• Before using this product read and understand instructions.
• Save these instructions for future reference.
• All work must be performed by qualified personnel trained in the proper application,
installation, and maintenance of plumbing, steam, and electrical and/or systems in
accordance with all applicable codes and ordinances.
• To prevent serious burns, the boiler must be cooled to 80°F (27°C) and the pressur emust be
0 psi (0 bar) before servicing.
• To prevent electrical shock, turn off the electrical power before making electrical
connections.
• This low water cut-off must be installed in series with all other limit and operating controls
installed on the boiler. After installation, check for proper operation of all of the limit and
operating controls, before leaving the site.
• We recommend that secondary (redundant) Low Water Cut-Off controls be installed on all
steam boilers with heat input greater than 400,000 BTU/hour or operating above 15 psi
of steam pressure. At least two controls should be connected in series with the burner control
circuit to provide safety redundancy protection should the boiler experience a low water
condition. Moreover, at each annual outage, the low water cut-offs should be
dismantled, inspected, cleaned, and checked for proper calibration and performance.
• Boiler manufacturer schematics should always be followed. In the event that the boiler
manufacturer's schematic does not exist, or is not available from the boiler manufacturer, refer
to the schematics provided in this document.
• To prevent a fire, do not use this low water cut-off to switch currents over 10.2A, 1/2 HP at
120 VAC or 5.1A, 1/2 HP at 240 VAC, unless a starter or relay is used in conjunction with it.
• This product can expose you to chemicals including Lead and Hexavalent Chromiun, which are
known to the State of California to cause cancer and birth defects or other reproductive harm.
For more information go to: www.P65Warnings.ca.gov.
INSTRUCTION MANUAL
MM-315H
210424

Advertisement

loading

Summary of Contents for Xylem McDonnell & Miller 51 Series

  • Page 1 INSTRUCTION MANUAL MM-315H 210424 • Before using this product read and understand instructions. • Save these instructions for future reference. • All work must be performed by qualified personnel trained in the proper application, installation, and maintenance of plumbing, steam, and electrical and/or systems in accordance with all applicable codes and ordinances. • To prevent serious burns, the boiler must be cooled to 80°F (27°C) and the pressur emust be 0 psi (0 bar) before servicing. • To prevent electrical shock, turn off the electrical power before making electrical connections. • This low water cut-off must be installed in series with all other limit and operating controls installed on the boiler. After installation, check for proper operation of all of the limit and operating controls, before leaving the site.
  • Page 2: Installation

    • California Proposition 65 warning! This product contains chemicals known to the state of California to cause cancer and birth defects or other reproductive harm. • Previous controls should never be installed on a new system. Always install new controls on a new boiler or system. Failure to follow this warning could cause property damage, personal injury or death.
  • Page 3 STEP 2 - Installation of the Models 51/51-2, 51-S/51-S-2 and 53/53-2 a. Using the criteria in Step 1, Figure 1 determine the location of the Gauge Glass Mounted in the Boiler 51/51-2, 51-S/51-S-2 or 53/53-2. This applies when the gauge 1"...
  • Page 4 INSTRUCTIONS FOR PIPING THE WATER FEEDER VALVE Models 51 / 51-2, Models 51-S / 51-S-2 and Models 53 / 53-2 For Steam or Hot Water Boilers TOOLS NEEDED: Two (2) pipe wrenches. STEP 1 - Piping the Valve on Models 51/51-2 a.
  • Page 5: Electrical Wiring

    ELECTRICAL WIRING Models 51-2, 51-S-2 and 53-2 TOOLS NEEDED: One (1) flathead screwdriver. WARNING • To prevent electrical shock, turn off the electrical power before making electrical connections. • This low water cut-off must be installed in series with all other limit and operating controls installed on the boiler.
  • Page 8 Xylem Inc. 8200 N. Austin Avenue Morton Grove, Illinois 60053 Phone: (847) 966-3700 Fax: (847) 965-8379 www.xylem.com/mcdonnellmiller McDonnell & Miller is a trademark of Xylem Inc. or one of its subsidiaries. © 2019 Xylem Inc. MM-315H March 2019 Part No. 210424...

This manual is also suitable for:

Mcdonnell & miller 51-2 seriesMcdonnell & miller 53 seriesMcdonnell & miller 53-2 seriesMcdonnell & miller 51-s seriesMcdonnell & miller 51-s-2 series