SFC 16-125 - Fuel Conversion to Natural
Gas (LP to NG) Kit P-807
 
Note
If converting from   N atural Gas to Propane, order the Propane conversion parts kit (IBC Part # P-806) from your 
authorized IBC distributor.
Use the Natural Gas conversion parts kit if the fuel source at the site uses Natural Gas and the unit has been set up 
(factory fire-tested) to operate with Propane. Check the rating plate on the unit to see which fuel source the particular unit 
has been set up with.
Using this conversion kit, a qualified technician will need to:
 1.  Perform a fuel conversion.
 2.  Perform a combustion test.
 3.  Fill in the information required on the fuel conversion labels, and affix them to the unit after the conversion is 
completed.
Warning
This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer's 
instructions and all applicable codes and requirements of the authority having jurisdiction. If the information in 
these instructions is not followed exactly, a fire, an explosion or production of carbon monoxide may result 
causing property damage, personal injury or loss of life. 
The qualified service agency is responsible for the proper installation of this kit. The installation is not proper 
and complete until the operation of the converted appliance is checked as specified in the manufacturer's 
instructions supplied with the kit.
The unit will automatically de-rate the maximum input at a rate of approximately 2% per 1,000' above 4,500'. The gas 
valve's zero-governor will ensure that the gas-air mixture is not affected at altitude.
Included with the conversion kit:
1 x Orifice - Marked 450 - IBC Part # 180-228
1 x O-ring - IBC Part # 150-175
1 x Rating Plate Fuel Overlay - IBC Part # 080-247
1 x Gas Valve Conversion Label - IBC Part # 080-107
1 x Installer Identifier Label - IBC Part # 080-245
120-245E-R1
| 1

Advertisement

loading

Summary of Contents for IBC INTERGAS SFC 16-125

  • Page 1 SFC 16-125 - Fuel Conversion to Natural Gas (LP to NG) Kit P-807   Note If converting from   N atural Gas to Propane, order the Propane conversion parts kit (IBC Part # P-806) from your  authorized IBC distributor. Use the Natural Gas conversion parts kit if the fuel source at the site uses Natural Gas and the unit has been set up  (factory fire-tested) to operate with Propane. Check the rating plate on the unit to see which fuel source the particular unit  has been set up with. Using this conversion kit, a qualified technician will need to:  1.  Perform a fuel conversion.  2.  Perform a combustion test.  3.  Fill in the information required on the fuel conversion labels, and affix them to the unit after the conversion is  completed. Warning This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer’s  instructions and all applicable codes and requirements of the authority having jurisdiction. If the information in  these instructions is not followed exactly, a fire, an explosion or production of carbon monoxide may result  causing property damage, personal injury or loss of life.  The qualified service agency is responsible for the proper installation of this kit. The installation is not proper  and complete until the operation of the converted appliance is checked as specified in the manufacturer’s  instructions supplied with the kit. The unit will automatically de-rate the maximum input at a rate of approximately 2% per 1,000’ above 4,500’. The gas  valve's zero-governor will ensure that the gas-air mixture is not affected at altitude.
  • Page 2 Combustion Test Target Ranges Figure 1 Gas valve and fan The Low Fire (zero-offset) valve adjustment cap on the gas valve has been factory set. Do not adjust this screw in the field  unless indicated   i n these instructions.  After converting the unit to natural gas, a combustion (CO ) reading must be taken by a qualified technician using properly  functioning and calibrated combustion analyzing equipment and the results compared to the values in Table 1. Value (%) at High Fire with front cover Value (%) at Low Fire with front cover Natural Gas open open Max. CO  value 10.1% Actual Value at High Fire ...
  • Page 3: Fuel Conversion Instructions

    Alternative Naturel Gas Orifice - calorific values between 750-900 BTU/FT To perform a fuel conversion:  1.  Turn off the gas supply at the manual gas valve.  2.  Disconnect the electrical power.  3.  Disconnect the nut at the gas valve outlet (top of the gas valve), and remove the O-ring and orifice.  4.  Insert the correct orifice into the O-ring, and re-install into the nut at the gas valve outlet (top of the gas valve),  and then tighten the nut.  5.  Restore the gas supply by opening the gas control valve.  6.  Test for leaks by using an approved leak detection solution on all joints.  7.  Power on the unit. Now, carefully follow the procedures on Combustion Testing and Adjustment. SFC 16-125 - Fuel Conversion to Natural Gas (LP to NG) Kit P-807...
  • Page 4 Combustion Testing and Adjustment Danger A combustion test checks that the gas valve is operating properly in the field. To perform a combustion test, you  must be a qualified, trained and licensed gas fitter. Making adjustments to the gas valve without a properly calibrated gas combustion analyzer and by people who  are not trained and experienced in its use is forbidden. Failure to use an analyzer can result in an immediate  hazard. Model Number High Fire Input SFC 16-125 125 MBH Table 4 Rated input of a converted unit Normal ignition system sequence of operation: The unit's control, upon a call for heat or DHW, turns on the combustion fan for a 5-second pre-purge, then energizes the  spark electrode and gas valve for a 5-second trial for ignition. If the burner does not light, the process is repeated until the burner lights and flame is detected. After 4 unsuccessful trials  for ignition, the unit locks out and will need to be manually reset by pressing the Return Arrow   button.  To perform a combustion test and adjustment:  1.  Turn off the unit’s manual gas valve.   2. ...
  • Page 5  c.  When finished, replace the Low Fire cap, and leave the manual mode by pressing + AND -  simultaneously.  7.  Switch off the unit by pressing the space above the dot.   8.  Turn off the gas at the unit's manual gas valve.  9.  Remove the flue gas analyzer from the test port, and reinstall the test port cap.   10.  Remove the gas pressure manometer from the gas valve, and fully close the test port.  11.  Turn on the gas at the unit’s manual gas valve.  12.  Ensure there are no gas leaks before reinstalling the front cover.   13.  Turn on the unit by pressing the space above the dot. Completing and Affixing the Conversion Labels  1.  Fill in the conversion labels (included in the kit) associated with the new fuel type.  2.  Place the conversion labels onto the unit at the positions indicated on the last page.  SFC 16-125 - Fuel Conversion to Natural Gas (LP to NG) Kit P-807...
  • Page 6 Clocking the Meter (for Natural Gas only)  1.  Turn off all other appliances and pilots  2.  Turn on the unit and set the unit to high fire.  3.  Ensure the unit has a large load to heat, so that the unit will not shut off.  4.  With a Stop-Watch, record the number of seconds for the smallest dial to make 1 full revolution.  5.  CFH = (3600 x Dial Size) / Seconds  6.  CFH x 1000 (check local Btu content) = Input Btu’s.   Note For 2 PSI meters multiply CFH x 1.097 For Metric meters multiply CFH x 35.3 For 2 PSI metric meters multiply CFH x 1.097 x 35.3 For Altitude above 4,500' deduct 2% per 1,000’ of altitude from the Input Btu’s.
  • Page 7 Where to Place Conversion Labels on the Unit   SFC 16-125 - Fuel Conversion to Natural Gas (LP to NG) Kit P-807...