius
Keep away from sources of
excessive heat whenever
possible. Fiber probe shall not
be a ached to surfaces with
te m p e rat u re s exc e e d i n g
100ºC or 200ºF.
Fiber
- MAX 100ºC
Sensor Tip - MAX 120ºC
Powell Canada Inc,
Suite 201, 55 Gos ck Place
North Vancouver, BC, V7M 3N2
Components for Hardware Installa on:
35 mm DIN rail (6"-8") and moun ng
hardware
CAT5 Ethernet cable (if connec ng to SCADA or
computer.
II. Insert the washers and secure it with a nut.
Ensure the hole for fiber inser on is pointed in
the direc on of the fiber rou ng.
R
!
Quick Start Guide
III. Insert fiber into the holding fixture and secure it
Do not fasten or a ach ANY
moun ng hardware ( e-wraps,
etc.) to at least a 30 cm (12")
length of fiber between the
por on of the probe at high
v o l t a g e a n d i t s fi r s t n o n -
energized point of contact.
Power Supply Requirements:
Voltage: 12-24 VDC (0.12A@24VDC)
Power: 3 Wa s (Max)
with a 1.5 mm hex screwdriver.
Avo i d r u n n i n g fi b e rs I n t h e
direc on of the fold of the boot to
!
minimize bending and damage of
the fiber.

Advertisement

loading
Need help?

Need help?

Do you have a question about the BriteSpot Fiber-Opc and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Powell BriteSpot Fiber-Opc

  • Page 1 100ºC or 200ºF. Fiber - MAX 100ºC Sensor Tip - MAX 120ºC Powell Canada Inc, Suite 201, 55 Gos ck Place North Vancouver, BC, V7M 3N2...
  • Page 2 Star Topology (Ethernet) Typical Serial Topology (MODBUS RTU) BriteSpot ID#: STAT BriteSpot BriteSpot ID#: ID#: STAT STAT BriteSpot ID#: STAT HMI/Master G3 Slave Device 1-31 G3 Slave Devices Powell Canada Inc, Suite 201, 55 Gos ck Place North Vancouver, BC, V7M 3N2...
  • Page 3 Keep the bu on depressed un l both the "SYS" and "COM" LEDs stay green (about 5 seconds). II. Release the bu on and the device will restart with its default values. Powell Canada Inc, Suite 201, 55 Gos ck Place North Vancouver, BC, V7M 3N2...
  • Page 4 MOD PORT: MOD PORT: MOD PORT: LOG RATE: 1 MIN LOG RATE: 1 MIN LOG RATE: 1 MIN DEGREE: DEGREE: DEGREE: BAUD: 19200 BAUD: 19200 BAUD: 19200 Powell Canada Inc, Suite 201, 55 Gos ck Place North Vancouver, BC, V7M 3N2...