United Technologies Carrier OPN-VAVB1 Installation And Startup Manual

Vav zone controllers
Table of Contents

Advertisement

V
A
V
Z
o
n
e
V
A
V
Z
o
n
e
I
n
s
t
a
l
l
a
I
n
s
t
a
l
l
a
CARRIER CORPORATION ©2013
A member of the United Technologies Corporation family · Stock symbol UTX · Catalog No. 11-808-432-01 · 9/10/2013
C
o
n
t
r
o
l
l
e
r
C
o
n
t
r
o
l
l
e
r
t
i
o
n
a
n
d
S
t
i
o
n
a
n
d
S
s
s
t
a
r
t
-
u
p
G
u
t
a
r
t
-
u
p
G
u
i
d
e
i
d
e

Advertisement

Table of Contents
loading

Summary of Contents for United Technologies Carrier OPN-VAVB1

  • Page 1 CARRIER CORPORATION ©2013 A member of the United Technologies Corporation family · Stock symbol UTX · Catalog No. 11-808-432-01 · 9/10/2013...
  • Page 3: Table Of Contents

    Table of Contents Introduction .................................. 1 What are VAV Zone Controllers? ........................1 Linkage ................................... 4 Specifications ................................ 5 Safety Considerations ............................8 Installation ................................... 9 Field-supplied hardware ............................9 Mounting the VAV Zone Controller ........................10 To mount the controller ........................10 Wiring the VAV Zone Controller for power .....................
  • Page 4 Table of Contents Combination heat (ducted electric heat with modulating baseboard heat) - Fan box application. 32 2-stage electric heat (ducted or baseboard) - Fan box application ..........33 SCR electric heat (ducted or baseboard) - Single duct application ..........33 Wiring a field-supplied high-torque actuator to the analog output ...........
  • Page 5: Introduction

    Introduction What are VAV Zone Controllers? An i-Vu® Open Control System offers 2 VAV Zone Controllers, the VAV Zone Single Duct controller (#OPN-VAVB1) and the VAV Zone Fan Terminal controller (#OPN-VAVB3), to control zone temperature using single duct or fan powered terminals in a Variable Air Volume (VAV ®...
  • Page 6 Introduction VAV Zone Single Duct controller (#OPN-VAVB1) Enclosed Energy Management Equipment High (with filter) 88FO E143900 Flow TYPE: 002101 CAUTION: To ReduceThe Risk of Fire or Electric Shock, Do Not Interconnect the Outputs of Different Class 2 Circuits. CAUTION: Rnet This product was designed to be mounted inside the building envelope.
  • Page 7 Introduction VAV Zone Fan Terminal controller (#OPN-VAVB3) Enclosed Energy Management Equipment High (with filter) 88FO E143900 Flow TYPE: 002101 CAUTION: To ReduceThe Risk of Fire or Electric Shock, Do Not Interconnect the Outputs of Different Class 2 Circuits. CAUTION: Rnet This product was designed to be mounted inside the building envelope.
  • Page 8: Linkage

    Introduction Linkage The i-Vu Open Control System uses linkage to exchange data between the zone terminals and their air source to form a coordinated HVAC system. The system's air source controller and zone controllers are linked so that their data exchange can be managed by one zone controller configured as the VAV Master. A VAV Master can have a maximum of 63 slave zone controllers reporting to it.
  • Page 9: Specifications

    Introduction Network #: 16115 Network #: 16117 Network #: Network #: 16113 16116 Address Network #: 16130 Slaves Sub- Sub- Master Master Master You set up linkage for the system by defining the Linkage properties for each controller. See Linkage Properties (page 68).
  • Page 10 Introduction Inputs 4 inputs for connecting the following types of sensors: • An alternate space temperature sensor (#33ZCT55SPT) • Supply air temperature sensor (#33ZCSENSAT) • Duct air temperature sensor (#33ZCSENDAT) • CO2 sensor (#33ZCSENCO2) • Relative humidity sensor (#33ZCSENSRH-02 [indoor space] or 33ZCSENDRH-02 [duct]) •...
  • Page 11 Introduction Overall dimensions 7 in. (17.8 cm) 6-1/32 (15.4 cm) 6 in. (15.24 cm) Mounting dimensions 5-5/8 in. (14.3 cm) 4-9/16 in. (24.3 cm) 1-5/16 in. (3.3 cm.) 7/8 in. (2.2 cm) 1-5/16 in. (3.3 cm) Panel depth 2-1/2 in. (6.4 cm) minimum Shaft dimensions Minimum shaft diameter: 3/8 in.
  • Page 12: Safety Considerations

