E-Star® OESE
Condensing Unit
3.5 and 5 HP HFC
INSTALLATION AND OPERATION MANUAL
Part No. 8828747
Effective April 13, 2020

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the E-Star OESE-A351-HFC and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Mueller E-Star OESE-A351-HFC

  • Page 1 E-Star® OESE Condensing Unit 3.5 and 5 HP HFC INSTALLATION AND OPERATION MANUAL Part No. 8828747 Effective April 13, 2020...
  • Page 3: Table Of Contents

    Safety Alert ....................... . . 7 Mueller E-Star OESE 3.5 and 5 HP HFC Condensing Unit Installation and Operation Manual, Part No.
  • Page 4 Figure 7: Sound Measurement ................... . 21 Mueller E-Star OESE 3.5 and 5 HP HFC Condensing Unit Installation and Operation Manual, Part No.
  • Page 5 Personal Protective Equipment ................... 29 Mueller E-Star OESE 3.5 and 5 HP HFC Condensing Unit Installation and Operation Manual, Part No.
  • Page 6 ..............37 Mueller E-Star OESE 3.5 and 5 HP HFC Condensing Unit Installation and Operation Manual, Part No.
  • Page 7: Section 1.0 - Introduction

    Section 1.0 – Introduction GENERAL SPECIFICATIONS Mueller® E-Star OESE condensing units are engineered to maximize the energy efficiency and cooling capacity of a milk cooling system. Custom and specialized components consist of the following: A quiet, energy-efficient Copeland® “ZB” scroll refrigeration compressor, designed for commercial refrigeration service rather than air conditioning, provides improved performance over the entire milk cooling temperature range.
  • Page 8: Technical Support

    TECHNICAL SUPPORT This manual provides basic installation and operating information for Mueller E-Star OESE condensing units. Please contact your local Paul Mueller Company Sales and Service Representative if you require additional technical assistance pertaining to installation or operating procedures. Manufacturer’s support is available by contacting the following:...
  • Page 9: Section 2.0 - Installation

    IMPORTANT: Equipment used to move or lift this equipment must be rated for the weight of the equipment. See Table 1 for equipment weight. LOCATION When choosing a location for the Mueller E-Star OESE condensing unit, consider these items: • Environment: The unit must be located where it is protected from extreme temperatures of –30°F (–34.4°C) and below or 115°F (46.1°C) and above.
  • Page 10 Discharge Line Horsepower Liquid Line Suction Line (Fre-Heater®) ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ Mueller E-Star OESE 3.5 and 5 HP HFC Condensing Unit Installation and Operation Manual, Part No. 8828747 Effective April 13, 2020...
  • Page 11: Electrical Connections

    Connecting high-voltage control to this circuit will cause equipment failure and a possible electrical hazard. The control circuit can be modified for high-voltage supply in installations that do not utilize a Mueller low-voltage refrigeration control. Refer to Section 7.0 for details.
  • Page 12: Section 3.0 - Refrigerant Charging

    Section 3.0 – Refrigerant Charging EPA REFRIGERANT REGULATIONS Mueller E-Star OESE condensing units are designed to operate with R-507 refrigerant. R-507 is specified by the ASHRAE Standard 34 Safety Classification as an A-1 refrigerant with low-flame propagation and low toxicity.
  • Page 13: Final Operating Charge

    When refrigerants come in contact with an open flame or a high heat source, dangerous gases will form. This is characterized by a strong acidic odor. Immediately vacate the area and ventilate prior to reentry. Mueller E-Star OESE 3.5 and 5 HP HFC Condensing Unit Installation and Operation Manual, Part No. 8828747...
  • Page 14: Section 4.0 - Operating Features

