This document covers the following filter types: • RFI - filters on the input side, and ® • dU/dt - filters and sine - filters on the output side of the VACON NX AC drive. Safety notice WARNING: All internal components and component boards, with the exception of the galvanically separated input and output terminals are connected to high voltage when the AC drive is connected to the mains.
Page 5
The galvanically coupled interference may have to ® be filtered in order to achieve EMC compliance. The VACON NX range of AC drives contain an internal filter for bringing the drives into compliance with the standard (specifically IEC 61800- 3:2004).
5 = 520 V 6 = 690 V 0012 = Maximum current [A] DUT = filter type RFI = radio frequency filter DUT= du/dt-filter SIN = sinusoidal filter 7118_uk ® Figure 1. Type code for VACON NX filters Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/...
2.1.1 General ® Table 1 shows the filters used to make the VACON NX range of AC drives comply with EN/IEC 61800-3 for the domestic and industrial environment, in case the basic drive does not comply. All enclosure sizes 4 - 9 comply with the requirements of EN/IEC 61800-3, ed 2 for the categories 1 and 2, the 690 V versions for category 3.
NX AC drives comply with the immunity requirements EN/IEC 61800-3; 2004, second environment as standard. Note that the filters RFI-0012-5-IP54 to RFI-0105-5-IP54 are designed to fit mechanically directly to the corresponding drive. All others are loose and must be connected to the drive separately.
Page 9
Filter types vacon • 9 Footprint RFI-filter types can be installed in two ways. Back installation procedure is shown in Figure 3 and side installation procedure is shown in Figure 4. 7120_00 Reference Reference Maximum screw length for AC Ø7 drive mounting;...
Page 10
• 10 Filter types 7121_00 Reference Reference Maximum screw length for Ø7 AC drive mounting; M6x16 minimum 20 mm Figure 4. RFI filter side installation Dimension data Detailed dimension drawings in Chapter 3.1. Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/...
Filter types vacon • 11 2.1.3 External RFI filter types The external filters must be mounted close to the input of the drive or drive system. Note that the cable layout must be such, that the maximum physical separation exists between the filter input and output cables.
Page 12
• 12 Filter types Installation recommendations: The motor cable must be kept as short as possible both inside and outside the enclosure. This means that the optimum location for the drive is close to the driven motor in wall mounted units or close to the cable conduit hole in enclosed units.
Page 13
Dimension data Table 6. External RFI filter dimension data Dimensions Weight Filter type Drawing V W X Z* m [kg] code number RFI-0130-5-0 70CMC10375 270 150 240 255 RFI-0150-5-0 70CMC10377 300 210 120 160 120 185 420 171 127 RFI-0250-5-0 70CMC10377 300 230 125 180 120 205 420 191 132 70CMC10376 RFI-0320-5-0...
• 14 Filter types dU/dt filters 2.2.1 General ® The VACON NX drives use IGBT transistors as an output element. These semiconductors create the correct voltage to the motor switching it at very high speed (4 - 6 kV/s) with an unloaded IGBT.
Page 15
Filter types vacon • 15 Voltage stress Incoming pulse U Reflected pulse U –Z Total Voltage = U (1+r)=2U 7123_uk Figure 6. Voltage pulse reflection The reflected voltage maximum value is 2 × DC-link voltage, in practice 1.8 ...1.9 × U DC. The voltage is fully developed at cable lengths >...
Page 16
Filters are chosen so that their rated current > drive rated current. They will thermally withstand ® the same overload specifications as the drive. For VACON NX there is only one range of filters, suitable for the voltage range from 380 to 690 V. The filters can also be used at lower voltages, if required.
Page 17
Filter types vacon • 17 Recommendations: Figure 8, Table 7 and Table 8 show the filter and motor requirements based on the nominal voltage level and IEC & NEMA motor standards. A 690V A 500V B 690V B 500V [µs] 7125_00 Figure 8.
• 18 Filter types 2.2.2 dU/dt filter types The available IP ratings are IP00, IP21 and IP54. Table 9. dU/dt-filter types Nominal Nominal Manufacturer's part Rated voltage, Power loss Filter type code current at current at IP class code 3~ [V AC] at 40°C [W]...
Page 19
Filter types vacon • 19 Suitability Table 10. Drive suitability for 200 V AC air-cooled drives Filter, Filter, 200 V AC drive Filter, IP00 class 200 V AC drive IP 21 class IP 54 class NX_0003-0012 2 DUT-0012-6-0 NX_0003-0012 2 DUT-0012-6-2-P DUT-0012-6-5-P...
Page 20
• 20 Filter types Table 12. Drive suitability for 690 V AC air-cooled drives Filter, Filter, 690 V AC drive Filter, IP00 class 690 V AC drive IP 21 class IP 54 class NX_0005-0010 6 DUT-0012-6-0 NX_0004-0010 6 DUT-0012-6-2-P...
Filter types vacon • 21 Table 14. Drive suitability for 690 V AC liquid-cooled drive Filter, Filter, 690 V AC drive Filter, IP00 class 690 V AC drive IP 21 class IP 54 class NX_0170-208 6 DUT-0210-6-0-P DUT-0280-6-0-S NX_0170-208 6...
Page 22
• 22 Filter types The S- type dU/dt filters are forced air cooled and require a 220 V AC power supply for their fans. The filter has a build-in thermal switch, which indicates if the filter temperature has exceeded the safe limits.