    Introduction Safety Considerations SAFETY NOTE Air conditioning equipment will provide safe and reliable service when operated within design specifications. The equipment should be operated and serviced only by authorized personnel who have a thorough knowledge of system operation, safety devices, and emergency procedures. Good judgment should be used in applying any manufacturer's instructions to avoid injury to personnel or damage to equipment and property.
  • Page 13: Installation

    Installation Installation To install the VAV Zone Controller: Mount the controller to the VAV terminal. (page 10) Wire the controller for power. (page 12) Set the controller's address. (page 13) Wire the controller to the MS/TP network. (page 14) Wire sensor(s) to the controller. (page 15) Wire equipment to the controller's outputs.
  • Page 14: Mounting The Vav Zone Controller

    Installation Mounting the VAV Zone Controller Mount the VAV Zone Controller on the zone terminal’s damper actuator shaft. For service access, allow at least 1 foot (.3 m) of clearance between the front of the controller and adjacent surfaces. Allow 1 ft. (.3 m) clearance for service access 2.5 in.
  • Page 15 Installation 5/8-in. nuts Damper release button Release the button. Tighten the actuator clamp to the damper shaft by tightening the two 5/16 inch nuts. Hold down the damper release button and rotate the damper from fully closed to fully open. If the damper traveled less than 90 degrees, do the following to set the actuator's fully open position: Loosen the appropriate stop clamp screw.
  • Page 16: Wiring The Vav Zone Controller For Power

    Installation High High 13 Replace the controller’s cover. Wiring the VAV Zone Controller for power The VAV Zone Controller is powered by a Class 2 power source. Take appropriate isolation measures when mounting it in a control panel where non-Class 2 circuits are present. Carrier controllers can share a power supply as long as you: •...
  • Page 17: To Address The Vav Zone Controller

    Installation Verify that the Power LED is on and the Run LED is blinking. To address the VAV Zone Controller You must give the VAV Zone Controller an address that is unique on the network. You can address the VAV Zone Controller before or after you wire it for power.
  • Page 18: Wiring The Vav Zone Controller To The Ms/Tp Network

    Installation Wiring the VAV Zone Controller to the MS/TP network The VAV Zone Controller communicates using BACnet on an MS/TP network segment communications at 9600 bps, 19.2 kbps, 38.4 kbps, or 76.8 kbps. Wire the controllers on an MS/TP network segment in a daisy-chain configuration. Install a BT485 on the first and last controller on a network segment to add bias and prevent signal distortions due to echoing.
  • Page 19: Wiring Sensors To Inputs

    Installation Insert the power screw terminal connector into the VAV Zone Controller's power terminals. Verify communication with the network by viewing a module status report. Wiring sensors to inputs You can wire the following sensors to the VAV Zone Controller's inputs: •...
  • Page 20: Wiring An Spt Sensor

    Installation Wiring an SPT sensor The VAV Zone Controller is connected to a wall-mounted space temperature sensor to monitor room temperature. An i-Vu Open Control System offers the following SPT sensors: Sensor Part # Features • Local access port SPT Standard •...
  • Page 21: To Wire The Spt Sensor To The Controller

    Installation Voltage 300 Vac, power limited Listing UL: NEC CL2P, or better To wire the SPT sensor to the controller Partially cut, then bend and pull off the outer jacket of the Rnet cable(s). Do not nick the inner insulation. Strip about .25 inch (.6 cm) of the inner insulation from each wire.
  • Page 22: Wiring A T55 Space Temperature Sensor

    Installation Wiring a T55 space temperature sensor Part #33ZCT55SPT This wall-mounted sensor monitors space temperature and can be used instead of an SPT sensor. Wiring specifications Cable from sensor to controller: If <100 ft (30.5 meters) 22 AWG, unshielded If >100 ft (30.5 meters) 22 AWG, shielded Maximum length: 500 feet (152 meters)
  • Page 23: Wiring Specifications

