Lamp memory emergency call system
Hide thumbs Also See for NEM-10:

Advertisement

NBR-7AS Pull Cord and NBY-4AEM Corridor Lamp
The NEM-EM system provides communication from a central master station to multiple sub stations
(up to 80). A call from a standard room station is annunciated with a steady LED light and an
intermittent tone. An emergency call from a bathroom pull cord (NBR-7AS) is annunciated with a
flashing LED light and buzzer tone. A standard call can be reset at the master station. An emergency
call must be reset at the bathroom pull cord location.
WIRING DIAGRAM:
NEM-20EM
PS-45E
Individual Components for NEM-EM System:
NA-A:
Surface mount sub station
NA-AN:
Surface mount sub with privacy
NA-NE:
Flush mount sub, aluminum (backbox included)
NB-L:
Flush mount ceiling speaker sub station
NBY-4A/EM: Corridor lamp for NEM-EM system
PC-359B:
Call holding circuit board (required if standard sub stations are not used)
PS-24E:
24V DC Power Supply (for NEM-10EM, NEM-10AEM only)
PS-45E:
13.8V DC, 8A Power Supply (for 20, 30, 40-station masters)
IMPORTANT NOTES:
1. When wiring NA-A or NA-AN to NBR-7AS,
install diode (1N4001~4007) as shown above.
2. If no corridor lamp is included with NA-A/AN,
leave jumper between D and E attached.
3. If corridor lamp is installed with NA-NE or NB-L,
separate Green and Black wires, and connect
Blue and Black wires together.
NEM-EM
NEM Lamp Memory Emergency Call System
NEM-nEM Master Station
- INSTRUCTIONS -
+
-
NBY-4A/EM
1
Blu Blu
2
3
~
20
Remove
jumper
E
M
S
S
D1: Value
1N4001~4007
NA-A
NA-AN
NBR-7AS
A
Red
D1
D
E
Blu
Blk
Jumper blue and
black wires when
corridor lamp is
used.
NEM-EM TERMINAL DEFINITIONS:
+
Positive (24V DC for NEM-10EM; 13.8V DC
for NEM-20~40EM)
-
Negative
1~40
Station number
E
Common communication
M
Common for Emergency Call Signal
Special
Order
Products
NB-L
NBR-7AS
NA-NE
Red
Red
Org/
Wh
Grn
Grn
Blk
Blk
Jumper green
and black wires
when corridor
lamp is not used.
Pg. 1

Advertisement

loading

Summary of Contents for Aiphone NEM-10

  • Page 1 NEM Lamp Memory Emergency Call System NBR-7AS Pull Cord and NBY-4AEM Corridor Lamp The NEM-EM system provides communication from a central master station to multiple sub stations (up to 80). A call from a standard room station is annunciated with a steady LED light and an intermittent tone.