Page 23
Filter types vacon • 23 There are enclosure restrictions and details for selection and mounting when using UL listed accessories, IP00 dU/dt-filter models. These restrictions and details should be noted during the filter assembly. For details of drive selection and enclosure restrictions, see Table 15.
NOTE! The sine filters are designed for a switching frequency of 1.5 kHz for 690 V AC and 3.6 kHz for ® 500 V AC, which corresponds to the nominal switching frequency of VACON NX drives. It is safe to increase the switching frequency, but IT IS NOT ALLOWED TO DECREASE THIS VALUE below nominal, as there is a risk of overheating.
• 28 Filter types 2.3.2 Sine filter types Table 20. Sine filter type Nominal Nominal Manufacturer's part Rated voltage, Power loss Filter type code current at current at IP class code 3~[V AC] at 40°C [W] 40°C [A] 50°C [A]...
Page 29
Filter types vacon • 29 The available IP ratings are IP00 and IP54. Suitability Table 21. Drive suitability table for 200 V AC air-cooled drives 200 V AC drive Filter, IP00 class 200 V AC drive Filter, IP 54 class...
• 30 Filter types Table 23. Drive suitability table for 500 V AC and 690 V AC liquid-cooled drives Filter, IP 54 500 V AC drive Filter, IP00 class 500 V AC drive 690 V AC drive Filter, IP00 class...
Drawings and diagrams vacon • 51 dU/dt-filters in enclosed drive Figure 30 represents a dU/dt filter with drive and main switch in enclosure. The main dimensions of the drive are 2200 x 600 x 600 mm (HxWxD). This representation includes all dU/dt filters up to 600 A with or without drive in enclosure .
Page 50
• 52 Drawings and diagrams • In NFS_CHK is illustrated 2 x chokes up to 650 A each in a single enclosure with semicon- ductor fuses. The main dimensions of the drive are 2000 x 400 x 600 mm (HxWxD).
Page 51
Drawings and diagrams vacon • 53 Figure 32 represents a dU/dt filter with drives in enclosure. The main dimensions of the drive are 2200 x 800 x 600 mm (HxWxD). This representation includes all dU/dt filters up to 1500 A with or without drive in enclosure .
Page 52
• 54 Drawings and diagrams In Figure 33, there is two dU/dt filters in a single enclosure. The main dimensions of the drive are 2200 x 400 x 600 mm (HxWxD). This representation includes two dU/dt filters up to 600 A in single enclosure .
Page 53
Drawings and diagrams vacon • 55 Figure 34 represents a dU/dt filter with drive and main switch in enclosure. The main dimensions of the drive are 2000 x 400 x 600 mm (HxWxD). This representation includes all dU/dt filters up to 2x80 A or 1x210 A with or without drive in enclosure .
Page 54
• 56 Drawings and diagrams Figure 35 represents a dU/dt filter up to 1500 A in a single enclosure with control plate, control units, control auxiliaries and other accessories. The main dimensions of the drive are 2000 x 600 x 600 mm (HxWxD).
Drawings and diagrams vacon • 57 Safe operating area for dU/dt-filters The safe operating area for DUT-0280-6-0-S is shown in Figure 36 - assuming a cable capacitance of 750 pf/m. The values should be scaled in accordance with the actual cable capacitance.
Page 56
• 58 Drawings and diagrams The safe operating area for DUT-0420-6-0-S is shown in Figure 37 - assuming a cable capacitance of 800 pf/m. The values should be scaled in accordance with the actual cable capacitance. In case of multiple cables the capacitance is the sum of the cable capacitances.
Page 57
Drawings and diagrams vacon • 59 The safe operating area for DUT-0590-6-0-S is shown in Figure 38 - assuming a cable capacitance of 1700 pf/m. The values should be scaled in accordance with the actual cable capacitance. In case of multiple cables the capacitance is the sum of the cable capacitances.
Page 58
• 60 Drawings and diagrams The safe operating area for DUT-0820-6-0-S is shown in Figure 39 - assuming a cable capacitance of 1700 pf/m. The values should be scaled in accordance with the actual cable capacitance. In case of multiple cables the capacitance is the sum of the cable capacitances.
Page 59
Drawings and diagrams vacon • 61 The safe operating area for DUT-1250-6-0-S and DUT-1600-6-0-S is shown in Figure 40 - assuming a cable capacitance of 1700 pf/m. The values should be scaled in accordance with the actual cable capacitance. In case of multiple cables the capacitance is the sum of the cable capacitances.
• 62 Drawings and diagrams Output current for frequency operation P-type dU/dt filters 110% 100% 100 120 140 160 180 200 220 240 260 280 300 320 f [Hz] 7154_en Figure 41. P-type dU/dt filters output current derating as a function of output frequency...
Page 61
Drawings and diagrams vacon • 63 S-type dU/dt filters f [Hz] 7129_en Figure 42. S-type dU/dt filters output current derating as a function of output frequency Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/...
Page 62
• 64 Drawings and diagrams Sine filters 110% 100% f [Hz] 7155_en Figure 43. Sine filters output current derating as a function of output frequency Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/...
Page 63
Document ID: Vacon Ltd DPD01805C Member of the Danfoss Group Rev. C Runsorintie 7 65380 Vaasa Finland...