    Installation Wiring specifications Cable from sensor to controller: If <100 ft (30.5 meters) 22 AWG, unshielded If >100 ft (30.5 meters) 22 AWG, shielded Maximum length: 500 feet (152 meters) To wire the SAT sensor to the controller Wire the sensor to the controller. See diagram below. Verify that the Enable SAT jumper is on.
  • Page 24: Wiring Specifications

    Installation Wiring specifications Cable from sensor to controller: If <100 ft (30.5 meters) 22 AWG, unshielded If >100 ft (30.5 meters) 22 AWG, shielded Maximum length: 500 feet (152 meters) To wire the CO2 sensor to the controller #33ZCSPTCO2 Wire the sensor to the controller. See appropriate diagram below. Verify that the RH/CO2 jumper is set to 0-5Vdc on the VAV Zone Controller.
  • Page 25: Wiring A Relative Humidity Sensor

    Installation Wiring diagram for #33ZCT55CO2: Wiring a Relative Humidity sensor Part #33ZCSENSRH-02 The Relative Humidity (RH) sensor is used for zone humidity control (dehumidification) if the rooftop unit has a dehumidification device. If not, the sensor only monitors humidity. NOTE Do not use a relative humidity sensor and CO sensor on the same zone controller.
  • Page 26: To Wire The Rh Sensor To The Controller

    Installation To wire the RH sensor to the controller Strip the outer jacket from the cable for at least 4 inches (10.2 cm). Strip .25 inch (.6 cm) of insulation from each wire. Wire the sensor to the controller. See diagram below. Using electrical tape, insulate any exposed resistor lead to prevent shorting.
  • Page 27: Wiring Specifications

    Installation Wiring specifications Cable from sensor to controller: If <100 ft (30.5 meters) 22 AWG, unshielded If >100 ft (30.5 meters) 22 AWG, shielded Maximum length: 500 feet (152 meters) Wiring equipment to outputs Use the following wiring diagrams to wire zone terminal equipment to the VAV Zone Controller's outputs. VAV Zone Single Duct Controller or VAV Zone Fan Terminal Controller No heat - Single duct (page 28) 2-position hot water/steam heat - Single duct (ducted or baseboard) (page 29)
  • Page 28: Wiring Specifications

    Installation Wiring specifications To size output wiring, consider the following: • Total loop distance from the power supply to the controller, and then to the controlled device NOTE Include the total distance of actual wire. For 2-conductor wires, this is twice the cable length. •...
  • Page 29: Step 2: Balance Each Zone

    Installation Step 2: Balance each zone In the i-Vu or Field Assistant tree, select the zone controller that is physically closest to the air source. Go to Properties > Equipment > Configuration > Service Configuration > Flow Control > Details tab. Do one of the following: Single Duct or Parallel Fan zone terminals –...
  • Page 30: To Calibrate Vav Zone Airflow

    Installation To calibrate VAV Zone airflow Select the VAV Zone air terminal in the tree. NOTE You can select View > Device ID or View > Primary Use to show this information next to each item in the tree. Select the Test and Balance tab. NOTE If appear on the status bar, see Air terminal calibration status to determine what you must do before calibration can occur.
  • Page 31: Step 3: Upload Calibration Values To The I-Vu/Field Assistant Application

    Installation Damper Command Action Occupied Min Forces the damper to its minimum occupied position and enables the Occupied Min Flow calibration fields. Damper Close Forces the damper to its full closed position. Heat Max Forces the damper to its maximum heating position. Calibration fields apply only if the primary use of the damper is heating.
  • Page 32: Wiring Diagram Legend

    Installation Wiring diagram legend Ground Hot water valve sensor Not used REMOTE Remote occupancy sensor Relative humidity sensor Supply air temperature sensor Silicon controlled rectifier Space temperature sensor T55 (OPT) Alternate space temperature sensor – – – Field-supplied wiring No heat - Single duct or fan box application VAV Zone Single Duct Controller or VAV Zone Fan Terminal Controller VAV Zone Controllers...
  • Page 33: 2-Position Hot Water/Steam Heat - Single Duct

    Installation 2-position hot water/steam heat - Single duct VAV Zone Single Duct Controller or VAV Zone Fan Terminal Controller Modulating hot water/steam (ducted or baseboard) - Single duct application VAV Zone Single Duct Controller or VAV Zone Fan Terminal Controller VAV Zone Controllers...
  • Page 34: Combination Heat (Ducted Electric Heat With Modulating Baseboard Heat) - Single Duct Application

