1100R SERIES
WIRELESS REPEATER
Installation Guide
WALL
TAMPER
ENABLE
DISABLE
Figure 1: 1100R Wireless Repeater
DESCRIPTION
The 1100R Series Wireless Repeaters
provide an increased communication
range by forwarding messages
from the transmitter to the wireless
receiver. The 1100RE features
128‑bit AES encryption.
Up to eight repeaters can be installed
on a wireless system. The repeater
is powered from a 12 VDC power
supply and includes a 24‑hour battery
backup.
Compatibility
•
All DMP 1100 Series Wireless
Receivers using Version 106 or
higher software.
•
All DMP panels with a built‑in
wireless receiver.
•
Encryption requires panel
version 183 or higher and wireless
receiver version 300 or higher.
•
The 1100R is not compatible with
the 1100T Wireless Translator
What is Included?
•
1100R Repeater
•
800 mAh Lithium Polymer
Rechargeable Battery
•
376L Plug‑In DC Power Supply
•
Hardware Pack
1
PROGRAM THE PANEL
Refer to the panel programming guide as needed. See links in
After completing each of the following steps, press CMD to
advance to the next option.
BAT
XTLplus and
XTLtouch
XT50 with built‑in
receiver
XT30 and XT50
(1100D Series)
XR150 (1100X Series)
XR550 (1100X Series)
2
ENABLE OR DISABLE THE TAMPER
The 1100R is equipped with a case and wall tamper. When the
housing cover is removed, the case tamper activates and the 1100R
sends a tamper trouble to the panel.
A two‑position header is provided to enable or disable the wall
tamper. To enable the tamper, place the jumper on the top two pins.
To disable the tamper, place the jumper on the bottom two pins.
1.
Reset the panel. At a keypad, enter 6653 (PROG) to access
the PROGRAMMER menu.
2.
In ZONE INFORMATION, enter the wireless zone number
from the table below. If using multiple repeaters, they must
be programmed as sequential zone numbers.
Available
DMP Panel
Zones
99
48
32
100
500
At *UNUSED*, enter the name of the repeater or repeater's
3.
location for easy identification later.
4.
Select AUX 1 (auxiliary 1) as the ZONE TYPE.
At WIRELESS? select YES.
5.
At SERIAL NO, enter the repeater's eight‑digit serial number.
6.
7.
At SUPRVSN TIME, enter a supervision time. Default is 240.
8.
At the NEXT ZONE prompt, select NO for more
programming options.
9.
Program ARMED OPEN and DISARMED OPEN as TROUBLE
so that a power trouble sends a trouble alert.
10. Program ARMED SHORT and DISARMED SHORT as ALARM
so that a tamper sends an alarm alert.
11. Press CMD until STOP displays. Press a top row select key or
area to save programming.
Zone Ranges
1 ‑ 99
11 ‑ 14, 21 ‑ 24, 31 ‑ 34, 41 ‑ 44, 51 ‑ 54,
61 ‑ 64, 71 ‑ 74, 81 ‑ 84, 80, 85 ‑ 99
11 ‑ 14, 21 ‑ 24, 31 ‑ 34, 41 ‑ 44, 51 ‑
54, 61 ‑ 64, 71 ‑ 74, 81 ‑ 84
500 ‑ 599
500 ‑ 999