    Section 4.0 – Operating Features REFRIGERANT CYCLE Mueller E-Star OESE condensing units utilize an thermal expansion valve (TEV) that controls the evaporator’s superheat. The expansion valve must be field adjusted to maintain the milk coolor’s evaporator’s superheat at 4–6°F (2.2–3.3°C) or the chiller’s superheat at 10–12°F (5.6–6.7°C).
  • Page 15 (access ports P2) to ensure the compressor is protected against damage caused by liquid refrigerant slugging. Mueller E-Star OESE 3.5 and 5 HP HFC Condensing Unit Installation and Operation Manual, Part No. 8828747 Effective April 13, 2020...
  • Page 16: Section 5.0 - Expansion Valve

    10–12°F. Proper location and sizing of the thermal expansion valve is critical. Refer to Section 5.2 for the superheat adjustment procedure. An externally equalized TEV must be used on Mueller milk cooling applications. A sight glass must be installed at the TEV inlet.
  • Page 17: Checking And Adjusting Superheat

    • Actual suction line temperature equals 40°F. Results: 60 PSIG • 40°F – 34°F = 6°F (4.4°C – 1.1°C = 3.3°C) superheat at evaporator. Mueller E-Star OESE 3.5 and 5 HP HFC Condensing Unit Installation and Operation Manual, Part No. 8828747 Effective April 13, 2020...
  • Page 18: Section 6.0 - Accumulator Heat Exchanger

    IMPORTANT: The Mueller accumulator heat exchanger utilizes a special “pancake” heat exchange coil. The use of a generic (spiral) accumulator heat exchanger will severely reduce cooling capacity of the E-Star OESE condensing unit and may cause premature compressor failure. Use genuine Mueller replacement parts only.
  • Page 19: Section 7.0 - Electrical Schematics

    8. All grounds terminate in the control box except the crankcase heater which terminates next to the compressor on the base plate. DFE0212 Mueller E-Star OESE 3.5 and 5 HP HFC Condensing Unit Installation and Operation Manual, Part No. 8828747...
  • Page 20: Oese 5 Hp, 460/60/3 Wiring Schematic (Effective Until August 31, 2007)

    6. Field wiring not to come in contact with control box heater. 7. All enforced electrical codes must be followed during GROUND installation, service, and/or operation of this equipment. DFE0155 Mueller E-Star OESE 3.5 and 5 HP HFC Condensing Unit Installation and Operation Manual, Part No. 8828747 Effective April 13, 2020...
  • Page 21: Oese 3.5 And 5 Hp, 200-220/50/1, 208-230/60/1 Wiring Schematic

    6. Field wiring not to come in contact with control box heater. 7. All enforced electrical codes must be followed during installation, service, and/or operation of this equipment. DFE0153 Mueller E-Star OESE 3.5 and 5 HP HFC Condensing Unit Installation and Operation Manual, Part No. 8828747 Effective April 13, 2020...
  • Page 22: Oese 3.5 And 5 Hp, 200-240/50/3, 208-230/60/3 Wiring Schematic

    6. Field wiring not to come in contact with control box heater. 7. All enforced electrical codes must be followed during installation, service, and/or operation of this equipment. DFE0154 Mueller E-Star OESE 3.5 and 5 HP HFC Condensing Unit Installation and Operation Manual, Part No. 8828747 Effective April 13, 2020...
  • Page 23: Oese Low-Voltage, 24-Vac Control Circuit

    LOW PRESSURE SWITCH MANUAL OR AUTO RESET 24V CONTROL FROM CONTROL BOX BLUE BLUE HIGH PRESSURE SWITCH MANUAL OR AUTO RESET Mueller E-Star OESE 3.5 and 5 HP HFC Condensing Unit Installation and Operation Manual, Part No. 8828747 Effective April 13, 2020...
  • Page 24: Oese Control Circuit Retrofit, 24-Vac To 240-Vac, Pre-1996 Control Boxes

    “OH” AND PRE-1996 “OE” CONTROLS NOT UTILIZING 24 VAC CONTROL OUTPUT. BLUE HIGH PRESSURE SWITCH MANUAL OR AUTO RESET Mueller E-Star OESE 3.5 and 5 HP HFC Condensing Unit Installation and Operation Manual, Part No. 8828747 Effective April 13, 2020...
  • Page 25: Section 8.0 - Pressure Switches And Fan Control