    Installation Combination heat (ducted electric heat with modulating baseboard heat) - Single duct application VAV Zone Single Duct Controller or VAV Zone Fan Terminal Controller Electric heat (ducted or baseboard) - Single duct application VAV Zone Single Duct Controller or VAV Zone Fan Terminal Controller VAV Zone Controllers...
  • Page 35: Scr Electric Heat (Ducted Or Baseboard) - Single Duct Application

    Installation SCR electric heat (ducted or baseboard) - Single duct application VAV Zone Single Duct Controller or VAV Zone Fan Terminal Controller 2-position hot water/steam (ducted or baseboard) - Fan box application VAV Zone Fan Terminal Controller only VAV Zone Controllers...
  • Page 36: Modulating Hot Water (Ducted Or Baseboard) - Fan Box Application

    Installation Modulating hot water (ducted or baseboard) - Fan box application VAV Zone Fan Terminal Controller only Combination heat (ducted electric heat with modulating baseboard heat) - Fan box application VAV Zone Fan Terminal Controller only VAV Zone Controllers...
  • Page 37: 2-Stage Electric Heat (Ducted Or Baseboard) - Fan Box Application

    Installation 2-stage electric heat (ducted or baseboard) - Fan box application VAV Zone Fan Terminal Controller only SCR electric heat (ducted or baseboard) - Single duct application VAV Zone Fan Terminal Controller VAV Zone Controllers...
  • Page 38: Wiring A Field-Supplied High-Torque Actuator To The Analog Output

    Installation Wiring a field-supplied high-torque actuator to the analog output You can wire one of the following Belimo actuators to the VAV Zone Controller's analog output instead of using the controller's built-in, 35 in.-lb (4 Nm) actuator. NMX24-MFT P-10028 90 in.-lb (10 Nm) actuator with 0–10 Vdc control and 0–10 Vdc feedback AMX24-MFT P-10028 180 in.-lb (20 Nm) actuator with 0–10 Vdc control and 0–10 Vdc...
  • Page 39: Start-Up

    Start-up Start-up To start up the VAV Zone Controller, you need one of the following user interfaces. These items let you access the controller information, read sensor values, and test the controller. This interface... Provides a... i-Vu Open application Permanent interface Field Assistant application Temporary interface runs on a laptop connected to controller's Local Access port...
  • Page 40: Commissioning The Vav Zone Controller

    Start-up Verify that zone terminal fans and system controls operate properly. Verify that actuator screws are properly tightened. At the zone terminals, check electrical system and connections of any optional electric reheat coil. If hot water reheat is used, check piping and valves against job drawings. Verify that all zone terminal dampers are fully open.
  • Page 41: Balancing The System

    Start-up Balancing the system Most VAV system airflow designs are based on cooling requirements which require a greater cfm (liters/second) flow than heating requirements. Using the following balancing procedure, you adjust the cooling airflow first. If the heating and cooling maximum airflow requirements are the same, you do not need to balance the heating airflow. Use the Test &...
  • Page 42: Sequence Of Operation

    Sequence of operation Sequence of operation The VAV Zone Controller supports 3 types of pressure-independent terminal configurations: • Single duct • Series fan-powered • Parallel fan-powered The controller can operate as part of a linked system (VAV or VVT) or as a stand-alone controller. Temperature sensors The VAV Zone Controller supports the following temperature sensors: Sensors...
  • Page 43: Zone Reheat Control

    Sequence of operation Single duct with reheat – The Auxiliary Heat Min Airflow allows an increase of primary airflow across the terminal’s ducted heating coil whenever the terminal operates its local heat. This provides the ability to lower the cooling minimum airflow limits while providing the necessary airflow when the terminal is heating to ensure design load conditions and electric heater minimum airflow.
  • Page 44: Demand Control Ventilation (Dcv) And Dehumidification Using Optional Sensors

    Sequence of operation Two-Position Hot Water / Steam Heating Heat – The controller operates a normally closed or normally open hot water or steam valve connected to the discharge air heating coil. The valve opens and closes as needed to satisfy the zone's heating requirements.
  • Page 45: Occupancy

