Romutec romod-eco Series Technical Documentation/Instruction Manual
Remote controlled i-/o-devices containing digital and analog inputs and outputs for use in building automation and control systems with modbus rtu interface for din rail mounting
Do you have a question about the romod-eco Series and is the answer not in the manual?
Questions and answers
Summary of Contents for Romutec romod-eco Series
Page 1
Modbus RTU interface for DIN rail mounting romutec® Steuer- u. Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald Phone: +49 (0) 98 67/ 97 90-0...
D6 - Overview of Registers 8AO eco Module .................... 45 D7 - Overview of Registers which all modules have in common ............... 46 Rev 20.11.2019 V1.07 - Page 2 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
Copyright Copyright 19 romutec® Steuer- u. Regelsysteme GmbH. All rights reserved. Without the express written permission, this manual may not be reproduced, transmitted, transcribed, stored in a data recording system, or translated into any language or computer language, neither in whole or in part.
Doing so, parts inside the device might be damaged on contact. Basically, if you have any problems please contact the manufacturer. Rev 20.11.2019 V1.07 - Page 4 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
3 System description The romod-eco module family is a set of romutec® remote controlled Input-/Output-devices (remote I/Os) for mounting on DIN rails. It consists of various types of I/O modules. The connection to the MODBus master device is done via a RS485 connection. The communication takes place via MODBus RTU.
Communicating with the master (valid Orange flashing telegram received) flashing Faulty or unvalid telegram received Rev 20.11.2019 V1.07 - Page 6 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
4.2 Bus connection to MODBus master devices 4.2.1 Communication within MODBus master-slave systems For communication between a controller (DDC or PLC) and the romutec® Remote I/O devices, it is necessary to configure an RS485 interface of the controller as MODBus master with the serial port parameter settings 8, N, 1.
By means of this register, functions like the reset of all configuration registers can be triggered by sending a command to the device. Rev 20.11.2019 V1.07 - Page 8 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
24 V AC or DC, connection via terminals Current consumption: max. 150 mA (DC), 220 mA (AC), all DIs loaded Rev 20.11.2019 V1.07 - Page 9 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
Page 10
Bus connection Terminal No. I-GND Net A (–) aka /D Net B (+) aka D Rev 20.11.2019 V1.07 - Page 10 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
Inductive loads should be avoided as far as possible, or be suppressed at the source, respectively. Rev 20.11.2019 V1.07 - Page 11 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
Page 12
Bus connection Terminal No. I-GND Net A (–) aka /D Net B (+) aka D Rev 20.11.2019 V1.07 - Page 12 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
Inductive loads should be avoided as far as possible, or be suppressed at the source, respectively. Rev 20.11.2019 V1.07 - Page 13 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
Page 14
Bus connection Terminal No. I-GND Net A (–) aka /D Net B (+) aka D Rev 20.11.2019 V1.07 - Page 14 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
Using the settings in MODBus registers, you can select open circuit or closed-circuit principle for each input separately. Rev 20.11.2019 V1.07 - Page 15 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
Page 16
Bus connection Terminal No. I-GND Net A (–) aka /D Net B (+) aka D Rev 20.11.2019 V1.07 - Page 16 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
Inductive loads should be avoided as far as possible, or be suppressed at the source, respectively. Rev 20.11.2019 V1.07 - Page 17 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
Page 18
Bus connection Terminal No. I-GND Net A (–) aka /D Net B (+) aka D Rev 20.11.2019 V1.07 - Page 18 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
°C/10 (1000 = 100,0 °C) NTC 10k -50,0 °C 149,9 °C °C/10 (1000 = 100,0 °C) Rev 20.11.2019 V1.07 - Page 19 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
Page 20
Bus connection Terminal No. I-GND Net A (–) aka /D Net B (+) aka D Rev 20.11.2019 V1.07 - Page 20 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
