TECHNICAL CHARACTERISTICS
MAINS VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERY (Ni-Cd)
BATTERY PROTECTION
INDICATIONS/ CONTROL
RECHARGING TIME
MINIMUM EMERGENCY DURATION
LIGHT SOURCE INTENSITY (230V) / (emerg.)
VIEWING DISTANCE
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIALS
EXTERNAL DIMENSIONS (LxWxH)
TYPICAL WEIGHT
GUARANTEE
GENERAL
These luminaires are used indoors (ta 40 C)
where emergency light is needed.
E a c h l u m i n a i r e m u s t b e p e r m a n e n t l y
connected to mains power supply.
In normal operation the led strip lights and the
battery is charging.
In case of a mains power supply failure
the
luminaire
automatically in emergency mode (powered
by its battery).
When the
supply is restored the device turns to normal
operation.
INSTALLATION
To install the illumination sign you must
follow the installation instructions on pages
3,4,5 and 6.
NON
MAINTAINED
OPERATION
There is an option to select the non maintained
or maintained operation by placing the jumper to
the appropriate place according to the
procedure on page 4.
Page 1 from 6
MAINTAINED EDGE EMERGENCY
ILLUMINATION SIGN WITH LEDS
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3, EN 1838
Thank you for your trust in our products.
Olympia Electronics - European manufacturer.
will
light the led strip
mains
/
MAINTAINED
selection
(
for LED MODULE Specs. see page 2)
220-240V AC/50-60Hz
Overcharging and deep discharging protection
Charge LED / Test button
Aluminum, plexiglas, ABS/PC
3 years (1 year for the battery)
Test Button Function -
As the luminary is in normal operation, by pressing
o
the test button and holding it you can check the
emergency operation of the luminary When you
stop pressing the button the luminary returns to
normal operation.
conducted only if the mains power supply and
the battery is connected.
Indication LED status (with connected
mains power supply).
power
Charge
On: Good charge condition.
Οff: No battery (No charging current
or disconnected battery).
INDICATORS/CONTROLS
CHARGE
LED
CLD-30/NST
3.5W / 3.7VA
3.6V/1.0Ah
24h
3h
45lm / 95lm
30m
IP40
o
5
to
40 C
Up to 95%
310x240x51mm
1060gr.
Manual Test
,
,
The manual test can be
TEST
BUTTON
922503001_09_001
.

Advertisement

loading

Summary of Contents for olympia electronics CLD-30/NST

  • Page 1 1060gr. TYPICAL WEIGHT 3 years (1 year for the battery) GUARANTEE Thank you for your trust in our products. Olympia Electronics - European manufacturer. Manual Test Test Button Function - GENERAL As the luminary is in normal operation, by pressing...
  • Page 2 In case of battery or led strip LED MODULE CHARACTERISTICS CLD-30/NST Olympia Electronics S.A. Manufacturer Model Number 2602185/15LED 2,8-3,3V DC Voltage Range Nominal Power Plug in connection (take care of orientation between the main pcb and led module) Connections 40 °C max.
  • Page 3: Installation Instructions

    INSTALLATION INSTRUCTIONS ELECTRICAL CONNECTIONS 1. Dismantle the luminaire by pushing the lock/unlock button and slide the luminaire to the right and pull it down. 2. Pass through the cables from the entry hole and connect them as shown on the picture. The battery must be connected (see the battery installation process on page 4).
  • Page 4 BATTERY INSTALLATION AND REPLACEMENT PROCESS 1. Dismantle the luminaire step 1 of the installation instructions (page 3). Unfasten the 2 screws, and gently remove the plastic base from the aluminum profile. 2. Unfasten the 2 screws without moving the marking panel. 3.
  • Page 5: Mounting Methods

    MOUNTING METHODS FLAG MOUNTED ON A WALL A-1133 SET (OPTIONAL AFTER REQUEST) Cable entry hole Place the included mounting screws for the flag mounting base SURFACE MOUNTING ON A WALL (single side luminaire) A-1134 SET (INCLUDED IN THE PACKAGE) Place the included mounting screws in these holes of the plastic bracket If necessary place the included spacers to mount the base.
  • Page 6: Hanging Installation

    Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the buyer the transportation cost.