Download Print this page
Zamel EXTA ASM-02 Instruction Manual

Zamel EXTA ASM-02 Instruction Manual

Staircase lighting timer

Advertisement

Quick Links

STAIRCASE LIGHTING TIMER ASM-02
DESCRIPTION
The staircase lighting time delay
switch ASM-02 is used to control lighting
devices on staircases and corridors. After
releasing the system it switches on the
lighting for the preset time by the user.
After that it switches off automatically.
The operating time can be adjusted from
2 s to 10 min by means of the potentio-
meter placed on the front panel of the
device. The device is equipped with an
anti-blocking function. The staircase li-
ghting time delay switch ASM-02 can be
used as standard time delay relay.
FEATURES
● Staircase lighting control,
● operating time adjustment from 2 sec
to 10 min,
● power supply indicator – red LED,
● cooperation with monostable push-
buttons equipped with illumination
lamps,
● anti blocking function,
● cooperation with 4-wire installation,
● voltage relay output - one NO contact
max 16 A capacity,
● monomodular casing,
● TH 35 DIN rail installation.
The device is designed
for one-phase instal-
lation and must be in-
stalled in accordance
with
standards
CAUTION
in a particular country.
The device should be
connected according to the details inc-
luded in this operating manual. Installa-
tion, connection and control should be
carried out by a qualified electrician staff,
who act in accordance with the service
manual and the device functions. Disas-
sembling of the device is equal with a
loss of guarantee and can cause electric
shock. Before installation make sure the
connection cables are not under voltage.
The cruciform head screwdriver 3,5 mm
should be used to instal the device. Im-
proper transport, storage, and use of the
device influence its wrong functioning.
It is not advisable to instal the device in
the following cases: if any device part is
missing or the device is damaged or de-
formed. In case of improper functioning
of the device contact the producer.
Zakład Mechaniki i Elektroniki
ZAMEL sp.j.
J.W. Dzida, K. Łodzińska
ul. Zielona 27, 43-200 Pszczyna, Poland
Tel. +48 (32) 210 46 65, Fax +48 (32) 210 80 04
www.zamelcet.com, e-mail: marketing@zamel.pl
TECHNICAL PARAMETERS
Input (supply) terminals: L, N
Input voltage tolerance: from -15 to +10 %
Rated power consumption: 35 mA
Release control current: 300 µA
Time adjustment range: from 2 sec to 10 min (rotational potentiometer)
Time accuracy adjustment: ±10 %
Time repeatability adjustment: ±5 %
Power/relay supply indicator: red LED
Output relay parameters: 1NO - 16 A / 250 V AC1 4000 VA
Number of terminal clamps: 8
Section of connecting cables: from 0,2 to 2,50 mm
Ambient temperature range: from -20 to +45
Overvoltage category: II
Rated impulse withstand voltage: 1 kV (PN-EN 61000-4-5)
Dimensions (height / width / depth): monomodular (17,5 mm) 90x17,5x66 mm
Reference standards: PN-EN 60669-1; PN-EN 60669-2-1
APPEARANCE
Input supply terminal (L)
valid
Power/relay supply indicator
Output (load) relay
terminals (11,11,14)
ASM-02
Input rated voltage: 230 V~
Nominal frequency: 50 / 60 Hz
Release terminals: IN, IN, IN
Operating position: free
Mounting: TH35 rail (PN-EN 60715)
Protection degree: IP20 (PN-EN 60529)
Protective class: II
Pollution degree: 2
Weight: 76 g
PN-EN 61000-4-2,3,4,5,6,11
INSTRUCTION MANUAL
2
C
o
Input supply terminal (N)
Release terminals
(IN,IN,IN)
VER. 001_16.02.2009