Liteplan CB5S/3W/M3 Assembly Instructions

Advertisement

Quick Links

CB5S/3W/M3
CB5S/3W/ST
Technical Specification:
-
Supply Voltage: 220-240V AC 50/60Hz
-
Insulation Class: II
-
Ingress Protection: IP65
-
Emergency Duration: 3 hours
-
Light Source: for M3 and ST version 3W
-
Battery 6.4V 3.0Ah LiFEPO4 for 3W M3 & ST
-
Battery Recharge Time: 12h
-
Max Battery Temperature: 55°C
-
Ambient Temperature: 0 - 40°C
-
Charge indicator: Green / Red LED
-
Deep Discharge Protection DDP
-
Self-Test version available
-
Surface assembly
-
Assembly indoors to flat surface
-
Polycarbonate body
-
Maintained or Non-Maintained Operation
Important:
It is recommended that the unit is installed by a competent person
ensuring the installation complies with the necessary standards. The
company accept no responsibility for incorrect installation, operation
or maintenance. The unit requires an unswitched supply for charging
the battery and a switched supply for a maintained unit. After
installation of the fitting, the battery must be charged for 24 hours.
LED indication Chart
IP65
Testing / Commissioning:
Ensure the load is connected
Enter the commissioning date on battery pack and onnect the
battery
Switch on the unswitched supply – Check that the green charge LED
illuminates
Switch on the maintained supply – Check that the fitting illuminates as
normal
Switch off the maintained supply
Switch off the unswitched supply – Check that the green charge led
extinguishes and the fitting illuminates
Switch on the unswitched supply
It is recommended that the batteries are renewed every 6 years.
The fitting is equipped with non-replaceable LED.
Self-Test Function:
A Function Test automatically runs every 28 days. During this test the
fitting is switched into emergency mode for 1 minute. During the test
the battery discharge current is checked.
A Full Duration Test automatically runs every 364 days. During this
test the fitting is switched into emergency mode for 3 hours . During
the test the battery discharge current and battery voltage is checked
CB5S fitting
c
Disassembling the CB5S fitting
4x Press to
release
Light source and LED indicator are connected,
!
be careful during opening
Connections for Maintained or Self-Test version
3
4x to
release reflector
4x
I
II

Advertisement

loading

Summary of Contents for Liteplan CB5S/3W/M3

  • Page 1 CB5S fitting CB5S/3W/M3 CB5S/3W/ST Technical Specification: Testing / Commissioning: Supply Voltage: 220-240V AC 50/60Hz Ensure the load is connected Insulation Class: II Enter the commissioning date on battery pack and onnect the Ingress Protection: IP65 battery Emergency Duration: 3 hours Switch on the unswitched supply –...
  • Page 2 Connections for Non-Maintained or Self-Test version Assembly instruction Push to lock 8x click Light source connection Dimensions Mounting details Additional guidelines Guidelines for installation Ensure a permanent supply to connection L Ensure a switched supply connection L1 For Non-Maintained use only L, do not connect to L1 Ensure correct polarity of the battery The drawing in the fitting may vary to the actual product, connect as per label on fitting.

This manual is also suitable for:

Cb5s/3w/st