    Sequence of operation NOTE If the connected sensor and/or system sensor value are to be used by the air source through Linkage, set the appropriate control type to Enable. If you do not need local control at the zone, set DCV Max Vent Airflow or Maximum RH Override Airflow to 0.
  • Page 46: Alarms

    Sequence of operation Remote Occupancy Override – The controller monitors its Remote input that is typically connected to the isolated, dry contact of an occupancy sensor located in the zone. (To use the occupancy override as described here, the Standby Offset value must be set to zero.) The controller can override the occupancy state based on whether or not the space is actually occupied.
  • Page 47: Demand Limiting

    Sequence of operation Space Relative Humidity Alarm – If Optional Ctrl Type is set to RH Control (Space Relative Humidity (RH) sensor is installed), the controller generates an alarm if the sensor's value exceeds the Occ High RH Alarm Limit (100% rh default) or the Unocc High RH Alarm Limit (100% rh default).
  • Page 48 Sequence of operation The basic linkage process is as follows: The Master gathers data from the slave zone controllers such as occupancy status, setpoints, and zone temperature. The Master performs mathematical calculations and algorithms on the data. The Master sends the composite information to the air source. The air source returns information such as mode, supply air temperature, and outside air temperature, if present.
  • Page 49 Sequence of operation VVT Systems A VVT Master determines system operation by prioritizing heating and cooling requirements from all the zones based on their occupancy, demand, and damper size. The VVT Master continuously scans the system to determine if any zones are occupied. If any zones are occupied, the VVT Master evaluates the occupied zones' heating or cooling demands to determine the following: •...
  • Page 50: Air Source Mode Determination

    Sequence of operation Air source mode determination Linked air source modes – In a linked system, the air source determines its operating mode and qualifies that mode based on its own SAT. The following modes can be sent by the air source depending on its capability and configuration: •...
  • Page 51 Sequence of operation Metric: Use manufacturer’s liters/second at .249 kpa NOTE A local air source fan mode of OFF usually cannot be detected on series fan boxes. This is because the terminal’s series fan, when operating with the terminal damper open, usually creates enough primary airflow to prevent the control from properly detecting that the air source is off.
  • Page 52: Troubleshooting

    Troubleshooting Troubleshooting If you have problems mounting, wiring, or addressing the VAV Zone Controller, contact Carrier Control Systems Support. NOTE To help you troubleshoot, obtain a Module Status (Modstat) from the controller and review the System Error and Warning details. LED's The LED's on the VAV Zone Controller show the status of certain functions.
  • Page 53: Serial Number

    Troubleshooting If Run LED shows... And Error LED shows... Status is... 2 flashes per second Exec halted after frequent system errors, due to: • Controller halted • Program memory corrupted • One or more programs stopped 5 flashes per second Exec start-up aborted, Boot is running 5 flashes per second...
  • Page 54: Compliance

    Compliance Compliance FCC Compliance This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment.
  • Page 55: Appendix A: Vav Zone Controller Points/Properties

    Appendix A: VAV Zone Controller Points/Properties Appendix A: VAV Zone Controller Points/Properties NOTE Engineering units shown in this document in the defaults and ranges are strictly for reference. You must enter an integer only. Status Navigation: i-Vu® / Field Assistant: Properties Control Program Status...
  • Page 56: Unit Configuration

    Appendix A: VAV Zone Controller Points/Properties Unit Configuration Navigation: i-Vu® / Field Assistant: Properties Equipment Configuration Unit Configuration > > > view ®: HOME CONFIG UNIT > > Point Name/Description Default/Range Heat Enable – Enables the reheat function. Enable Disable/Enable Parallel Fan Heat On Delay –...
  • Page 57 Appendix A: VAV Zone Controller Points/Properties Point Name/Description Default/Range Occupancy Schedules – If , the controller stores and follows a schedule sent over Enable Enabled the network or programmed locally through a BACview device or Field Assistant. If Disable/Enable , the controller occupancy is controlled from the Disabled BAS On/Off System Occupancy...
  • Page 58: Setpoints