    By placing the switch in the cutoff mode when pressure is below the setpoint value, the fan motor will be turned off and remain off until the pressure increases above the setpoint value. Mueller E-Star OESE 3.5 and 5 HP HFC Condensing Unit Installation and Operation Manual, Part No. 8828747...
  • Page 26: Rge Electronic Fan Pressure Control Setpoint Adjustment

    NOTE: All high-side pressure safety connections will not have a Schrader core due to safety regulation on the system’s high side. Mueller E-Star OESE 3.5 and 5 HP HFC Condensing Unit Installation and Operation Manual, Part No. 8828747 Effective April 13, 2020...
  • Page 27: Section 9.0 - Equipment Sound Level

    84 dB. FIGURE 7: SOUND MEASUREMENT Compressor 84 dB 80 dB 81 dB 81 dB Condenser Mueller E-Star OESE 3.5 and 5 HP HFC Condensing Unit Installation and Operation Manual, Part No. 8828747 Effective April 13, 2020...
  • Page 28: Section 10.0 - Maintenance

    Provide the actual time below. Readings should be taken at five-minute intervals. Compressor Amperage Time* Measured Supply Voltage: Condensing Unit Model and Part No.: Serial No.: Mueller E-Star OESE 3.5 and 5 HP HFC Condensing Unit Installation and Operation Manual, Part No. 8828747 Effective April 13, 2020...
  • Page 29: Maintenance Procedures

    10.2 MAINTENANCE PROCEDURES Mueller E-Star OESE condensing units require minimal maintenance. The following scheduled maintenance procedures are recommended and should be performed by a knowledgeable service technician on an annual basis: Clean the condenser tubes and fins from accumulated dust or other foreign matter to ensure proper air flow.
  • Page 30: Section 11.0 - Disposal

    The condensing unit’s basic structure consists of steel, tin, aluminum, plastic, and copper, all of which may be separated and recycled. Mueller E-Star OESE 3.5 and 5 HP HFC Condensing Unit Installation and Operation Manual, Part No. 8828747 Effective April 13, 2020...
  • Page 31: Section 12.0 - Equipment Markings

    Leak test and evacuate Run test unit Dry nitrogen holding charge: Manual Part No.: Final Inspection: Date: 1806 8822574 Mueller E-Star OESE 3.5 and 5 HP HFC Condensing Unit Installation and Operation Manual, Part No. 8828747 Effective April 13, 2020...
  • Page 32: Label No. 8820155, Wiring Connections For Three-Phase Scrolls

    LABEL NO. 31193, SCREEN INSIDE (IDENTIFIES SUCTION LINE SCREEN LOCATION) SCREEN INSIDE • SCREEN INSIDE • SCREEN INSIDE • SCREEN INSIDE Mueller E-Star OESE 3.5 and 5 HP HFC Condensing Unit Installation and Operation Manual, Part No. 8828747 Effective April 13, 2020...
  • Page 33: Label No. 8822232, Warning Symbol: Hot

    PUEDE CAUSAR HERIDA O MUERTE. DESCONECTAR TODOS LOS SUMINISTROS DE REMOTO ELÉCTRICO DE PODER ANTES DE SERVICIO. 0001 8822141 Mueller E-Star OESE 3.5 and 5 HP HFC Condensing Unit Installation and Operation Manual, Part No. 8828747 Effective April 13, 2020...
  • Page 34: Label No. 8820764, Warning: Disconnect Power Before Screen Guard Removal

    DÉMARRERA AUTOMATIQUEMENT. PELIGRO EL ABANICO COMIENZA AUTOMATICAMENTE. 8906 8820769 12.16 LABEL NO. 8824383, MUELLER LOGO 12.17 LABEL NO. 8822705, CSA Mueller E-Star OESE 3.5 and 5 HP HFC Condensing Unit Installation and Operation Manual, Part No. 8828747 Effective April 13, 2020...
  • Page 35: Section 13.0 - Safety

