Download Print this page

Installation; Tools Needed - Xylem McDonnell & Miller 51 Series Instruction Manual

Advertisement

California Proposition 65 warning! This product contains chemicals known to the
state of California to cause cancer and birth defects or other reproductive harm.
Previous controls should never be installed on a new system. Always install new
controls on a new boiler or system.
Failure to follow this warning could cause property damage, personal injury or death.
CAUTION:
A more frequent replacement interval may be necessary based on the condition of
the unit at time of inspection. McDonnell & Miller's warranty is one (1) year from date
of installation or two (2) years from the date of manufacture.
INSTALLATION –
Models 51 / 51-2, Models 51-S / 51-S-2 and Models 53 / 53-2 –
For Steam Boilers with 1" (25mm) Equalizing Lines

TOOLS NEEDED:

One (1) flathead screwdriver and two (2) pipe wrenches.
STEP 1 - Determine the Location of the Feeder and/or Low Water Cut-Off
Determine which situation applies:
a. For models 51-2, 51-S-2 or 53-2 on steam boilers:
Always set the control to shut off the burner while
there is water visible in the gauge glass. This applies
when the gauge glass is directly mounted in the boiler
or on a water column.
b. For models 51, 51-S or 53 on steam boilers:
Set the line on the casting 3
manufacturer's normal water level.
c. For all models on steam process boilers when no
condensate is returned to the boiler: Set the line
on the casting 1
/
1
normal water level.
Series 51 and 53 Operating Level
2
/
" below the boiler
1
8
" below the boiler manufacturer's
8
Casting
Line
Operating Levels of 51/51-2,
51-S/51-S-2 or 53/53-2
Drip tight valve off – 1
Casting line
Burner on
Burner off
1
Valve Off -1
/
"
8
Casting Line - 0"
Burner On -
1
/
" (±
1
/
")
8
4
7
1
Burner Off -
/
" (±
/
")
8
4
/
"
1
8
– 0"
/
" (±
/
")
1
1
8
4
/
" (±
/
")
7
1
8
4

Advertisement

loading

This manual is also suitable for:

Mcdonnell & miller 51-2 seriesMcdonnell & miller 53 seriesMcdonnell & miller 53-2 seriesMcdonnell & miller 51-s seriesMcdonnell & miller 51-s-2 series