Polon-Alfa ASG-2001 Installation And Maintenance Manual

Polon-Alfa ASG-2001 Installation And Maintenance Manual

Autonomous gas detectors

Advertisement

IK-E366-001
1
AUTONOMOUS
GAS DETECTORS
TYPE ASG-2000
Installation and Maintenance Manual
IK-E366-001
Edition IA

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ASG-2001 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Polon-Alfa ASG-2001

  • Page 1 IK-E366-001 AUTONOMOUS GAS DETECTORS TYPE ASG-2000 Installation and Maintenance Manual IK-E366-001 Edition IA...
  • Page 2 Failure to follow the instructions of this manual may be dangerous or cause violation of applicable regulations. The Polon-Alfa manufacturer is not liable for damages resulting from use contrary to this instruction. A worn out product, not suitable for further use, should be transferred to one of the entities dealing with the collection of waste electrical and electronic equipment.
  • Page 3: Intended Application

    Thanks to the built-in temperature compensation, detectors can work in changing environmental conditions. Information about the installed sensor module together with the alarm threshold values can be found on the detector housing. Table 1: Selection of ASG-2000 detectors. Model ASG-2001 ASG-2001HV ASG-2002 ASG-2002HV ASG-2003 ASG-2003HV...
  • Page 4: Technical Data

    Power consumption max 3 W max 60 mA@24 V ASG-2001: A1 = 10% A2 = 20% A3 = 30% LEL methane (selective) ASG-2002: A1 = 10% A2 = 20% A3 = 30% LEL propane-butane (50/50) Alarm thresholds ASG-2003: A1 = 30 ppm CO (TWA 15 min.) A2 = 60 ppm CO (TWA 15 min.)
  • Page 5: Structure Description

    IK-E366-001 4. STRUCTURE DESCRIPTION. Jumper for selecting the common contact function TEST button TEST button Jumper for selecting the A3/FLT output function Sensor cover Power terminals and signal outputs Gas sensor module Figure 1 The detector after removing the cover. Figure 1 shows the interior view of the detector.
  • Page 6: Functional Description

    The default setting is to connect the common relay contacts to the V1 contact. The signalling diodes are marked in Figure 1. The ASG-2001 and ASG-2002 detectors on the sensor module include a cover with an anti-dust filter that protects not only against dust but also against small insects. In the ASG- 2003 detector, the sensor is insulated directly to the ventilation element.
  • Page 7: Place Of Installation

    IK-E366-001 ALARM CONTACT OUTPUTS STATUS Terminal A1 Terminal A2 Terminals A3/FLT ALARM LEVEL 2 CLOSED CLOSED opened opened opened ALARM LEVEL 3 CLOSED CLOSED CLOSED opened opened DETECTOR'S FAILURE opened opened opened CLOSED opened SENSOR'S FAILURE opened opened opened CLOSED opened POWER FAILURE opened...
  • Page 8: Mounting Position

    IK-E366-001 6.2. Mounting position. Detectors of the ASG-2000 series are recommended to be installed in a vertical position with the gas inlet down, this position guarantees the best protection against dust and splashes of water. In the case of methane detectors, due to the mounting height, a horizontal position (increased susceptibility to dust accumulation in the gas inlet element) or ceiling mounting is possible although not recommended.
  • Page 9 (applies only to detectors ASG-2001 and ASG-2002). Lack of the sensor cover reduces the protection of the housing to IP43, and detector operation without the sensor cover is not allowed. For ASG-2003 detectors, check whether the sensor insulation has been damaged.
  • Page 10 IK-E366-001 7. OPERATION AND SERVICE CONDITIONS. In accordance with the Regulation of the Minister of Interior and Administration of April 21, 2006 on the fire protection of buildings and other construction facilities 2006 No. 80, item 563, technical inspection and maintenance of gas detection systems ought to be conducted at least once a year. Periodic inspection is recommended to be carried out once every 3 months and after the occurrence •...
  • Page 11: Testing Detectors

    ASG-2003 containing 100 ÷ 200 ppm CO for a time suitable for triggering alarm A1 or A3, • for ASG-2001 and ASG-2002 containing> 20% LEL of gas detected until the alarm is triggered. When detecting a small amount of gas, the POWER diode is permanently lit with short stops every 2.5 seconds, allowing the test to be performed in a shorter time and not subjecting the sensors to a significant concentration of gas.
  • Page 12: Storage And Transport

    IK-E366-001 9.2. Work at heights. Work at heights related to the installation of detectors should be carried out with extreme caution when using efficient equipment and tools. Special attention should be paid to the stability of ladders, lifts, etc. Power tools should be used with observance of the conditions of their safe operation specified in the relevant manufacturer's instructions.