Klimor MCKT-HPX Documentation

Automatic control for compact ventilation unit mckt-hpx

Advertisement

Quick Links

DOCUMENTATION OF AUTOMATIC CONTROL
DTR.MCKT-HPX.
PAGE
FOR COMPACT UNITS
AUT-009.5.0
MCKT-HPX
2016
GDYNIA
1/35
DOCUMENTATION OF AUTOMATIC
CONTROL FOR COMPACT VENTILATION
UNIT MCKT-HPX
SERVICE
Tel.: (+48 58) 783 99 50/51
Fax: (+48 58) 783 98 88
Mobile: (+48) 510 098 081
Email: serwis@klimor.pl
November 2016
Information provided in this document is subject to change
KLIMOR Spółka z ograniczoną odpowiedzialnością, 81-035 Gdynia, ul. B. Krzywoustego 5
Fax: (+48 58) 783-98-88; Tel.: (+48 58) 783-99-99
email:
klimor@klimor.pl
– Office
Service – Fax: (+48 58) 783-98-88; Tel.: (+48 58) 783-99-50/51 Mobile: (+48) 510 098 081
serwis@klimor.pl
– Service

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MCKT-HPX and is the answer not in the manual?

Questions and answers

Summary of Contents for Klimor MCKT-HPX

  • Page 1 Mobile: (+48) 510 098 081 Email: serwis@klimor.pl November 2016 Information provided in this document is subject to change KLIMOR Spółka z ograniczoną odpowiedzialnością, 81-035 Gdynia, ul. B. Krzywoustego 5 Fax: (+48 58) 783-98-88; Tel.: (+48 58) 783-99-99 email: klimor@klimor.pl – Office Service –...
  • Page 2: Table Of Contents

    COMMUNICATION ............................. 3 SUPPORTED DEVICES ............................. 3 FANS .................................. 3 2.1.1 RPM ADJUSTMENT OF MCKT-HPX 1 AND MCKT-HPX 2 FAN MOTORS ............3 2.1.2 RPM ADJUSTMENT OF MCKT-HPX 3 FAN MOTORS ..................3 HEAT EXCHANGER ............................5 HEAT PUMP ............................... 5 FILTERS ................................
  • Page 3: Introduction

    Application of EC motors in MCKT-HPX 1 and MCKT-HPX 2 as well as AC motors controlled with inverters in MCKT-HPX3 also enables stepless adjustment of fan RPM in entire control range.
  • Page 4 2016 GDYNIA 4/35 Picture 1 Inverter control panel for the MCKT-HPX 3 Picture 2 Description of inverter control panel for the MCKT-HPX 3 Use the [Menu] key to select one of the following menus: Status For readouts only. Operation Keys...
  • Page 5: Heat Exchanger

    - Read out of low pressure gauge alert - Controlling the compressor casing heater The MCKT-HPX AHU can be equipped with the preliminary electric heater (optional), which heats up fresh air and ensures correct operation of the heat pump at low external temperatures (below -5°C).
  • Page 6: Control Panel

    (1st pair: +12V, G0; 2nd pair: A, B). Picture 5 Panel diameters Information provided in this document is subject to change KLIMOR Spółka z ograniczoną odpowiedzialnością, 81-035 Gdynia, ul. B. Krzywoustego 5 Fax: (+48 58) 783-98-88; Tel.: (+48 58) 783-99-99 email: klimor@klimor.pl...
  • Page 7: Control Panel User Guide

    1. The MCKT-HPX AHU is supplied with factory settings of individual parameters provided to the controller. 2. The user has to configure the system according to conditions in a facility where the MCKT-HPX is installed. 3. Changing most of the parameters entered by an user requires the password.
  • Page 8: Operation Of The Control Panel

    [Tzad] – currently requested temperature – this parameter can be edited in manual mode only Information provided in this document is subject to change KLIMOR Spółka z ograniczoną odpowiedzialnością, 81-035 Gdynia, ul. B. Krzywoustego 5 Fax: (+48 58) 783-98-88; Tel.: (+48 58) 783-99-99 email: klimor@klimor.pl...
  • Page 9: Main Screen

    [Rs] – info about the master (reference) sensor selected for control Information provided in this document is subject to change KLIMOR Spółka z ograniczoną odpowiedzialnością, 81-035 Gdynia, ul. B. Krzywoustego 5 Fax: (+48 58) 783-98-88; Tel.: (+48 58) 783-99-99 email: klimor@klimor.pl...
  • Page 10: Main Menu

