Contents Introduction Section Page Soldo ® limit switch boxes are used as position indicators by means of an electrical signal, if Introduction they mount microswitches or sensors, or by means of analogue signal if they mount position Specification of the safety functions transmitters.
Type B – Position Transmitters protection is not compromised (available for models SS, SF, SB, HW, SX, SW, SY, SH, SI) Aggressive substances – ex. Acidic liquids or gases that The device is classified Type B according to IEC 61508-2.
Rotork Instruments Italy S.r.l. Via Portico, 17 24050 Orio al Serio (Bergamo) Italy Additional Warning for SIL boxes Tel +39 035 451161 FAX +39 035 531763 IOM00069_ENG Rev 0-4 http: //www.soldo.net e-mail: info.instruments- italy@rotork.com Configuration of the product 3. CONFIGURATION OF THE PRODUCT...
Page 5
Rotork Instruments Italy S.r.l. Via Portico, 17 24050 Orio al Serio (Bergamo) Italy Additional Warning for SIL boxes Configuration of the product Tel +39 035 451161 FAX +39 035 531763 IOM00069_ENG Rev 0-4 http: //www.soldo.net e-mail: info.instruments- Type A: Microswitch box configurations (continued) italy@rotork.com...
Page 6
Configuration of the product Position transmitter: Input 1 Sensor PR 5437 or Siemens TH300/320/420 Position transmitter: Input 1 Sensor Safety PLC PR 5437 or Siemens Safety PLC TH300/320/420 Position transmitter: Input 1 Sensor PR 5437 or Siemens TH300/320/420 View 19. Single transmitter 1oo1 operation View 20.
For the specific case of Pepperl+Fuchs proximity switch model SJ-3.5-S1N, switch’s lower The ambient operating temperature range of Siemens temperature working limit has been improved by Rotork Instruments Italy and assessed by the TH320/420 and PR 5437D is -40 to +80 °C; while Certification Body from -40°C (P+F declared value) down to -50°C performing the following tests:...
FMEDA of the product • Performing of cycling test at low and high temperature • Evaluation of field feedback Rotork Instruments Italy has an effective system to manage field feedbacks, including failure and root cause analysis. Type B Configuration λDU [1/h] λDD [1/h]...
Test and maintenance requirements Proof test Line monitoring Type A In order to properly detect the fault in the field wiring, additional resistance is required at the switch in the field. The proof test should be performed at least once a year, The addition of a 1 kΩ...
Page 10
Rotork Instruments Italy S.r.l. Rotork Instruments Italy S.r.l. Via Portico, 17 Via Portico, 17 24050 Orio al Serio (Bergamo) Italy 24050 Orio al Serio (Bergamo) Italy Additional Warning for SIL boxes Additional Warning for SIL boxes Tel +39 035 451161 FAX +39 035 531763...
A suitable configuration tool is able to show the diagnostic mes If the fault is caused by a sensor error or sensor wiring, and the correct output current will automatically be re-e corrected. If the fault is in the device itself (detected by internal dia transmitter will light constantly RED.
Page 12
As part of a process of on-going product development, Rotork reserves the right to amend and change specifications without prior notice. Published data may be subject to change. For the very latest version release, visit our website at www.rotork.com PUB109-157-00 The name Rotork is a registered trademark.