11. Recharge the battery using a method indicated in section
12.1 or 12.2 or 12.3.
• Adjust the electrolyte level at a current of 0.2*I
to 10 minutes prior to end of the charge methods, 12.1, 12.2,
and 12.3
• Afterwards measure the voltage on each cell prior to the end of
charge at 0.2*I 1 .
Requirement: cell voltage shall be ≥ 1.56 V
• Record the values in the log book.
NOTE
If the battery has to be charged below 0°C, apply 7 hours
charge at 0.2*I
.
1
ATTENTION:
• Don't charge the battery with currents higher than I
• Do not apply method 12.3, if the battery cannot be fully
supervised.
12.1 IUI charge – method (Appendix 1)
• Charge the battery at I
times number of cells and charge for 2 hours at 0.2*I
• After about 1 hour charge, check that battery has reached
the voltage level to switch the charge current to 0.2*I
12.2 I charge method (Appendix 2)
• Charge the fully discharged battery for seven hours at 0.2*I
12.3 II charge method (Appendix 3)
• Charge the fully discharged battery with parameters selected
from the table below and afterwards charge for two hours at
0.2*I
1
• Check battery current switching to 0.2*I
time presented in the table below.
current
0.4*I
1
0.6*I
1
0.8*I
1
13. Stand the battery between 1 hour and 24 h (maximum) and then
refit the vent.
14. Fit the lid onto the case.
15. Release the battery to service, if required in accordance with
Task 3.3.
The document reference is online, please check the correspondence between the online documentation and the printed version.
15 minutes
1
until voltage has increased to 1.55V
1
1
1
at the stage 1(max)
1
Stage 1 time (max)
180
120
90
In case cells fail this requirement, contact the supplier.