EN
IR24-P
i
Read this instruction before installation
and wiring of the product
Motion detector
IR24-P is a passive infrared motion detector suitable for use in "on
demand" control of ventilation systems or in intrusion alarm circuits.
Technical data
Infrared sensor
Dual element
Supply voltage
24 ± 2 V AC/DC
Detection range
15 x 15 m, 110° angle
Power consumption
5 mA at 24 V AC
Output
200 mA, 24 V AC/DC, potential-free
change-over relay
Ambient humidity
Max. 95% RH
Temperature range
-20...+50°C
Protection class
IP20
Mounting bracket
MB-100
Mounting height
1.8...3.6 m
Detectable speed
0.1...3.0 m/s
ON-delay
0, 10, 30, 60, 300 or 600 s (selectable)
OFF-delay
10, 60, 300, 600, 1200 or 1800 s
(selectable)
Dimensions (HxWxD)
112 x 66 x 45
Cable hole
Corner mount
Jumpers
Fig. 1 IR24-P
Detection pattern
110°, 15 x 15 m, 110° Plan view
2,4m
Side view
2,5m
10m
15m
IR24-P
Mounting
For best coverage, IR24-P should be placed 6...8 ft above floor level
Terminal
in a location with an unhindered view of the area to be monitored.
Avoid exposure to direct sunlight or other powerful heat sources.
For corner mounting the two corner mounting holes in the casing
may be used. For other wall mounting or for ceiling mounting use
the supplied mounting bracket. Fasten the bracket according to the
appropriate figure. Fasten the unit to the bracket and lead the cable
LEDs
through the access tube in the bracket and through the cable hole in
the housing.
Align the unit and lock in position by tightening the locking screw on
Sensor
the bracket. Replace the front cover.
NB: Don't touch!
Ceiling mounting
22mm
Cover screw
1
Locking screw
Fig. 2 Installation of the mounting bracket
1
Fig. 3 Mounting the unit on the bracket
Wall mounting
2
1
8mm
3
2
End-cap*
End-cap*
*
The end-cap can be used to
cover the back of the bracket
2
3
3
5
4
6
1

Advertisement

loading

Summary of Contents for Regin IR24-P

  • Page 1 INSTRUCTION Cable hole Mounting IR24-P For best coverage, IR24-P should be placed 6...8 ft above floor level Corner mount Terminal in a location with an unhindered view of the area to be monitored. Avoid exposure to direct sunlight or other powerful heat sources.
  • Page 2 24 V AC/DC This product carries the CE-mark. More information is available at www. regincontrols.com. IR24-P är en passiv, infraröd rörelsedetektor som lämpar sig för be- hovsstyrda ventilationsanläggningar eller i larmanläggningar. Contact AB Regin, Box 116, 428 22 Kållered, Sweden...
  • Page 3 Montering Övervakningsmönster På För bästa täckning bör IR24-P sitta c:a 2...2,5 m över golvnivå på en 110°, 15 x 15 m, 110° vinkel Planvy plats med obehindrad sikt över det område som skall bevakas. Den På skall inte exponeras för direkt solljus eller andra starka värmekällor.
  • Page 4 Bringen Sie die Abdeckung wieder an. Montage Umgebungsfeuchte Max. 95 % rF Temperaturbereich -20...+50 °C Für eine optimale Erfassung sollte der IR24-P ca. 1,8...2,4 m Verdrahtung Schutzart IP20 über Bodenniveau an eine Stelle montiert werden, an der eine Versorgungsspannung: 24 V AC/DC ± 2 V...
  • Page 5: Détecteur De Mouvements

    INSTRUCTION Montage IR24-P Pour obtenir une couverture de zone optimale, IR24-P doit être installé entre 2 et 2,5 m du sol, dans un endroit sans obstacle Veuillez lire cette instruction avant de procéder à apparent qui pourrait gêner la surveillance de la pièce. Éviter l'installation et au raccordement du produit.
  • Page 6: Zone De Détection

    Tél : +33(0)1 71 00 34, Fax : +33(0)1 71 46 46 www.regincontrols.com, info@regin.fr Retards à la mise en marche/arrêt (temporisation) IR24-P est doté de retards à la mise en marche/arrêt réglables individuellement. Le détecteur est normalement en veille, avec la sortie inactive.