Thermotronik TT-77 1 Introduction 1.1 Intended Use The display and control unit is used to monitor the temperature in fluid systems. The level switch must not be used in highly flammable or corrosive liquids. Please note the technical data in the appendix for the specific intended use, existing material combinations, as well as temper- ature limits.
Thermotronik TT-77 2 Safety instructions 2.1 Important advice Operation of the device is only valid if: – the product is used under the conditions described in the installation- and operation instruction, the intended application according to the type plate and the intended use. In case of unauthorized modifications done by the user Bühler Technolo- gies GmbH can not be held responsible for any damage, –...
Thermotronik TT-77 2.2 General hazard warnings The equipment must be installed by a professional familiar with the safety requirements and risks. Be sure to observe the safety regulations and generally applicable rules of technology relevant for the installation site. Prevent malfunctions and avoid personal injuries and property damage.
Thermotronik TT-77 3 Transport and storage Only transport the product inside the original packaging or a suitable alternative. The equipment must be protected from moisture and heat when not in use. It must be stored in a covered, dry, dust-free room at room temperature.
Thermotronik TT-77 4 Setup and connection DANGER Electric voltage Risk of electric shock a) Always disconnect the unit from the mains before performing work. b) Secure the equipment from accidental restarting. c) The equipment may only be installed, maintained and put into operation by instruc- ted, competent personnel.
Thermotronik TT-77 5 Operation and control NOTICE The device must not be operated beyond its specifications. 5.1 Start-up procedure The device will automatically switch on when connected to power. It will first briefly display the software version, at which time the device will also check the built-in components.
Thermotronik TT-77 5.3 General key functions The keys below the display are used for operation. The menu controls are detailed in the following chapters. Mode Function – Measurement display: Toggles the display unit. – In the menu: Move down one menu level.
Thermotronik TT-77 5.5 Menu overview The menu structure is based on the VDMA standard sheet 24574-1. The menu structure is hierarchic. The top menu level contains the main menu items, e.g. tEMP, F, diA, E. Each main menu has additional submenu items.
Thermotronik TT-77 5.6 Changing basic settings The general basic settings can be changed under menu Basic Settings Extended Functions (bEF). These settings will affect the measurement display and the configuration options in the various main menus. Here you can also change the switching output assignment.
Thermotronik TT-77 5.6.3 Set supply cable length (wall mounting - optional) For accurate temperature measurement when installed with remote display, the supply line length and cross-section must be entered to calculate the compensation of the lead resistance. The lead length should be changed in the following menu: b.
Thermotronik TT-77 5.6.6 Set display refresh rate The refresh rate of the display can be changed based on the application. The display can also be completely disabled. The LEDs will remain functional. b. E F Display Rate Selection menu ____ Basic EF Basic Adv.
Page 17
Thermotronik TT-77 The factory settings are: Definitions: SP x Switching point / switch-back point x ds x Switch-on delay / switch-back delay for switching output x A x . . H i Ax. L o Maximum and minimum measurement for output A.
Thermotronik TT-77 Diagnostic settings: Diagnostics SJ. o u out1 dt. M M 0. 0 5.7 Switching outputs All switching outputs are configured the same way. The switching output number is therefore represented by x. Open the switching output to be configured from the menu for the respective measured variable.
Thermotronik TT-77 Example: F ILo = 15 °C, F IHi = 80 °C Frequency output If the output is defined as a frequency output, a with temperature T and frequency f: square wave signal with a frequency between 1 Hz and 100 Hz proportional to the measurement will be T ≤...
Thermotronik TT-77 5.7.3 Switching output x: Lower switching limit (switch-back point) The lower switching limit for switching output Out x can be defined with the following submenu: ____ Out X out_ ____ Selection menu ____ Measured variable rPI FLI F I. L o [ o.
Thermotronik TT-77 5.7.6 Switching output x: Testing the switching output The switching output test can be started with the following menu: ____ Out X Check Out X Measured variable out_ EF X C. o u_ Selection menu ____ Settings menu OUTX...
Thermotronik TT-77 Factory setting Status function State Status LED 3 inverted Temperature rises to > 70 °C PNP switching output 3 closed LED3 ON LED3 OFF Temperature rises to > 80 °C Error PNP switching output 4 closed LED4 and LED3 ON only LED4 ON Temperature falls to <...
