Advertisement

KSUA
Control panel
Valid from week of manufacture 50/2011 and
software version 2.8
Description
The KSUA is a control and monitoring unit
designed to control various types of fire/smoke
dampers and fans in a flexible way. This unit
is a master unit. Up to 32 slave units can be
connected to the KSUA. Each slave can
operate two damper groups, each with a
maximum of two dampers and two smoke
detector groups. These units can be grouped in
any way in up to 64 fire zones. Each damper
group and detector group can be monitored
individually. A central fire alarm system can
be connected using the KSUC, which has a
maximum capacity of 16+16 fire zones. The
KSUA can also be used to connect ventilation
systems, smoke evacuation fans and heater
batteries. These units are then controlled in an
intelligent way depending on their function.
The KSUA has additional inputs for an
external fire alarm, forced opening, night
mode, etc. The KSUA also has a standardised
input for connecting a Modbus network
monitoring all dampers, smoke detectors and
other devices.
General
• Master for KSUB and other slave units
• 32 slave units. Less with KSUE and KSUF.
• 64 damper groups
• 64 detector groups
• Separate KSUC unit for connecting a fire
alarm system
• Separate alarm inputs for isolating switches
in smoke extraction fans (for example)
• 2 fan groups
• 6 distributed relay outputs
• Real time clock with battery backup
• External input for central fire alarm system
___________________________________________________________________
• Night mode input
• Forced opening input
• Evacuation dampers (pressure relief) can be
configured in any way in the system
• Damper position indication
• Error logging
• Integrated troubleshooting program
• 8 Time Channels
• Compact plastic case
• Integrated transformer
• Programming using modern techniques
(knob with pushbutton)
• Easy to back up the configuration
• Serial Modbus RTU is standard, TCP/IP
Modbus is option.
• And more
Maximum configuration
The system can handle a total of 64 damper
groups with a maximum of 128 dampers and
64 detector inputs. In principle, an unlimited
number of smoke detectors can be connected.
These smoke detector inputs and fire dampers
can then be grouped into a maximum of 64 fire
zones. 16+16 fire zones come from the KSUC.
There are up to two outputs for fan control.
Using the KSUC, a further 6 outputs are
available. These outputs can be configured for
ventilation fans, smoke extraction fans,
various alarms or heater batteries. Custom
delays, etc. can be selected for each of the
options.
17/11/2017
Page
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the KSUA and is the answer not in the manual?

Questions and answers

Summary of Contents for Control KSUA

  • Page 1 • Integrated transformer • Programming using modern techniques Description (knob with pushbutton) The KSUA is a control and monitoring unit • Easy to back up the configuration designed to control various types of fire/smoke • Serial Modbus RTU is standard, TCP/IP dampers and fans in a flexible way.
  • Page 2: Installation

    • Assembly kit for rack installation • Forced opening • Night mode Outputs • Alarm (external control unit). Opening the • Sum alarm. Voltage-free changeover circuit has the same effect as a triggered contact 1A max 60VA. Terminal numbers smoke detector (the system switches to 16,17,18.
  • Page 3 Modbus menu is used to configure the address the system is symmetrical, twisted pair cable (the KSUA is always a slave). In the case of should be used to minimise the risk of SBus, the KSUA is the master and the KSUB transients.
  • Page 4: Connection Terminals

    Must be connected via fixed cables to a group Smoke fuse of at least 2A. The isolating switch must Detectors be positioned close to the unit. The KSUA is 1-96e Dampers built with reinforced insulation, so no ground 1-64 is necessary.
  • Page 5: Night Mode

    In menu 19 it could be changed to automatic reset. The KSUB fan relay output is dependent on the Relay 1 configuration in the KSUA. If you Night mode want the fans connected via the KSUB to stay on during the damper exercises until the...
  • Page 6: Fire Dampers

    There is a fuse holder on the bottom right-hand side. The Used to control the air handling system. 19-21 holder is the bayonet type. To remove the fuse, is normally closed. The delay can be adjusted press the holder down and twist anticlockwise.
  • Page 7: Menu System

    Move to next menu by pushing the knob Direct selection by pushing the knob. Flashes when a SBus message is received Some of the menus are described below. Many items are self-explanatory so no special Friday |KSUA V2.8 description is needed. 12-01-03 |Status:OK 08:42:29 |Day mode...
  • Page 8 Press any of the buttons to show the main menu from standby mode. A short summary of the system status appears in standby mode. Errors or anything else of interest appear in summary. MAIN MENU All outputs and inputs in the KSUA can be ►Log viewed in real time. SlvDay is a day mode Alarm Reset request from a slave.
  • Page 9 in sequence. If they are exercised in sequence, There are eight time channels. Each damper each damper is closed and opened fully before can belong to a time channel or none at all. In the next damper is exercised. If Modbus is the example above is damper 1 and 3 used for the exercise, the interval should be set connected to time channel 6.
  • Page 10 Ext. Fire is to be used if input 9-10 can be connected to the four different relays in should control relay 2. If you select VENT the KSUA. Menus 18 to 23 are used to change FAN, relay 2 completely follows relay 1. the settings.
  • Page 11: Troubleshooting

    Menu 6. You can see from this menu whether Normally, the system is set to critical state on the KSUA went into a specific state because of a communication error. If this is not desirable, an external system. It can take a lot of work to it can be disabled in this menu to delete the find out what exactly caused the problem.
  • Page 12 Disposal of old Electrical & Electronic Equipment (Applicable throughout the European Union and other European countries with separate collection programs) This symbol, found on your product or on it’s packaging, indicates that this product should not be treated as household waste when you wish to dispose of it.