Aereco S-PRE/DAY-NIGHT/T Installation And Maintenance Instruction page 4

Modbus sensor hub 8 se - accessories & third party modbus system

Advertisement

B
A
C
D
Modbus address rotary switch for selecting
sensors ( on the sensor's PCB)
2
4
3
TF6582_A_NOT_INST_PRE_SENSOR_MODBUS
4. DIMENSIONS
5. THE S-PRE/DAY-NIGHT/T CONNECTIONS WITH HUB 8 SE
5.1. SETTING OF THE S-PRE/DAY-NIGHT/T SENSOR FOR HUB 8 SE
8 indexation positions are allowed for every sensor (Occupancy or CO
E
included.
F
Important: Before to start the heat recovery unit, every sensor must have a specific
0
identification number (1 to 8) so that the system can identify them. This index number has to
be different from a sensor to another one. The index numbers must be incremented to each
other so that there is no digit jump.
Example:
· Presence sensor bedroom A = 1 / because Hub SE outlet n°1 is connected to bedroom A.
· Presence sensor bedroom B = 2 / because Hub SE outlet n°2 is connected to bedroom B.
· Presence sensor bedroom C = 3 / because Hub SE outlet n°3 is connected to bedroom C.
· CO
sensor in living room = 4 / because Hub SE outlet n°4 is connected to living room.
5
2
Note: the sensors are delivered in position 0. They must be manipulated with extreme care.
The supply power and data are transmitted through the Hub SE ModBus communication
Ø80
4 / 10
34
31
): position 1 to position 8
2
Aereco S.A.