    Technicians handling refrigerants should wear side-shielded safety glasses, impervious (preferably butyl-lined) gloves, and other protective equipment or clothing as required by the situation. Mueller E-Star OESE 3.5 and 5 HP HFC Condensing Unit Installation and Operation Manual, Part No. 8828747...
  • Page 36: Section 14.0 - Technical Data

    Copeland Ultra 22cc or Mobil EAL Arctic 22CC OESE-A534-HFC 8825319 5 HP, Three-Phase Unit, ZB38KCE 64 oz Copeland Ultra 22cc or Mobil EAL Arctic 22CC Mueller E-Star OESE 3.5 and 5 HP HFC Condensing Unit Installation and Operation Manual, Part No. 8828747 Effective April 13, 2020...
  • Page 37: Section 15.0 - Compressor Data Charts

    Nominal Performance Values (± 5%) based on 72 hours run-in. Subject to change without notice. Current @ 230 V. ©2016 Emerson Climate Technologies, Inc. Printed 1/11/2016 Autogenerated Compressor Performance 05-184 Mueller E-Star OESE 3.5 and 5 HP HFC Condensing Unit Installation and Operation Manual, Part No. 8828747 Effective April 13, 2020...
  • Page 38: Zb26Kce Three-Phase, 208/230 V Compressor Data Chart

    Nominal Performance Values (± 5%) based on 72 hours run-in. Subject to change without notice. Current @ 230 V. ©2016 Emerson Climate Technologies, Inc. Printed 1/10/2016 Autogenerated Compressor Performance 04-1338 Mueller E-Star OESE 3.5 and 5 HP HFC Condensing Unit Installation and Operation Manual, Part No. 8828747 Effective April 13, 2020...
  • Page 39: Zb38Kce Single-Phase, 208/230 V Compressor Data Chart

    Nominal Performance Values (± 5%) based on 72 hours run-in. Subject to change without notice. Current @ 230 V. ©2016 Emerson Climate Technologies, Inc. Printed 1/11/2016 Autogenerated Compressor Performance 04-1308 Mueller E-Star OESE 3.5 and 5 HP HFC Condensing Unit Installation and Operation Manual, Part No. 8828747 Effective April 13, 2020...
  • Page 40: Zb38Kce Three-Phase, 208/230 V Compressor Data Chart

    Nominal Performance Values (± 5%) based on 72 hours run-in. Subject to change without notice. Current @ 230 V. ©2016 Emerson Climate Technologies, Inc. Printed 1/10/2016 Autogenerated Compressor Performance 04-1317 Mueller E-Star OESE 3.5 and 5 HP HFC Condensing Unit Installation and Operation Manual, Part No. 8828747 Effective April 13, 2020...
  • Page 41: Zb38Kce Three-Phase, 460 V Compressor Data Chart

    Nominal Performance Values (± 5%) based on 72 hours run-in. Subject to change without notice. Current @ 460 V. ©2016 Emerson Climate Technologies, Inc. Printed 1/10/2016 Autogenerated Compressor Performance 04-1317 Mueller E-Star OESE 3.5 and 5 HP HFC Condensing Unit Installation and Operation Manual, Part No. 8828747 Effective April 13, 2020...
  • Page 43: Section 16.0 - R-507 Pressure Temperature Chart

    126.90 60.56 141.00 67.39 153.30 -2.31 27.85 18.26 64.87 32.54 90.57 43.67 110.60 52.84 127.10 60.67 141.20 67.45 153.40 Mueller E-Star OESE 3.5 and 5 HP HFC Condensing Unit Installation and Operation Manual, Part No. 8828747 Effective April 13, 2020...
  • Page 45: Section 17.0 - E-Star Oese Installation Survey

    Provide the actual time below. Readings should be taken at five-minute intervals. Compressor Amperage Time* Measured Supply Voltage: Condensing Unit Model and Part No.: Serial No.: Mueller E-Star OESE 3.5 and 5 HP HFC Condensing Unit Installation and Operation Manual, Part No. 8828747 Effective April 13, 2020...