Summary of Contents for Lindab Carat 31

  • Page 1 | we sim pli fy c ons tr u ction Carat Service & maintenance © 04.2021 Lindab Ventilation. All forms of reproduction without written permission are forbidden. is the registered trademark of Lindab AB. Lindab's products, systems, product and product group designations are protected by intellectual property rights (IPR).
  • Page 2: Service And Maintenance

    1.0 Installation 1.1 Product description Lindab’s chilled beam Carat is placed above a perforated suspended ceiling and supplies cooling, with a low air velocity, to the room below. Carat has a high radiation quotient of approx. 35% (compared to approx. 5% for traditional finned products).
  • Page 3 Mount a push-on fitting to the pipe. Make sure to press the fitting all the way onto the pipe. Consult the installation guide for the specific fitting for further details on proper installation. Push-on fitting Lindab reserves the right to make changes without prior notice 2021-04-15...
  • Page 4 Crocked or in other ways imperfect pipe ends will result in leaks. Deburr the pipe on the inside and the outside, using a deburr- ing tool before installation Lindab reserves the right to make changes without prior notice 2021-04-15...
  • Page 5 – Both flow and return pipe is covered by a plastic or rubber protection cover, which should be removed before installation. Lindab reserves the right to make changes without prior notice 2021-04-15...
  • Page 6 Push-on fitting Push-on valve Notice! The connection pipes are internally soft-welded why it’s not allowed to solder the beam to the pipes. Lindab reserves the right to make changes without prior notice 2021-04-15...
  • Page 7 Mark: Marking noted on order. – Nozzles: Number of nozzles. – Plugs: Number of plugged nozzles. – Product ID: Product number. – Sign: To be signed when checked and commissioned on site. Lindab reserves the right to make changes without prior notice 2021-04-15...
  • Page 8 ALWAYS handle the product from either the suspension bar, the pipe mani- fold or the bottom of the ‘A’ profile. Take care not to damage cooling fins or pipe tails. Lindab reserves the right to make changes without prior notice 2021-04-15...
  • Page 9 This means the maximal working pressure for the products at a water temperature of 20°C must not exceed 10 bar. 4.4 Water quality Lindab recommend water treatment and quality to be according to VDI 2035-2. – The water preparation and maintenance for the chilled beam water circuit should be handled by a specialist –...
  • Page 10 Änderungen vorbehalten. IT - Qui potete trovare istruzioni di montaggio, informa- zioni sul prodotto ed un supporto tecnico qualificato Tel. 011 9952099 - e-mail: lindab@lindab.it www.lindab.it Soggetto a modifica senza obbligo di preavviso. FR - Vous trouverez les fiches produits ou de montage actualisées ainsi que les coordonnées du support télépho-...

This manual is also suitable for:

Carat 44Carat 58Carat 71Carat 84Carat series