    Appendix A: VAV Zone Controller Points/Properties Setpoints Navigation: i-Vu® / Field Assistant: Properties Equipment Configuration Setpoints > > > view ®: HOME CONFIG SETPOINT > > Select a color band on the setpoint graph to see the current setpoints in the Heating and Cooling fields. The values in this graphic are Fahrenheit.
  • Page 59 Appendix A: VAV Zone Controller Points/Properties Default Range: -40 to 245°F (-40 to 118.3°C) Demand Level Point Name/Description Occupied Occupied Heating 1 – Light Blue 69°F 68°F 67°F 65°F The space temperature must be less than the Occupied Heating 1 (20.5°C) (20°C) (19.4°C)
  • Page 60 Appendix A: VAV Zone Controller Points/Properties Unoccupied Heating 2 – Dark Blue 52°F (11.1°C) The space temperature must be less than the Unoccupied Heating 2 setpoint to generate an 40 to 90°F unoccupied low space temperature alarm. We recommend that this value be set no less than (4.4 to 32.2°C) 0.5∆°F (.27∆°C) below the Unoccupied Heating 1 setpoint.
  • Page 61 Appendix A: VAV Zone Controller Points/Properties Hysteresis – The desired difference between the temperature at which the zone color 0.5∆°F (.27∆°) changes as the zone temperature departs from the acceptable range between the heating 0.2 to 1.0∆°F and cooling setpoints (green) into the Cooling 1 (yellow) or Heating 1 (light blue) and the (.1 to .5∆°C) temperature at which the zone color changes back to the acceptable range between the heating and cooling setpoints.
  • Page 62 Appendix A: VAV Zone Controller Points/Properties Point Name/Description Range English Metric Green – The amount the zone’s learned heating capacity is adjusted when the Learning 0.0600 .0333 Adaptive Optimal Start algorithm runs, when the zone’s thermographic color at 0 to 1 occupancy is green.
  • Page 63 Appendix A: VAV Zone Controller Points/Properties Point Name/Description Range English Metric Optimal Start Type – The method used to change from unoccupied to occupied setpoint. Temperature Compensated Options: None* – Unit will not change to occupied setpoint until the scheduled time or the unit None goes into an occupied mode.
  • Page 64: Alarm Configuration

    Appendix A: VAV Zone Controller Points/Properties Alarm Configuration Navigation: i-Vu® / Field Assistant: Properties Equipment Configuration Alarm Configuration > > > view ®: HOME CONFIG ALARMS > > Point Name/Description Default/Range Space Temperature Alarm Occupied Alarm Hysteresis – This value is added to the effective cooling setpoints and 5∆°F (2.7∆°C) subtracted from the effective heating setpoints as output from the Setpoint microblock.
  • Page 65: Service Configuration

    Appendix A: VAV Zone Controller Points/Properties Point Name/Description Default/Range 1100ppm Occupied High CO2 Alarm Limit – The value that the CO sensor must exceed to generate an Indoor Air Quality Alarm in the occupied mode if DCV Control is set to Enable. There is 0 to 9999 ppm a fixed hysteresis of 100ppm for return to normal.
  • Page 66 Appendix A: VAV Zone Controller Points/Properties Point Name/Description Default/Range External Actuator Enable – Enable if the controller's analog output is used for an external Disable high-torque or slave actuator. Enabling this setting disables the output for Modulating Hot Disable/Enable Water or Combination reheat functions. Heat Type –...
  • Page 67 Appendix A: VAV Zone Controller Points/Properties Point Name/Description Default/Range Occ Override Normal Logic State – The normal state of the controller's Remote Open Occupancy input. If the input's contact is the same state as the configured state, the Open/Closed controller follows its controlling schedule. If the contact is in the opposite state of the configured state, the controller is forced into the unoccupied mode.
  • Page 68 Appendix A: VAV Zone Controller Points/Properties Point Name/Description Default/Range Fan – The current value of the fan output relay. To override normal control for Off/On troubleshooting purposes, select Lock value to and then enter On or Off. The relay stays in that state until the Lock value to checkbox is cleared. Cooling Max Airflow –...
  • Page 69: Maintenance

    Appendix A: VAV Zone Controller Points/Properties Point Name/Description Default/Range System Space AQ – The indoor air quality received over the network. -999 indicates no 300 to 9999 ppm value has been received and it will not be used. System Cool Demand Level– The value received over the network and used by the 0 to 3 demand limiting function to expand the cooling setpoint.
  • Page 70 Appendix A: VAV Zone Controller Points/Properties Point Name/Description Default/Range Primary Airflow Setpoint – The desired airflow setpoint calculated by the controller to 0 to 99999 cfm meet the required temperature, IAQ, or dehumidification requirements. (liters/second) Relative Humidity Source – The source of the relative humidity value. Local Network Linkage...
  • Page 71: Alarms

