DELUGE VALVE, EXTERNAL RESETTING
MODEL F470 MULTIMATIC
GENERAL DESCRIPTION
The 4 and 6 inch (100 and 150 mm),
Model F470 External Resetting Multi-
matic Deluge Valves are differential
latch type valves designed for fire pro-
tection system service. They are used
as "automatic water control valves" in
deluge, preaction, and special types of
fire protection systems such as foam-
water and double interlock. The F470
Valves also provide for actuation of fire
alarms upon system operation.
The external resetting feature of the
F470 Valve provides for easy resetting
of a deluge or preaction system, with-
out having to open a valve handhole
cover to manually reposition a clapper
and latch mechanism. Simply depress-
ing a plunger at the left side of the
F470 Valve allows the clapper and
latch to reset.
Operation of an F470 Valve is provided
by an actuation (detection) system that
is separate from the normally dry sys-
tem piping. Trim configuration options
for automatic operation of the F470
include wet pilot actuation, dry pilot
actuation, and electric actuation. Trim
arrangements also provide for local
emergency (manual) release of the
F470 Valves.
APPROVALS AND STANDARDS
The 4 and 6 inch (100 and 150 mm),
Model F470 External Resetting Multi-
matic Deluge Valves are listed by Un-
derwriters Laboratories Inc. and Un-
derwriters' Laboratories of Canada.
The F470 Valves are also approved by
Factory Mutual Research Corporation
and the Scientific Services Laborato-
ries (Australia).
The Model F470 Deluge Valves with
either wet or dry pilot actuation and
galvanized trim are approved by the
Loss Prevention Council (United King-
dom).
Inquiries concerning approval by the
Verband
der
Schadeversicherer
should be directed to Grinnell Sales &
Distribution, Kopersteden 1, NL-7547
TJ Enschede, Netherlands, Tel. 31-
534-283-434 / Fax. 31-534-283-377.
Printed in U.S.A. 9-99
®
— 4 and 6 INCH (100 and 150 mm)
Nominal Dimensions in Inches and (mm)
VALVE
A
B
SIZE
4
2"
1/2"
(100)
NPT
NPT
6
2"
1/2"
(150)
NPT
NPT
VALVE
J
K
SIZE
4
8.00
10.50
(100)
(203,2)
(266,7)
6
8.87
11.50
(150)
(225,3)
(292,1)
MODEL F470 EXTERNAL RESETTING MULTIMATIC DELUGE VALVES
— DIMENSIONS AND PORT LOCATIONS —
4 Inch (100 mm) Valve
6 Inch (150 mm) Valve
C
D
E
1/2"
1/2"
3.44
NPT
NPT
(87,4)
(65,0)
1/2"
1/2"
3.40
NPT
NPT
(86,4)
(62,2)
L
M
N
8.50
3.75
2.37
(215,9)
(95,3)
(60,2)
(65,0)
9.18
4.54
3.20
(233,2)
(115,3)
(81,3)
(62,2)
FIGURE A
F
G
H
2.56
2.73
5.25
(69,3)
(133,4)
2.45
3.69
6.63
(93,7)
(168,4)
P
Q
R
2.56
1.72
13.25
(43,7)
(336,6)
2.45
1.82
14.25
(46,2)
(362,0)
TD116

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MULTIMATIC F470 and is the answer not in the manual?

Questions and answers

Summary of Contents for Grinnell MULTIMATIC F470

  • Page 1 2.37 2.56 1.72 13.25 Verband Schadeversicherer (100) (203,2) (266,7) (215,9) (95,3) (60,2) (65,0) (43,7) (336,6) should be directed to Grinnell Sales & 8.87 11.50 9.18 4.54 3.20 2.45 1.82 14.25 Distribution, Kopersteden 1, NL-7547 (150) (225,3) (292,1) (233,2) (115,3) (81,3)
  • Page 2 1 - Body 7 - Clapper Latch 13 - Diaphragm Cover 17 - Diaphragm 22 - Handhole Cover 2 - Clapper 8 - O-Ring, # 3-908 Bolt, (5 req’d) Housing 23 - Handhole Cover Gasket 3 - Clapper Facing 9 - Reset 1/2"...
  • Page 3: Technical Data

