Page 2
Replacement Guide INTRODUCTION The feature-rich CHS Series Indicating controller is the heart of the EPG Level Master System. The level is determined by detecting changes in hydrostatic pressure using a submerged stainless steel pressure transducer. The EPG Level Indicating Controller ‘reads’ the corresponding analog current and uses one or two of the three internal relays to turn on and off pumps.
LED segments. It will then display the current input value. If there is no input and the meter was setup at EPG, (EPG standard configuration is for a 0-5PSIG input with 4-20mA output) the meter will display –34.6. In order to change any set points or internal values, one must enter the respective SETUP MODE as defined in the Configuration Guide on page 10 of this manual.
Open or Normally Closed (see 3.4 & 3.5 below). 3.1 20mA CALIBRATION The meter is delivered from EPG pre-calibrated. Under normal operation this setting should NEVER be adjusted. If re-calibration is required consult your EPG representative. 3.2 MODBUS ADDRESS (Addr = 1- 240) Use the UP/DOWN arrow keys to enter the desired Modbus address and press the SETUP/ENTER key.
Page 15
19. Move one wire from old connector J2 terminal #9 (or #8) to new meter connector J1 terminal #10. Contact EPG Companies if more than two terminals are used on a meter relay output or if there are any remaining wires on the old meter connectors.
Need help?
Do you have a question about the LevelMaster CHS Series and is the answer not in the manual?
Questions and answers