    Appendix A: VAV Zone Controller Points/Properties Point Name/Description Default/Range Override Time Remaining – The amount of time remaining in an override period. 0 to 480 minutes Occupancy Contact Status – The physical state of the controller's Remote input. Inactive Active Unoccupied/Stdby Global Occupancy –...
  • Page 72: Linkage

    Appendix A: VAV Zone Controller Points/Properties Linkage Navigation: i-Vu® / Field Assistant: Properties Equipment Linkage > > view ®: HOME CONFIG LINKAGE > > Point Name/Description Default/Range Airside Linkage Click Linkage Collector/Linkage Provider to access the microblock popup's Summary and Details tabs.
  • Page 73 Appendix A: VAV Zone Controller Points/Properties Point Name/Description Default/Range Active Cooling Caller? – VVT system only. Determines if the zone will be counted as a cool caller for system cooling when the zone has a local demand for cooling. No/Yes Linkage Callers –...
  • Page 74: I/O Points

    Appendix A: VAV Zone Controller Points/Properties I/O Points Navigation: i-Vu / Field Assistant: Properties I/O Points > BACview: WARNING! Do not change the Value, Offset/Polarity, Exp:Num, I/O Type, Sensor/Actuator Type, Min/Max, or Resolution I/O configuration parameter for the points listed below. Changing these parameters could cause improper control and/or equipment damage.
  • Page 75 Appendix A: VAV Zone Controller Points/Properties Point Name/Description Default/Range Sensor Array: Sensor calculation method - When using multiple SPT sensors, select the process variable to be passed to the controller.. Avg, Min, Max BACnet configuration: Network Visible - Must be enabled for other BACnet objects to read or write to this Enabled point, and for this point to generate alarms.
  • Page 76: Appendix B: Vvt Terminal Modes

    Appendix B: VVT terminal modes Appendix B: VVT terminal modes Air Source Temperature Terminal Terminal Damper Control Heat Mode Control Type Mode Heat (Damper Setpoint Control Control Requirement used) None Hold Damper @ 70% Disable Disable (None) Hold Damper @ 70% Cooling Disable Disable...
  • Page 77 Appendix B: VVT terminal modes Air Source Temperature Terminal Terminal Damper Control Heat Mode Control Type Mode Heat (Damper Setpoint Control Control Requirement used) Heat, None Single Duct, Heating Minimum CFM (Heat) Disable Disable Parallel Fan Warmup Series Fan Heating Minimum CFM (Heat) Disable Enable...
  • Page 78: Index

    Index Index Local schedules • 41 Actuator • 1, 5, 38 Addressing the controller • 13 Maintenance • 65 Air source • 38, 43 Memory • 5 Air source modes • 38, 42, 46 Microprocessor • 5 Airside linkage • 68 Module driver •...
  • Page 79 Index CO2 Sensor Value @ Min Volts • 61 Learned heating capacity • 54 CO2 Source • 65 Learning Adaptive Optimal Start • 54 Cool Start K factor • 54 Learning Adaptive Start • 54, 65 Cooling • 54 Linkage Callers • 68 Linkage Collector •...
  • Page 80 Index SAT Sensor • 70 Zero Flow • 61 Schedules • 65 Zone Temp • 70 Sensor Array • 70 Zone Temp Sensor • 70 Sensor Calculation Method • 70 Power specifications • 5 Power wiring • 12 Sensor Failure • 65 Protection •...
  • Page 81 Index wall-mounted sensors CO2 sensor • 40 Weight • 5 Wiring 2-position hot water • 31 2-position hot water/steam heat - single duct • 2-stage electric heat • 33 Combination heat (ducted electric -modulating baseboard • 30 Combination heat (ducted or baseboard) • 32 Electric heat (ducted or baseboard) •...
  • Page 84 CARRIER CORPORATION ©2013 A member of the United Technologies Corporation family · Stock symbol UTX · Catalog No. 11-808-432-01 · 9/10/2013...

This manual is also suitable for:

Carrier opn-vavb3

Table of Contents