Control unit STG 1.2
for DRM ceiling smoke detector / DKM manual call point – bus compatible
Technical data
Supply voltage:
24 V AC + / -10%
24 V DC +15% / -10%
Power consumption:
250 mA (normal operation)
I
max
I
max
Relay outputs:
Alarm:
1 changeover contact
240 V AC / 30 V DC, 8 A
1 NC
240 V AC / 30 V DC, 8 A
Contamination:
1 changeover contact
400 V AC / 300 V DC, 6 A
Failure:
1 changeover contact
400 V AC / 300 V DC, 6 A
Service:
1 changeover contact
(service mode)
400 V AC / 300 V DC, 6 A
Notifications:
Display:
Plain text display status
DRM / DKM, configuration
Alarm:
red LED
Contamination:
yellow LED
Failure:
yellow LED
Operation:
green LED
Housing:
plastic ABS
Dimensions (W x H x D):
160 x 85 x 50 mm
Installation:
DIN-rail, panel
Protection class:
IP20
Ambient temperature:
0 °C to 50 °C
Connection:
spring terminals 0.5 – 2.5 mm²
Function
Up to 99 type DRM 3.3 or DRM 3.3-N/ DKM 3.3 ceiling smoke
detector or manual call points can be monitored by the STG con-
trol unit. The STG communicates with its connected detectors
2.5 A (alarm – 20 detectors)
6.2 A (0.02 s short circuit)
Can connect up to 99 DRM 3.3 or DRM 3.3-N
ceiling smoke detectors / DKM 3.3 manual call
points
Possible to query each detector as to status
and contamination
Large LCD display and 4 additional LEDs
RS485 Mod-Bus interface for informal
transmissions to the building management
system (BMS)
4 changeover contacts for alarm, failure,
service and contamination
1 NC for alarm
Monitoring for short circuits and cable breaks
by way of their security monitored system ring buses. Smoke
alarms, failure and contamination messages are all forwarded
from the detectors to the STG and shown on a display. This
makes it possible for a technician or custodian to supervise all
the connected detectors at a glance. The STG has one changeo-
ver relay each for alarm, contamination, failure and service mode
signalling. With the alarm message there is a relay available
which serves as an NC contact. With this relay the messages can
be reported to a central building management system (BMS).
The STG 1.2 additionally has an RS-485 interface to the BMS,
which also exports all of this data including the status of indivi-
dual detectors via a Modbus RTU protocol. With this interface it
is also possible to evaluate the STG via PLC control or a PC.
Important note: In addition, please note the separate
DRM / DKM data sheets.
If an alarm occurs at one or more connected detectors, the red
LED lights up on the STG, a message is issued to the STG display,
and the corresponding NC contact and changeover contact at
the STG drop out. By pressing the reset button the relay contact
can be restored, but the corresponding alarm must be termina-
ted/disabled first. In case of failure, connection problems as well
as contamination of one or more of the detectors, the yellow
contamination LED on the STG lights up and the corresponding
changeover relay of the STG drops out. If no connection to a
duct smoke detector can be made, a failure message appears
on the STG. If a new detector is connected in the service mode,
a corresponding message appears on the display. If the STG is
in service mode the service relay drops out. Failure and alarm
messages of the connected detectors must be acknowledged
once more through the STG "alarm /reset" button.
Fire Protection | Data sheet No. 43104 | Version 02-2016 | 1 | 8

Advertisement

Table of Contents
loading

Summary of Contents for Oppermann Regelgeräte STG 1.2

  • Page 1 (BMS). (service mode) 400 V AC / 300 V DC, 6 A The STG 1.2 additionally has an RS-485 interface to the BMS, Notifications: which also exports all of this data including the status of indivi-...
  • Page 2: Operation

    Operation smoke detectors) are displayed. Failure Alarms and error messages are self-sustaining and must be The STG 1.2 has two menu levels available: acknowledged once more on the STG (with the alarm / reset button) after correction. • Home menu: •...
  • Page 3: Electrical Connection

    Control unit STG 1.2 Electrical connection Work on electrical systems or equipment must be carried out only by a qualified electrician or by instructed personnel under the direction and supervision of a qualified electrician according to electrotechnical regulations. Please ensure to connect the current ceiling smoke detector model. The older version, type DRM 3.3, has been replaced by version DRM 3.3-N.
  • Page 4 Function Start address Number of registers (1-126) To receive a message from the STG 1.2, 8 bytes must be sent: the STG’s address, function, start address, number of registers and finally the redundancy check. Byte 4 and Byte 5: Byte 0: Number of registers (1 register = 2 bytes), which are read out.
  • Page 5 At the outset the address of the STG 1.2 and the query function are always returned. Then the designation follows regarding the number of databytes (2 bytes of data are incurred per register). Thereafter the data (register) follows. The register set is dependent on the query, and can vary between 1 and 125.
  • Page 6 Control unit STG 1.2 General status of the STG (Register address 0): Bit 15 - 8: Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Contamination Operation Contamination Alarm LED Failure LED Alarm relay...
  • Page 7 Control unit STG 1.2 Status for the detector: The status for each detector can be found at the following address: Address: 3 x n - 1 n: Address of the detector = (1 - 99) Bit 15 - 8 are always 0 and have no effect.
  • Page 8: Error Code

    The following error messages are generated by the STG 1.2: Error code = 1: Invalid function code. With the STG 1.2 only function code = 3 is valid. For all other functions, an error code is returned. Error code = 3: Data error.