    GRAPH A-1 GRAPH A-2 GRAPHS A-1 and A-2 NOMINAL PRESSURE LOSS VERSUS FLOW The Model F470 Multimatic Deluge at a maximum service pressure of 175 ASTM B148 (UNS C956200), the Re- Valves are accepted by the City of New psi (12,1 bar). The Valve dimensions set Bushing is brass per ASTM B16 York under MEA 38-92-M.
  • Page 4 GRAPH B WET PILOT LINE DESIGN CRITERIA Wet Pilot Actuation (Figure F-1, Items 1 through 35) The Wet Pilot Actuation Trim provides for connection of a detection system consisting of wet pilot sprinklers (heat detectors) and manual control stations interconnected with minimum 1/2 inch (15 mm) Schedule 40 steel pipe.
  • Page 5 To determine the most hydraulically F470 Valve, and the force differential pilot actuation system and/or alarm demanding location of a wet pilot line, applied through the Clapper Latch which separately indicates operation when the choice between two or more which holds the Clapper down in the of the detection system is recom- locations is not readily apparent, de- set position is reduced to below the...
  • Page 6: Operating Principles

    of the F470 Valve, and the force differ- ential applied through the Clapper Latch which holds the Clapper down in the set position is reduced to below the valve trip point. NOTE Consult with the Authority Having Jurisdiction regarding installation criteria pertaining to electric actua- tion circuitry.
  • Page 7: Installation

    Left View Front View Nominal Installation Dimensions in Inches and (MM) VALVE SIZE 12.00 8.69 14.25 13.69 19.00 5.44 6.69 8.75 7.75 6.31 0.25 (100) (304,8) (220,7) (362,0) (347,7) (482,6) (138,2) (169,9) (222,3) (196,9) (160,3) (6,4) 12.00 8.69 15.12 14.50 20.00 5.50 7.62...
  • Page 8 Left View Front View Nominal Installation Dimensions in Inches and (MM) VALVE SIZE 12.00 8.69 14.56 13.69 30.12 5.44 6.69 8.75 7.75 6.31 0.25 (100) (304,8) (220,7) (369,8) (347,7) (765,0) (138,2) (169,9) (222,3) (196,9) (160,3) (6,4) 12.00 8.69 15.44 14.50 31.12 5.50 7.62...
  • Page 9 12. Unused pressure alarm switch con- the reseating sound of the Clapper of a subsequent operation of an nections must be plugged. will not be heard. overheated solder type pilot sprin- kler, any solder type pilot sprin- 13. The Pressure Relief Valve provided Also under normal circumstances, klers which were possibly exposed with the Dry Pilot Actuation Trim is...
  • Page 10 NOTE: Refer to Page11 for the corresponding bills of materials. FIGURE F-1 EXPLODED VIEW OF VALVE TRIM -10-...
  • Page 11: Care And Maintenance

    1 - 300 lb. Water Pres- 31 - 1/2" x 5" Nipple sure Gauge (2 req’d) (2 req’d) 32 - 1/2" x 7-1/2" 2 - 1/4" Gauge Nipple Test Valve 33 - 1/2" x 10-1/2" 3 - Model F180 Nipple for Manual Control 4"...
  • Page 12 FIGURE G-1 DELUGE VALVE SYSTEM SCHEMATIC — WET PILOT ACTUATION— FIGURE G-2 DELUGE VALVE SYSTEM SCHEMATIC — DRY PILOT ACTUATION— -12-...
  • Page 13 FIGURE G-3 DELUGE VALVE SYSTEM SCHEMATIC — ELECTRIC ACTUATION— ing a fire condition) should be verified manufacturer’s instructions to ener- are any signs of deterioration due to at least once a year as follows: gize the solenoid valve. age or chemicals in the water. 1.
  • Page 14: Warranty

    with the manufacturer’s instructions Quarterly Waterflow Alarm Test no leaks, fully open the Main Control to energize the solenoid valve. Procedure Valve. 4. Verify that the flow of water from the Testing of the system waterflow alarms Solenoid Valve drain connection in- should be performed quarterly.
  • Page 15 “Standard Order” Accessories: 12 - Reset Knob ... PSN 62-470-1-001 13 - Diaphragm Factory Assembled Black Trim: Refer to the following Technical Data Cover Bolt ... PSN 62-039-1-207 Specify: Factory assembled black Sheets (TD), as applicable.