    {2d} – settings for SA–SU of the 2d+5d schedule {7d} – settings for MO–SU of the 7d schedule Information provided in this document is subject to change KLIMOR Spółka z ograniczoną odpowiedzialnością, 81-035 Gdynia, ul. B. Krzywoustego 5 Fax: (+48 58) 783-98-88; Tel.: (+48 58) 783-99-99 email: klimor@klimor.pl...
  • Page 11 [To] – current air temperature downstream of the heat recovery at the air exhauster Information provided in this document is subject to change KLIMOR Spółka z ograniczoną odpowiedzialnością, 81-035 Gdynia, ul. B. Krzywoustego 5 Fax: (+48 58) 783-98-88; Tel.: (+48 58) 783-99-99 email: klimor@klimor.pl...
  • Page 12 {DO4} – relay 4 (OUTPUT4) – heat pump compressor {DO5} – relay 5 (OUTPUT5) – solenoid valve 2 Information provided in this document is subject to change KLIMOR Spółka z ograniczoną odpowiedzialnością, 81-035 Gdynia, ul. B. Krzywoustego 5 Fax: (+48 58) 783-98-88; Tel.: (+48 58) 783-99-99 email: klimor@klimor.pl...
  • Page 13 [CTzEn] – external temperature below which the heat pump with cooling function does not receive permission to operate Information provided in this document is subject to change KLIMOR Spółka z ograniczoną odpowiedzialnością, 81-035 Gdynia, ul. B. Krzywoustego 5 Fax: (+48 58) 783-98-88; Tel.: (+48 58) 783-99-99 email: klimor@klimor.pl...
  • Page 14 [Sound] – activation of the panel speaker {YES} – speaker ON {NO} – speaker OFF Information provided in this document is subject to change KLIMOR Spółka z ograniczoną odpowiedzialnością, 81-035 Gdynia, ul. B. Krzywoustego 5 Fax: (+48 58) 783-98-88; Tel.: (+48 58) 783-99-99 email: klimor@klimor.pl –...
  • Page 15 [DI0f]:[DI6f] – selecting alarm message displayed for the digital input’s signal: {DIN} – digital input, no message Information provided in this document is subject to change KLIMOR Spółka z ograniczoną odpowiedzialnością, 81-035 Gdynia, ul. B. Krzywoustego 5 Fax: (+48 58) 783-98-88; Tel.: (+48 58) 783-99-99 email: klimor@klimor.pl...
  • Page 16 [Ti3] – integration constant [1/Kp3] – reinforcement converse Heat recovery Information provided in this document is subject to change KLIMOR Spółka z ograniczoną odpowiedzialnością, 81-035 Gdynia, ul. B. Krzywoustego 5 Fax: (+48 58) 783-98-88; Tel.: (+48 58) 783-99-99 email: klimor@klimor.pl –...
  • Page 17 [TRS2on] – 4d valve opening time once the operation is finished, to compensate the system pressures Information provided in this document is subject to change KLIMOR Spółka z ograniczoną odpowiedzialnością, 81-035 Gdynia, ul. B. Krzywoustego 5 Fax: (+48 58) 783-98-88; Tel.: (+48 58) 783-99-99 email: klimor@klimor.pl...
  • Page 18 {LoP} – low pressure signal of heat pump compressor {HiP} – high pressure signal of heat pump compressor Information provided in this document is subject to change KLIMOR Spółka z ograniczoną odpowiedzialnością, 81-035 Gdynia, ul. B. Krzywoustego 5 Fax: (+48 58) 783-98-88; Tel.: (+48 58) 783-99-99 email: klimor@klimor.pl...
  • Page 19: Wiring Diagrams

    Dimensions of the control cabinet for MCKT-HPX (the same for all sizes): L×H×B - 380×300×120 mm Wiring diagrams present STANDARD (right) version of the MCKT-HPX. In non-standard version (left) of the MCKT-HPX, the 4-WAY VALVE is connected to the “NC” connector of the “OUTPUT 2” relay.
  • Page 20 GDYNIA 20/35 Picture 8.1 MCKT-HPX 1 wiring diagram Information provided in this document is subject to change KLIMOR Spółka z ograniczoną odpowiedzialnością, 81-035 Gdynia, ul. B. Krzywoustego 5 Fax: (+48 58) 783-98-88; Tel.: (+48 58) 783-99-99 email: klimor@klimor.pl – Office Service –...
  • Page 21 GDYNIA 21/35 Picture 8.2 MCKT-HPX 1 wiring diagram Information provided in this document is subject to change KLIMOR Spółka z ograniczoną odpowiedzialnością, 81-035 Gdynia, ul. B. Krzywoustego 5 Fax: (+48 58) 783-98-88; Tel.: (+48 58) 783-99-99 email: klimor@klimor.pl – Office Service –...
  • Page 22 GDYNIA 22/35 Picture 9.1 MCKT-HPX 2 wiring diagram Information provided in this document is subject to change KLIMOR Spółka z ograniczoną odpowiedzialnością, 81-035 Gdynia, ul. B. Krzywoustego 5 Fax: (+48 58) 783-98-88; Tel.: (+48 58) 783-99-99 email: klimor@klimor.pl – Office Service –...
  • Page 23 GDYNIA 23/35 Picture 9.2 MCKT-HPX 2 wiring diagram Information provided in this document is subject to change KLIMOR Spółka z ograniczoną odpowiedzialnością, 81-035 Gdynia, ul. B. Krzywoustego 5 Fax: (+48 58) 783-98-88; Tel.: (+48 58) 783-99-99 email: klimor@klimor.pl – Office Service –...
  • Page 24 GDYNIA 24/35 Picture 10.1 MCKT-HPX 3 wiring diagram Information provided in this document is subject to change KLIMOR Spółka z ograniczoną odpowiedzialnością, 81-035 Gdynia, ul. B. Krzywoustego 5 Fax: (+48 58) 783-98-88; Tel.: (+48 58) 783-99-99 email: klimor@klimor.pl – Office Service –...
  • Page 25 GDYNIA 25/35 Picture 10.2 MCKT-HPX 3 wiring diagram Information provided in this document is subject to change KLIMOR Spółka z ograniczoną odpowiedzialnością, 81-035 Gdynia, ul. B. Krzywoustego 5 Fax: (+48 58) 783-98-88; Tel.: (+48 58) 783-99-99 email: klimor@klimor.pl – Office Service –...
  • Page 26 GDYNIA 26/35 Picture 10.3 MCKT-HPX 3 wiring diagram Information provided in this document is subject to change KLIMOR Spółka z ograniczoną odpowiedzialnością, 81-035 Gdynia, ul. B. Krzywoustego 5 Fax: (+48 58) 783-98-88; Tel.: (+48 58) 783-99-99 email: klimor@klimor.pl – Office Service –...
  • Page 27: Danfoss Fc 51 Inverters For Mckt-Hpx 3

