Omega PX602 Quick Start Manual page 2

Pressure transducer

Advertisement

omega.com
omega.com
PX602, PX603, PX605
PX612, PX613, PX615
Pressure Transducer
M947/1009
ACCURACY:
(Linearity, Hysteresis and Repeatability)
HYSTERESIS:
REPEATABILITY:
ZERO BALANCE:
STORAGE TEMPERATURE:
OPERATING TEMPERATURE:
COMPENSATED TEMPERATURE:
THERMAL EFFECTS:
(Zero)
(Span)
PROOF PRESSURE:
BURST PRESSURE:
EXCITATION:
OUTPUT:
SENSITIVITY:
OUTPUT IMPEDANCE:
WEIGHT:
EXCITATION:
OUTPUT:
SUPPLY CURRENT:
OUTPUT IMPEDANCE:
WEIGHT:
EXCITATION:
OUTPUT:
MAX. LOOP RESISTANCE: 50 x (supply voltage –10)
WEIGHT:
Fluid hammer and surges can destroy any pressure transducer and
must always be avoided. A pressure snubber should be installed to
eliminate the damaging hammer effects. Fluid hammer occurs
when a liquid flow is suddenly stopped, as with quick closing sole-
noid valves. Surges occur when flow is suddenly begun, as when
pump is turned on to full power or a valve is quickly opened.
Liquid surges are particularly damaging to pressure transducers if
the pipe is originally empty. To avoid damaging surges, fluid lines
should remain full (if possible), pumps should be brought up to
power slowly and valves opened slowly. To avoid damage from both
fluid hammer and surges, a surge chamber should be installed and
TM
®
COMMON SPECIFICATIONS FOR ALL UNITS
±0.4% FS (BFSL)
±0.2% FS
±0.07% FS
±1% FS
–65° to 250°F
(–53° to 121°C)
–20° to 180°F
(–28° to 82°C)
–20° to 160°F
(–28° to 71°C)
±0.04% FS/°F
±0.04% FS/°F
15-2000 PSI = 200% FS;
3000-5000 PSI = 150% FS
7500-20,000 PSI = 120% FS
15-2000 PSI = 800% FS;
3000-5000 PSI = 300% FS
7500-20,000 PSI = 150% FS
PX602 & PX612 SERIES MILLIVOLT OUTPUT
10Vdc, (5-10Vdc limit @ 6mA max)
100mV ±1mV
10mV/V
100
2 oz (without cable)
PX603 & PX613 SERIES VOLTAGE OUTPUT
24Vdc, (10-36Vdc)
1-5Vdc (3 wire)
<3mA
1000
2 oz (without cable)
PX605 & PX615 SERIES CURRENT OUTPUT
24Vdc, (10-36Vdc)
4-20mA (2 wire)
2 oz (without cable)
WARNING! READ BEFORE INSTALLATION
PX602, PX603, PX605
CONSTRUCTION:
VIBRATION:
SHOCK:
FATIGUE:
CIRCUIT TO CASE
INSULATION:
SENSOR TYPE:
WETTED PARTS:
PRESSURE PORT:
CASE:
RESPONSE TIME:
a pressure snubber should be installed on every transducer.
Symptoms of fluid hammer and surge's damaging effects:
1. Pressure transducer exhibits an output at zero pressure (large
zero offset). If zero offset is less than 10% FS, user can usually
re-zero meter, install proper snubber and continue monitoring
pressures.
2. Pressure transducer output remains constant regardless of
pressure.
3. In severe cases, there will be no output.
PX612, PX613, PX615
Sealed units (All cables are vented.
Sensor >300 PSI is not)
<±0.1% FS effect for 0-2000 Hz @
20G's in any axis
<±0.05% FS effect 100 G's, 20msec
shock in any axis
100 million cycles 20/80% FS with
negligible performance loss
100M ohms at 50Vdc
Chemical vapor deposited polysilicon
strain gages
17-4 PH SS, 300 Series SS
1
-18 NPT
4
9
(15,000-20,000 =
-18 UNF Female Aminco)
16
NEMA 4X, 304 SS
5ms
WIRING
(PX612)
(PX602)
A
Red
B
Green
C
Black
D
White
WIRING
(PX613)
(PX603)
A
Red
B
Green
D
White
WIRING
(PX615)
(PX605)
A
Red
C
Black
+EXC
+OUTPUT
–OUTPUT
–EXC
+EXC
OUTPUT
COMMON
+