10 mA each (short circuit proof) Resolution AO 10 Bit Linearity error < +/- 2% Rev 20.11.2019 V1.07 - Page 21 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
Page 22
Bus connection Terminal No. I-GND Net A (–) aka /D Net B (+) aka D Rev 20.11.2019 V1.07 - Page 22 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
0...70C Relative humidity 10...90%, non-condensing Protection class IP 20 Dimensions (for exact dimensions see appendix Rev 20.11.2019 V1.07 - Page 23 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
4 DO-R eco 8 AI eco 8 AO eco All dimensions in mm, weight in grams Rev 20.11.2019 V1.07 - Page 24 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
C) Wiring diagrams Fig. C-1 : romod 16 DI eco Rev 20.11.2019 V1.07 - Page 25 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
Page 26
Fig. C-2 : romod 8 DO eco Rev 20.11.2019 V1.07 - Page 26 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
Page 27
The signals to be switched must have the same phasing. Fig. C-3 : romod 8 DO-R eco Rev 20.11.2019 V1.07 - Page 27 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
Page 28
The signals to be switched must have the same phasing. Fig. C-4 : romod 4 DIO-R eco Rev 20.11.2019 V1.07 - Page 28 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
Page 29
Fig. C-5 : romod 4 DO-R eco Rev 20.11.2019 V1.07 - Page 29 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
Page 30
Fig. C-6 : romod 8 AI eco Rev 20.11.2019 V1.07 - Page 30 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
Page 31
Fig. C-7 : romod 8 AO eco Rev 20.11.2019 V1.07 - Page 31 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
8 AI rail mounted module, inputs active (0..10 V) and passive (RTD) configurable 8 AO eco 8 AO rail mounted module 0..10 V Rev 20.11.2019 V1.07 - Page 32 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
20 00 Inverting DI 14 40 00 Inverting DI 15 80 00 Inverting DI 16 Rev 20.11.2019 V1.07 - Page 33 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
Page 34
Delay = 100 ms (if activated using R1101) Delay = 40 ms (minimum recommended for 50 Hz AC signals) Rev 20.11.2019 V1.07 - Page 34 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
… … 00 80 DO 8 will be switched ON when safe state is triggered Rev 20.11.2019 V1.07 - Page 35 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
00 01 State of DO 1 … … … 00 08 State of DO 4 Rev 20.11.2019 V1.07 - Page 36 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
Page 37
Value not valid for DO 3 00 08 DO 3 will be interlocked by activating DO 4 Rev 20.11.2019 V1.07 - Page 37 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
Page 38
Minimum time for state 'on' (DO 1) … … R 3114 Minimum time for state 'on' (DO 4) Rev 20.11.2019 V1.07 - Page 38 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
Page 39
00 02 Inverting DI 2 00 04 Inverting DI 3 00 08 Inverting DI 4 Rev 20.11.2019 V1.07 - Page 39 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
Page 40
Delay = 100 ms (if activated using R1101) Delay = 40 ms (minimum recommended for 50 Hz AC signals) Rev 20.11.2019 V1.07 - Page 40 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
… 00 08 Setting in R 2121 determines DO 4 when Safe State is triggered Rev 20.11.2019 V1.07 - Page 41 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
Page 42
… … 00 08 DO 4 will be switched ON when safe state is triggered Rev 20.11.2019 V1.07 - Page 42 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
Delta value for the analog input AI 1 … … R 1598 Delta value for the analog input AI 8 Rev 20.11.2019 V1.07 - Page 43 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
Page 44
11 = NTC 20k °C/10 (1000 = 100.0°C) 12 = NTC 10k °C/10 (1000 = 100.0°C) Rev 20.11.2019 V1.07 - Page 44 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
R 2521 … … Safe state value for AO 8 (values 0...1000 0…10V) R 2528 Rev 20.11.2019 V1.07 - Page 45 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
R 4 is given in decimal, the unit is ‘seconds’. Bus timeout = 60 seconds Timeout and Safe State function disabled Rev 20.11.2019 V1.07 - Page 46 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
Page 47
R2 and R3, or it has been identified by the autobaud function. 1 … 4 Meaning of the values identical to register R2 Rev 20.11.2019 V1.07 - Page 47 Subject to modifications! romutec Steuer.-und Regelsysteme GmbH Jochsberger Straße 39 D-91592 Buch am Wald www.romutec.de Subject to technical changes...
Need help?