    The User Manual of the FC 51 inverter and the full programming manual can be found at the manufacturer's website: http://www.danfoss.com/Poland/BusinessAreas/DrivesSolutions/frequency+converters/VLT+Micro+Drive.htm Information provided in this document is subject to change KLIMOR Spółka z ograniczoną odpowiedzialnością, 81-035 Gdynia, ul. B. Krzywoustego 5 Fax: (+48 58) 783-98-88; Tel.: (+48 58) 783-99-99 email: klimor@klimor.pl...
  • Page 28: Bms Variable List - Rtu Modbus Protocol

    TSET LSB: Requested temperature set via COM2 Read only Information provided in this document is subject to change KLIMOR Spółka z ograniczoną odpowiedzialnością, 81-035 Gdynia, ul. B. Krzywoustego 5 Fax: (+48 58) 783-98-88; Tel.: (+48 58) 783-99-99 email: klimor@klimor.pl – Office Service –...
  • Page 29 LSB: Heat exchanger efficiency calculated according to the formula Read only (Tn-Tz)/(Tw-Tz) * 100% [%], {0-99%} Information provided in this document is subject to change KLIMOR Spółka z ograniczoną odpowiedzialnością, 81-035 Gdynia, ul. B. Krzywoustego 5 Fax: (+48 58) 783-98-88; Tel.: (+48 58) 783-99-99 email: klimor@klimor.pl –...
  • Page 30 BMS/Readout SUPPLY_ level MANUAL Information provided in this document is subject to change KLIMOR Spółka z ograniczoną odpowiedzialnością, 81-035 Gdynia, ul. B. Krzywoustego 5 Fax: (+48 58) 783-98-88; Tel.: (+48 58) 783-99-99 email: klimor@klimor.pl – Office Service – Fax: (+48 58) 783-98-88; Tel.: (+48 58) 783-99-50/51 Mobile: (+48) 510 098 081 serwis@klimor.pl...
  • Page 31 LSB: Lower limit of air supply temperature (adjustment against Read only Tn2) [°C], {0÷50} Information provided in this document is subject to change KLIMOR Spółka z ograniczoną odpowiedzialnością, 81-035 Gdynia, ul. B. Krzywoustego 5 Fax: (+48 58) 783-98-88; Tel.: (+48 58) 783-99-99 email: klimor@klimor.pl –...
  • Page 32 Note4: Reading registers starting from the 40030 address is possible from firmware ver. 2.10 (0x2A). Device addressing Device addressing is carried out using the S1MX dip-switch located on the MCKT-HPX control PCB. Address 0 - reserved The address is set by switching on individual bits of the binary word.
  • Page 33: Control Modules Of Preliminary Electric Heaters

    1 separate temperature sensor with 3m cable 10.2 Cooperation of the preliminary heater control module with the MCKT-HPX control system During on-site installation – switch the “TZ” temperature sensor at the MCKT-HPX control PCB from the current position into the “TN” terminals.
  • Page 34 Picture 11 Wiring diagram of the 230V electric heater control cabinet for MCKT-HPX1 Information provided in this document is subject to change KLIMOR Spółka z ograniczoną odpowiedzialnością, 81-035 Gdynia, ul. B. Krzywoustego 5 Fax: (+48 58) 783-98-88; Tel.: (+48 58) 783-99-99 email: klimor@klimor.pl...
  • Page 35 2016 GDYNIA 35/35 Picture 12 Wiring diagram of the 3x400V electric heater control cabinet for MCKT-HPX2 and MCKT-HPX 3 Information provided in this document is subject to change KLIMOR Spółka z ograniczoną odpowiedzialnością, 81-035 Gdynia, ul. B. Krzywoustego 5 Fax: (+48 58) 783-98-88; Tel.: (+48 58) 783-99-99 email: klimor@klimor.pl...