Download Print this page

Viega Basic Digital Setpoint Control II Product Instructions page 4

Advertisement

Product
Instructions
Troubleshooting
If the system is not operating correctly, first check that all
electrical connections have been made properly. Check
for power to all components (120 V and 24 V).
If the setpoint configuration is correct disconnect the
sensor and check its resistance. Replace the sensor if its
resistance value does not match the temperature in the
accompanying chart to the right.
301 N. Main, 9th Floor • Wichita, KS 67202 • Ph: 800-976-9819 • Fax: 316-425-7618 • www.viega.com
©2012, ProPress
®
, FostaPEX
®
, GeoFusion
Trak
, MANABLOC
, Radiant Wizard
, S-no-Ice
®
®
®
of Viega LLC; ProPressG
and ViegaPEX
PI-PR-560400 0412 (Basic Digital Setpoint Control II)
Viega... The global leader in plumbing, heating and pipe joining systems
®
, Seapress
®
MegaPress
®
, MegaPressG
®
, and Viega
, Snap Panel
, XL
and XL-C
are registered trademarks of Viega LLC. MiniBloc
®
®
®
®
are trademarks of Viega GmbH & Co. KG. RIDGID
Temp °F
-40
-30
-20
-10
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
210
220
230
240
250
®
are registered trademarks of Viega GmbH & Co. PureFlow
, Rapid Grid
®
is a registered trademark of RIDGID, Inc.
Resistance
Temp °C
Ohms
-40.0
851
-34.4
872
-28.8
893
-23.3
914
-17.7
935
-12.2
956
-6.6
977
-1.1
998
4.4
1019
10.0
1040
15.5
1061
21.1
1082
26.6
1103
32.2
1124
37.7
1145
43.3
1166
48.8
1187
54.4
1208
60.0
1229
65.5
1250
71.1
1271
76.6
1292
82.2
1313
87.7
1334
93.3
1355
98.8
1376
104.4
1397
110.0
1418
115.5
1439
121.1
1460
®
, Smart Connect
®
, Climate Panel
, ProRadiant
, PolyAlloy
, SmartLoop
®
, Climate Mat
®
, Climate
and Zero Lead
are trademarks
4 of 4

Advertisement

loading

This manual is also suitable for:

17029Digital setpoint control ii