Thermotronik TT-77 5.8.2 Analogue output x: Lower limit assignment Used to configure at which temperature to output the minimum analogue signal. This is configured in menu: ____ Analog OutX Analog MinX A I. L o Selection menu ____ Measured variable Settings menu Analog X [ o.
Thermotronik TT-77 5.9 Diagnostic options The device is able to log events for a switching output. The LED lighting up is considered an event. The logging of switching pro- cedures therefore depends on how the LED switching function is configured.
Thermotronik TT-77 5.9.2 Maximum and minimum temperature Used to view or delete the saved maximum and minimum temperature: Diagnostic Max/Min Temp t. M M ____ Selection menu ____ - --- Diagnostics menu Max/Min Memory The journal entries will be displayed as: Example: –...
Thermotronik TT-77 6 Cleaning and Maintenance This device is maintenance-free. The method for cleaning the devices must be adapted to the IP protection class of the devices. Do not use cleaners which could damage the device materials. Bühler Technologies GmbH...
Thermotronik TT-77 7 Service and repair This chapter contains information on troubleshooting and correction should an error occur during operation. Repairs to the unit must be performed by Bühler authorised personnel. Please contact our Service Department with any questions: Tel.: +49-(0)2102-498955 or your agent If the equipment is not functioning properly after correcting any malfunctions and switching on the power, it must be inspected by the manufacturer.
Thermotronik TT-77 Possible errors Problem / Malfunction Possible cause Action Switching output not trigger- – Switching output configured incorrectly – In submenu Coux: “Test Switching Output“ to ing when exceeding limits ensure normal mode – Switching output defect – In submenu Coux: “Test Switching Output” to...
Thermotronik TT-77 8 Disposal Dispose of parts so as not to endanger the health or environment. Follow the laws in the country of use for disposing of elec- tronic components and devices during disposal. BE140013 ◦ 07/2019 Bühler Technologies GmbH...
Thermotronik TT-77 9 Appendices 9.1 Technical Data TT-77 Material / Version Housing swivels by min. 270° Version M12x1 Operating pressure max. 5 bar max. 10 bar Operating temperature -40°C to +100°C -40°C to +100°C Lengths 280, 370, 500 mm (standard) vari- LEDs able from 70 to max.
Page 31
Thermotronik TT-77 -1T-KT -2T-KT -4T-KT Plug (base) M12 – 4-pin M12 – 5-pin M12 – 8-pin Switching outputs 1x freely programmable 2x freely programmable 4x freely programmable Alarm memory with 1 x assignable to alarm with 1 x assignable to alarm...
Thermotronik TT-77 9.2 Technical Data TT-77W Material / Version M12x1 Version Operating pressure max. 5 bar max. 10 bar Operating temperature -40°C to +100°C -40°C to +100°C LEDs Lengths 280, 370, 500 mm (standard) vari- able from 70 to max. 1000 mm...
Thermotronik TT-77 9.5 Current settings Switching outputs Basic Settings Diagnostics o. u ni SJ. o u t. u ni dt. M M o. H i o. L o r. o u1 r. o u2 r. o u3 r. o u4...
Thermotronik TT-77 9.7 Menu Sequence Overview Main menu Submenu 1 Submenu 2 Submenu 3 Settings and Display Menu Configuration t___ Equipment configuration Shortcut ____ Display ____ or 60s no action: Measurement display Exit main/submenu Temperature ____ Out 1 out1 ____...
Thermotronik TT-77 9.8 Display resolution Range x = |Max - Min| °C, °F none (non1) (up to 1 decimal place) (1 fixed-point number) Range x Resolution Range x Resolution x < 50 x < 50 50 <= x < 100 50 <= x <...
Page 40
RMA-Formular und Erklärung über Dekontaminierung RMA-Form and explanation for decontamination RMA-Nr./ RMA-No. Die RMA-Nummer bekommen Sie von Ihrem Ansprechpartner im Vertrieb oder Service./ You may obtain the RMA number from your sales or service representative. Zu diesem Rücksendeschein gehört eine Dekontaminierungserklärung. Die gesetzlichen Vorschriften schreiben vor, dass Sie uns diese Dekontaminierungserklärung ausgefüllt und unterschrieben zurücksenden müssen.