Mitsubishi Electric PUZ-HA24NHA1 Service Manual page 82

Split-type, heat pump air conditioners
Hide thumbs Also See for PUZ-HA24NHA1:
Table of Contents

Advertisement

(2) Functions available when setting the unit number to 01-03 or AL (07 in the case of the IR wireless remote controller)
• When setting functions for an indoor unit in an independent system, set the unit number to 01 referring to 4 setting the
indoor unit number.
• When setting functions for a simultaneous twin indoor unit system, set the unit number to 01 to 03 for each indoor
unit in the case of selecting different functions for each unit referring to 4 setting the indoor unit number.
• When setting the same functions for an entire simultaneous Twin-indoor unit system, set refrigerant address to AL
(07 in the case of the IR wireless remote controller) referring to 4 setting the indoor unit number.
<Table 3> Available functions and settings
Function
100h
Filter sign
2500h
"Clean the filter" indicator is not displayed
Quiet
Airflow
( Fan speed )
Standard
High ceiling
4 directions
No.of air outlets
3 directions
2 directions
Not supported
Optional high efficiency
filter
Supported
No vanes (Vane No.3 setting: PLA only)
Vane setting
Vane No.1 setting
Vane No.2 setting
Not supported
Optional humidifier
( PLA only )
Supported
No.1 setting (TH5: 75–82˚F [24–28˚C])
Vane differential setting
No.2 setting (Standard, TH5: 82–90˚F [28–32˚C])
in heating mode
( cold wind prevention )
No.3 setting (TH5: 90–100˚F [32-38˚C])
Not available Swing
Swing
Available
Available
Set temperature in heating
mode ( 4 degC up )
Not available
Extra low
Fan speed when the
Stop
heating thermostat is OFF
Keeping fan speed set by remote controller
Keeping fan speed set by remote controller
Fan speed when the
cooling thermostat is OFF
Stop
Detect
Detection of abnormality of
the pipe temperature ( P8 )
Neglect
<Table 4> Mode No.11
Setting No. Settings
1
Vane No.3 setting
2
Vane No.1 setting
3
Vane No.2 setting
* In this setting, the ceiling may be smudged.
<Table 5> Mode No. 08 and 10
Setting No.
External static
pressure
Mode No. 08 Mode No. 10
35Pa
2
50Pa
3
70Pa
1
100Pa
2
150Pa
3
12-2. SELECTING FUNCTIONS USING THE REMOTE CONTROLLER
Refer to "15-3. SERVICE MENU" and "15-5. FUNCTION SETTING" when selecting functions.
OCH750A
Settings
}
PLA-EA
Wave airflow
PLA-EA
Less smudging
( Downward position than the standard )
Standard
Less draft *
( Upward position than the standard )
Initial setting
( Factory setting )
1
1
2
2
2
Mode No.
Setting No.
Wired remote controller
(RF thermostat)
1
07
2
(107)
3
1
08
2
(108)
3
1
09
2
(109)
3
10
1
(110)
2
1
11
2
(111)
3
13
1
(113)
2
1
14
2
(114)
3
23
1
(123)
2
24
1
(124)
2
1
25
2
(125)
3
27
1
(127)
2
28
1
(128)
2
No vane function
Standard
Less draft *
( Upward position than the standard )
82
: Initial setting ( Factory setting )
-: Not available
Cealing
4-Way
Ceiling
concealed
cassette
Suspended
PLA-EA
PCA-KA
PEAD-AA
Refer to
the <Table 5>
below.
-
-
-
-
-
-
Refer to
the <Table 5>
below.
-
-
-
-
-
-
-
-
-
-
-
-
PCA-KA